Plan Review Details - Permit 09040022
Plan Review Stops For Permit 09040022
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-06 Cont ID  
Sent By jwitmer Date 2009-07-06 Time 16:55 Rev Time 0.55
Received By jwitmer Date 2009-07-06 Time 16:30 Sent To PC
Notes
2009-07-06 16:35:43BUILDING PROVISO:
 FOR A SHINGLE ROOF THIS IS THE LEAST SLOPE THAT
 SHINGLES CAN BE APPLIED IS A 2:12 PITCH WITH A DOUBLE
 UNDERLAYMENTAND LAPPED 19 INCHES. R905.2.7.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-14 Cont ID  
Sent By jwitmer Date 2009-04-14 Time 13:04 Rev Time 1.55
Received By jwitmer Date 2009-04-14 Time 13:04 Sent To  
Notes
2009-04-14 14:40:50BUILDING PLAN REVIEW
 PERMIT: 09040022
 ADD: 1020 PASEO ANDORRA
 CONT: O/B SANTIAGO FERNANDEZ
 TEL: (561)835-1997
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 20079 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH THE 2009 SUPPLEMENTS. PLANS ALSO WILL BE
 REVIEWED TO THE 2007 EXISTING BUILDING CODE WITH 2009
 SUPPLEMENTS. PLEASE UPDATE PLANS
  
 2) 2007 EXISTING BUILDING CODE 506.2.2 A BUILDING THAT
 HAS SUSTAINED SUBSTANIAL STRUCTURAL DAMAGE TO THE
 ELEMENTS OF ITS LATERAL-FORCE RESISTING SYSTEM SHALL BE
 EVALUATED AND REPAIRED IN ACCORDANCE WITH THE
 APPLICABLE PROVISIONS OF SECTION 506.2.2.1 THROUGH
 506.2.2.3.
  
 506.2.2.1 EVALUATION . THE BUILDING SHALL BE EVALUATED
 BY A REGISTERED DESIGN PROFESSIONAL, AND THE EVALUATION
 FINDINGS SHALL BE SUBMITTED TO THE CODE OFFICIAL . THE
 EVALUATION SHALL ESTABLISH WHETHER THE DAMAGED
 BUILDING, IF REPAIRED TO ITS PREDAMAGED STATE, WOULD
 COMPLY WITH WITH THE PROVISIONS OF THE CODES THAT WERE
 IN EFFECT WHEN THE BUILDING WAS PERMITTED.WIND FORCES
 FOR THIS EVALUATION SHALL BE THOSE PRESCRIBED IN THE
 CODE THAT WERE IN EFFECT WHEN THE BUILDING WAS
 PERMITTED. PLEASE ALSO REVIEW 506.2.2.2 FOR EXTENT
 OFREPAIRS FOR COMPLIANT BUILDINGS AND 506.2.2.3.
 EXTENT OF REPAIRS FOR NONCOMPLIANT BUILDINGS.
  
 3) ADDITIONAL INFORMATION IS REQUIRED, THE PERMIT
 APPLICATION INDICATES THAT THTE OWNER IS PULLING THE
 REPAIR PERMIT FOR THE STRUCTURAL PORTION OF WORK. FOR
 THE ROOFING PERMIT THE OWNER HAS NOT SIGNED ON NOR HAS
 A ROOFING CONTRACTOR SIGNED THE BOTTOM PORTION OF THE
 PERMIT APPLICATION FOR A ROOFING PERMIT. THE TWO ISSUES
 AT HAND ARE :
 3A) PLANS INDICATE A 2/12 PITCH TO BE VERIFIED BY TRUSS
 MANUFACTURER. R905.2.7.
 3B) FOR A SHINGLE ROOF THIS IS THE LEAST SLOPE THAT
 SHINGLES CAN BE APPLIED IS A 2:12 PITCH WITH A DOUBLE
 UNDERLAYMENTAND LAPPED 19 INCHES. R905.2.7.
  
 4) SHEET A1 DOES NOT INDICATE ATTIC ACCESS PER SECTION
 R807.1.ATTIC ACCESS. BUILDINGS WITH COMBUSTIBLE CEILING
 OR ROOF CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M2) AND
 HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR MORE.
 PLANS FAIL TO INDICATETHE ROUGH-FRAMED OPENING SHALL
 NOT BE LESS THAN 22 INCHES BY 30 INCHES (559 MM BY 762
 MM) AND SHALL BE LOCATED IN A HALLWAY OR OTHER READILY
 ACCESSIBLE LOCATION. A 30-INCH (762 MM) MINIMUM
 UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT SOME POINT ABOVE THE ACCESS OPENING. SEE
 SECTION M1305.1.3 FOR ACCESS REQUIREMENTS WHERE
 MECHANICAL EQUIPMENT IS LOCATED IN ATTICS.
  
 5) ROOF VENTILATION R806.2 MINIMUM AREA. THE TOTAL NET
 FREE VENTILATING AREA SHALL NOT BE LESS THAN 1/150 OF
 THE AREA OF THE SPACE VENTILATED EXCEPT THAT REDUCTION
 OF THE TOTAL AREA TO 1/300 IS PERMITTED, PROVIDED THAT
 AT LEAST 50 PERCENT AND NOT MORE THAN 80 PERCENT OF THE
 REQUIRED VENTILATING AREA IS PROVIDED BY VENTILATORS
 LOCATED IN THE UPPER PORTION OF THE SPACE TO BE
 VENTILATED AT LEAST 3 FEET (914 MM) ABOVE THE EAVE OR
 CORNICE VENTS WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. AS AN
 ALTERNATIVE, THE NET FREE CROSS-VENTILATION AREA MAY BE
 REDUCED TO 1/300 WHEN A VAPOR BARRIER HAVING A
 TRANSMISSION RATE NOT EXCEEDING 1 PERM (5.7 ?? 10-11
 KG/S ?? M2 ?? PA) IS INSTALLED ON THE WARM-IN-WINTER
 SIDE OF THE CEILING.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-04 Cont ID  
Sent By dpalmer Date 2009-07-04 Time 10:22 Rev Time 0.00
Received By dpalmer Date 2009-07-04 Time 10:21 Sent To  
Notes
2009-07-04 10:22:33** REDLINED PLANS**
  
 1) NOTE: LOAD CALCULATIONS INDICATE TWO ELECTRICAL
 WATER HEATERS YET THE PLANS AND THE PANEL SCHEDULE ONLY
 INDICATE ONE UNIT. PER 422.13 THE LOAD FOR WATER
 HEATERS ARE TO BE SHOWN AT 125%. HOWEVER SINCE THERE IS
 AN EXTRA WATER HEATER FIGURED WHEN NOT INSTALLED LOAD
 IS OK>
  
 2) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCES. THE
 WATER HEATER IN LAUNDRY ROOM IS SHOWN IN THE MINIMUM
 WORKING SPACE REQUIRED FOR ELECTRICAL PANEL. THIS NEEDS
 TO MEET SECTION AS THIS IS A LIFE SAFETY HAZARD. PLEASE
 RELOCATE WATER HEATER OR ADJUST LOCATION TO MEET
 MINIMUM.
  
 ** THE ABOVE COMMENTS ALONG WITH ANY OTHER CHANGES
 DURING THE ROUGH IN PROCESS NEED TO BE REVISED BEFORE
 ROUGH ELECTRICAL INSPECTION. IF THERE ARE ANY QUESTIONS
 ON THE PROCESS OR WHAT NEEDS TO BE REVISED, PLEASE
 CALL.
 **IF REAR OPEN AREA IS REVISED TO CLOSE IN AS PART OF
 THE HOUSE, THE SERVICE WILL BE REQUIRED TO BE
 RELOCATED. MAY NOT HAVE THE SERVICE/ METER LOCATED
 INSIDE THE HABITABLE SPACE INSIDE DWELLING AREA.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-10 Cont ID  
Sent By dpalmer Date 2009-04-10 Time 16:39 Rev Time 0.00
Received By dpalmer Date 2009-04-10 Time 16:39 Sent To  
Notes
2009-04-10 16:39:11** DENIED**
  
 1) NOTE: PLANS ARE STATING ALL DESIGNS PER 2004 FBC.
 ANY PLANS SUBMITTED FOR PER AFTER MARCH 1ST, 2009 MUST
 BE UNDER THE NEW 2007 FBC WITH 2009 AMENDMENTS.
 PLEASE BE SURE THE FOLLOWING CODES ARE STATED ON PLANS
 AT A MINIMUM.
 2005 NFPA-70
 2002 NFPA-72
 2007 FBC RESIDENTIAL
  
 2) NOTE: PLANS STATE SMOKE DETECTORS. SMOKE DETECTORS
 ARE UNITS WHICH ONLY DETECT AND DO NOT SOUND. PLEASE
 SEE DEFINITIONS IN NFPA-72 2002. PLEASE KNOW THAT SMOKE
 ALARMS ARE DEVICES WHICH DETECT AND SOUND. IF THESE ARE
 INDEED SMOKE DETECTORS, PLEASE COMPLETE PLANS WITH FIRE
 ALARM PANEL, SOUNDING DEVICES.
 ** PLEASE ALSO SHOW COMPLETE LAYOUT OF EXISTING
 DWELLING. ALL EXISTING LOCATIONS MUST BE BROUGHT UP TO
 CURRENT NFPA-72 11.5.1 FOR SMOKE ALARMS.
 PLEASE SEE FBC R313.
 ** PLEASE ALSO SEE 210.12 OF THE NEC AS THIS REQUIRES
 ARC FAULT PROTECTION.
  
 3) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR APPLIED SCOPE
 OF WORK PER 2005 NEC.
 THE NEC 2005 WAS GIVEN IN GENERAL AS THERE ARE MANY
 CODE SECTION WHICH NEED TO BE MET ON MINIMUM DESIGN.THE
 PERMIT APPLICATION STATES COMPLETE RE-WIRE HOWEVER
 PLANS DO NOT SHOW ANY LIGHTING, LIGHTING CONTROLS PER
 210.70.
 NO CIRCUITING OR PANEL SCHEDULES PER 408.4 PLEASE BE
 SURE ALL REQUIRED CIRCUITING PER 210.52,210.11,220 ARE
 SHOWN AND LISTED.
 PLEASE SEE 210.52 FOR MISSING RECEPTACLES.
  
 4) NOTE: PLEASE BE SURE TO INCLUDE ARC FAULT PROTECTION
 210.12
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-06 Cont ID  
Sent By jwitmer Date 2009-07-06 Time 16:30 Rev Time 0.00
Received By jwitmer Date 2009-06-25 Time 08:14 Sent To  
Notes
2009-06-25 08:19:58RESIDENTIAL BOARD # 8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-04-20 Time   Rev Time 0.00
Received By adarroug Date 2009-04-06 Time 09:05 Sent To  
Notes
2009-04-06 09:11:38TO "R13"

Review Stop Z ZONING
Rev No 1 Status N Date 2009-04-20 Cont ID  
Sent By mcruz Date 2009-04-20 Time 08:50 Rev Time 0.00
Received By mcruz Date 2009-04-20 Time 08:49 Sent To  
Notes
2009-04-20 08:50:53*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  