Plan Review Details - Permit 09040011
Plan Review Stops For Permit 09040011
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-18 Cont ID  
Sent By shill Date 2009-06-18 Time 07:53 Rev Time 0.00
Received By shill Date 2009-06-18 Time 07:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-04-09 Cont ID  
Sent By shill Date 2009-04-09 Time 10:55 Rev Time 0.00
Received By shill Date 2009-04-09 Time 10:55 Sent To  
Notes
2009-05-06 16:07:37PLANNING AND ZONING: **** FAILED ****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THE PROJECT IS PART OF THE ST. MARY'S CSPD AND IS
 CURRENTLY BEING REVIEWED FOR A MINOR PD AMENDMENT DUE
 TO ALTERATION AND RELOCATION OF LANDSCAPING AND NEW
 FOUNTAIN. UPON A SITE VISIT IT WAS DISCOVERED THAT
 TREES THAT WERE PREVIOUSLY APPROVED AND PLANTED HAVE
 BEEN REMOVED FROM THE SITE. THEREFORE, A
 TREE/ALTERATION PERMIT WILL HAVE TO BE SUBMITTED TO
 ROBERT KUSSNER, LANDSCAPE PLANNER IN THE PLANNING AND
 ZONING DEPARTMENT PRIOR TO THE APPROVAL OF THIS
 BUILDING PERMIT AND THE MINOR AMENDMENT APPLICATION.
 REFER TO LANDSCAPE COMMENTS FOR ADDITIONAL INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-05-21 Cont ID  
Sent By dpalmer Date 2009-05-21 Time 09:58 Rev Time 0.00
Received By dpalmer Date 2009-05-21 Time 09:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-16 Cont ID  
Sent By dpalmer Date 2009-04-16 Time 11:33 Rev Time 0.00
Received By dpalmer Date 2009-04-16 Time 11:33 Sent To  
Notes
2009-04-16 11:38:53** DENIED REVIEW**
  
  
  
 1) NOTE: THE PERMIT APPLICATION WAS MADE AFTER MARCH
 1ST, 2009 WHICH PLACES THE PROJECT UNDER THE 2007 FBC
 WITH 2009 GLITCH AMENDMENTS. PLANS STATE 2004 FBC.
 PLEASE STATE THE FOLLOWING AT A MINIMUM FOR THIS REVIEW
 TRADE ON ELECTRICAL PLANS.
 2007 FBC W/2009 REVISIONS.
 2005 NFPA-70
  
 ** THIS AHJ DOES NOT HAVE THE AUTHORITY TO REVISE AND
 CHANGE CODE DESIGNS ON PLANS WHICH ARE DONE AND SIGNED
 AND SEALED BY THE LICENSED DESIGNED PROFESSIONAL.
  
 2) NOTE: PLEASE INDICATE CIRCUITING AND LOCATION IN
 WHICH THESE CIRCUITS ARE BEING FED.
 408.4, 310.16, 240.4
  
 3) NOTE: PLEASE SEE 680.50, 56, 54, ETC FOR REQUIRED
 GROUNDING AND PROTECTION. SOME INFORMATION IS ON PLANS
 HOWEVER ATTACHMENT LOCATIONS ARE NOT SHOWN AND MISSING
 SOME OTHER ATTACHMENTS.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2009-05-29 Cont ID  
Sent By mawillia Date 2009-05-29 Time 13:58 Rev Time 0.00
Received By mawillia Date 2009-05-29 Time 13:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-05-15 Cont ID  
Sent By rmcdouga Date 2009-05-15 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2009-05-15 Time 16:03 Sent To  
Notes
2009-05-15 16:06:01TO C7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-05-06 Time   Rev Time 0.00
Received By adarroug Date 2009-04-06 Time 15:09 Sent To  
Notes
2009-04-06 15:14:47TO "C9"

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2009-05-27 Cont ID  
Sent By rkussner Date 2009-05-27 Time 12:17 Rev Time 0.00
Received By rkussner Date 2009-05-27 Time 12:16 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2009-05-22 Cont ID  
Sent By rkussner Date 2009-05-22 Time 16:29 Rev Time 0.00
Received By rkussner Date 2009-05-22 Time 16:29 Sent To  
Notes
2009-05-22 16:31:16***LANDSCAPE REVIEW FAILED***
  
 1. PROVIDE TWO (2) SETS OF LANDSCAPE PLANS WITH THIS
 SUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-05-06 Cont ID  
Sent By rkussner Date 2009-05-06 Time 13:50 Rev Time 0.00
Received By rkussner Date 2009-05-06 Time 13:50 Sent To  
Notes
2009-05-06 13:53:09***LANDSCAPE REVIEW FAILED***
  
 1. APPLY FOR A TREE ALTERATION PERMIT THROUGH PLANNING
 AND ZONING.
  
 2. PROVIDE TWO (2) SETS OF LANDSCAPE PLANS WITH THIS
 SUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-05-28 Cont ID  
Sent By kstevens Date 2009-05-28 Time 09:59 Rev Time 0.00
Received By kstevens Date 2009-05-28 Time 09:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-04-22 Cont ID  
Sent By kstevens Date 2009-04-22 Time 10:57 Rev Time 0.00
Received By kstevens Date 2009-04-22 Time 10:57 Sent To  
Notes
2009-04-22 13:44:28DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 ANSI/APSP-7
 FBC-2007(4) CHAPTER 1
  
 1. SHT A-1 GENERAL NOTES #1 INDICATES FBC-2004.
 APPLICATIONS SUBMITTED FOR PERMIT ON OR AFTER MARCH 1,
 2009 FALL UNDER THE FBC-2007 WITH 2009 SUPLEMENTS CODE.
 THE CATCH BASIN SHALL BE DESIGNED & REFERENCED PER THE
 CORRECT CODE CYCLE. SECTION 106.1.1.
  
 2. SHT A-1 DETAIL A SHOW THE MAIN DRAINS IN THE DETAIL.
 PLAN VIEW AND PLUMBING PLAN SHOWS THE DRAINS ON EACH
 SIDE OF THE CATCH BASIN, BUT DETAIL A DOES NOT SHOW THE
 DRAINS. SECTION 106.1.2. (MORE INFORMATION REQUIRED).
  
 3. SHOW THE CALCULATIONS & PIPE SIZES TO EACH MAIN
 DRAIN BRANCH LINE, (MAXIMUM 3 FT/SEC), (MAXIMUM 6
 FT/SEC IF ONE LINE OF THE PAIR IS BLOCKED). ALL OTHER
 SUCTION VELOCITIES SHALL BE 6 FT/SEC.
  
 4. SUBMIT MANUF. SPECIFICATIONS FOR THE LISTED SUCTION
 OUTLET COVERS/GRATES. ANSI/APSP-7 SECTION4.5.
  
 5. SHT A-2 GENERAL NOTES #1 STATES THE POOL SHALL
 CONFORM TO SECTION 424.2 PRIVATE SWIMMING POOLS. SINCE
 THIS POOL IS NOT LOCATED IN A RESIDENTIAL AREA, THE
 CONFORMATCE REQUIREMENTS SHALL BE PER SECTION 424.1
 PUBLIC POOLS/CATCH BASIN. PLEASE DELETE ALL REFERENCES
 TO RESIDENTIAL POOLS AND SHOW REFERENCE TO PUBLIC
 SWIMMING POOLS. SECTION 106.1.1.
  
 6. SHT A-2 PIPING DIAGRAM DOES NOT REFLECT THE PLUMBING
 PLAN SHOWN ON SHT A-1, NOR DOES IT REFLECT THE VENT
 ARRANGEMENT SHOWN ON SHT A-2. THE CONNECTION OF THE
 DRAIN LINE SHALL BE IN THE CENTER OF THE MAIN DRAINS
 AND THE VENT IS NOT SHOWN. PLEASE CORRELATE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2009-05-27 Cont ID  
Sent By lfranco Date 2009-05-27 Time 16:36 Rev Time 0.00
Received By lfranco Date 2009-05-27 Time 16:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2009-05-22 Cont ID  
Sent By lfranco Date 2009-05-22 Time 16:51 Rev Time 0.00
Received By lfranco Date 2009-05-22 Time 16:51 Sent To  
Notes
2009-05-22 16:59:02PLANNING AND ZONING: ***** FAILED****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THE PROJECT IS PART OF THE ST. MARY'S CSPD AND IS
 CURRENTLY BEING REVIEWED FOR A MINOR PD AMENDMENT DUE
 TO ALTERATION/RELOCATION OF LANDSCAPING AND ADDITION OF
 FOUNTAIN.
  
 RE-SUBMITTAL - A LANDSCAPE PLAN WAS NOT SUBMITTED FOR
 REVIEW. SEE LANDSCAPE COMMENTS FOR ADDITIONAL
 INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-05-06 Cont ID  
Sent By lfranco Date 2009-05-06 Time 14:49 Rev Time 0.00
Received By lfranco Date 2009-05-06 Time 14:49 Sent To I
Notes
2009-05-06 16:19:01PLANNING AND ZONING: ***** FAILED****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THE PROJECT IS PART OF THE ST. MARY'S CSPD AND IS
 CURRENTLY BEING REVIEWED FOR A MINOR PD AMENDMENT DUE
 TO ALTERATION/RELOCATION OF LANDSCAPING AND ADDITION OF
 FOUNTAIN . UPON A SITE VISIT, IT WAS DISCOVERED THAT
 CERTAIN TREES THAT WERE PREVIOUSLY APPROVED AND PLANTED
 HAVE BEEN REMOVED FROM THE SITE. AN
 ALTERATION/RELOCATION PERMIT WILL HAVE TO BE APPLIED
 FOR SHOWING THESE REVISIONS WITH ROBERT KUSSNER,
 LANDSCAPE PLANNER IN THE PLANNING AND ZONINGDEPARTMENT,
 PRIOR TO APPROVAL OF THE BUILDING PERMIT AND MINOR
 AMENDMENT APPLICATION. SEE LANDSCAPE COMMENTS FOR
 ADDITIONAL INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  