Plan Review Details - Permit 09030589
Plan Review Stops For Permit 09030589
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-07 Cont ID  
Sent By mjacobs Date 2009-04-07 Time 13:16 Rev Time 0.00
Received By mjacobs Date 2009-04-07 Time 13:16 Sent To  
Notes
2009-04-07 13:16:51BUILDING PLAN REVIEW
 PERMIT: 09030589
 ADD: 801 S. OLIVE AVE #113
 CONT: MICHELLE FRIEDMAN
 TEL: (561)901-8855
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) THE PLANS SHALL INDICATE THE TYPE OF CONSTRUCTION
 PER CHAPTER 6 AND TABLE 503, THE USE AND OCCUPANCY PER
 CHAPTER 3 AND THE OCCUPANT LOAD PER TABLE 1004.1.1 THIS
 INFORMATION IS REQUIRED SO THAT ANY ADDITIONAL
 CONSTRUCTION WILL BE IN ACCORDANCE WITH THE ORIGINAL
 BUILDING TYPE. STATE CLEARLY ON THE PLANS THE USE OF
 THE SPACE; OFFICE/BUSINESS OR RESIDENTIAL USE?
  
 4) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2007 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH THE 2009 SUPPLEMENTS.
  
 5) 2007 FBC (EXISTING) 401.4 A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF
 THIS CODE. THIS INFORMATION SHALL BE INDICATED ON THE
 PLANS.
  
 6) PER FLORIDA STATUTES, 481.229 EXEMPTIONS FROM
 ARCHITECTURAL LICENSURE ONLY APPLY TO ONE AND TWO
 FAMILY RESIDENCES (R3) NOT MULTI-FAMILY (R2) OR
 BUILDINGS OVER $25.000, THEREFORE, DRAFTSMAN QUALITY
 DRAWINGS ARE REQUIRED TO BE DRAWN BY A LICENSED DESIGN
 PROFESSIONAL. A LICENSE CONTRACTOR IS REQUIRED TO
 PERFORM THE WORK INDICATED ON THE APPLICATION. THE
 DRAWINGS SUBMITTED ARE INADEQUATE; PLANS DRAWN WITH
 PENCIL ARE NOT ACCEPTABLE. 106.1.3* THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 STANDARDS FOR PLANS AND SPECIFICATIONS IN ORDER TO
 PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. THE
 POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED RECORD
 MANAGEMENT. THE PLANS WHICH CONTAIN ITEMS TAPED TO THE
 SHEET AND PENCIL DRAWN INFORMATION DOES NOT MEET THE
 ABOVE REQUIREMENTS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE.
  
 7) INDICATE THE TYPE OF 2X4 WHICH WILL BE USED FOR THE
 SOLE PLATE ON THE PLANS. THE TYPE OF WOOD USED SHALL
 MEET THE REQUIREMENTS OF FBC 2007 SECTION 603.
  
 8) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL COST INCLUDING DESIGNER FEES
 AND ALL WORK INVOLVED WITH THE PROJECT. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES 108.3*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6731
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-13 Cont ID  
Sent By dpalmer Date 2009-04-13 Time 12:16 Rev Time 0.00
Received By dpalmer Date 2009-04-13 Time 12:16 Sent To  
Notes
2009-04-13 12:16:38** DENIED**
  
 1) NOTE: PLEASE BE SURE TO SUBMIT TWO COMPLETE SETS OF
 PLANS BOUND TOGETHER.
 PLEASE BE SURE ALL OF THE FOLLOWING MINIMUM CODES ARE
 STATED ON PLANS.
 2007 FBC W/ 2009 REVISIONS.
 2006 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: THE SCOPE OF WORK AS APPLIED MAY NOT BE DONE
 AS AN OWNER/BUILDER PER FS 489. THIS HAS BEEN CONFIRMED
 WITH THE LAW DEPARTMENT AND THE STATE OF FLORIDA
 ATTORNEY GENERALS OFFICE.
 PLEASE OBTAIN LICENSED CONTRACTORS PER FS 489.
  
 3) NOTE: PLEASE SUBMIT COMPLETED PLANS FOR ALL CURRENT
 CODES IN AFFECT AFTER MARCH 1ST, 2009. PLEASE SEE
 CHAPTER 3 OF THE FBC TO STATE USE AND OCCUPANCY.
 PLANS STATE SKINCARE HOWEVER USE FOR ITEMS SUCH AS
 OTHER BEAUTY NAIL CARE ETC WILL AFFECT MINIMUM CODE
 COMPLIANCE DESIGNS.
  
 4) NOTE: LIGHTING CONTROLS PER 13-415.1.AB.1.1,.1.2
 REQUIRED.
  
 5) NOTE: PRESCRIPTIVE LIGHTING PERFORMANCE NEEDS TO BE
 SHOWN PER 13-415.AB.5. THIS IS ONLY FOR NEW BEING
 INSTALLED.
 THE PLANS DO NOT INDICATE SPECIFIC LIGHTING.
  
 6) NOTE: PLEASE COMPLETE CIRCUITING TO NEW RECEPTACLES
 AND LIGHTING. PLEASE INDICATE WHERE THEY ARE BEING FED
 FROM. WHAT SIZE CIRCUIT, OVER CURRENT PROTECTION ETC.
 408.4, 240.4, 310.16
  
 7) NOTE: PLANS TO BE SUBMITTED SHALL BE DESIGNED BY
 REQUIRED DESIGNER PER FS 471.003, 481.221. AS THE SCOPE
 MAY BE REVISED ALONG WITH VALUATION ON THE FOLLOWING
 COMMENT THE PLANS SUBMITTED DO NOT MEET MINIMUM
 REQUIREMENTS.
 PLEASE ALSO SEE FBC 106.1.1, 106.1, ETC AS PLANS
 SUBMITTED MAY NOT BE CUT AND PASTE OF PIECES OF OTHER
 PLANS, DRAWN IN PENCIL ETC.
 ONE SET OF PLANS SUBMITTED ARE BEING RETAINED BY THIS
 OFFICE.
  
 8) NOTE: THE APPLIED VALUE IS LOW FOR THE SCOPE OF WORK
 SHOWN ON PLANS WHICH WILL ALSO BE REQUIRED TO MEET
 MINIMUM CODE.
 THE VALUE FOR COMPLETE SCOPE MUST INCLUDE DESIGN COSTS,
 LABOR, EQUIPMENT, MATERIALS EVEN IF ANY OF THESE ITEMS
 ARE OWNER SUPPLIED.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-09 Cont ID  
Sent By mawillia Date 2009-04-09 Time 16:15 Rev Time 0.00
Received By mawillia Date 2009-04-09 Time 15:21 Sent To  
Notes
2009-04-09 16:15:37*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE
 (BASED ON NFPA 101 - LIFE SAFETY CODE - 2006 EDITION
 AND NFPA 1 - UNIFORM FIRE CODE - 2006 EDITION - SHALL
 BE REFERENCED.
  
 3. THE PROJECT SITE ADDRESS, INCLUDING UNIT NUMBER,
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 4. LIST THE PROJECT SITE'S OCCUPANCY TYPE (I.E.
 BUSINESS, RESIDENTIAL, MERCANTILE), OCCUPANT LOAD, AND
 OTHER PERTINENT INFORMATION NECESSARY FOR A THOROUGH
 PLAN REVIEW.
  
 5. SPECIFY THE INTERIOR FINISH MATERAILS FOR THE NEW
 WALL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6. PLANS INDICATE THAT A NEW DOOR TO THE EXISTING
 STAIRCASE WILL BE INSTALLED, PROVIDE WIDTH AND HEIGHT
 DIMENSIONS OF THE SAID DOOR.
  
 7. WILL THE PROJECT SCOPE OF WORK HAVE CAUSE FOR THE
 SPRINKLER HEADS TO BE REMODELED? THIS WRITER WAS UNABLE
 TO LOCATE SUCH DEVICES IN THE ORIGINAL FLOOR PLAN.
  
 8. PLANS INDICATE THAT SMOKE DETECTORS (SD) ARE
 INSTALLED. PLEASE BE ADVISED THAT SMOKE DETECTOR ARE
 TIED INTO THE BUILDING'S FIRE ALARM SYSTEM WHEREAS
 SMOKE ALARMS (SA) SHALL ONLY SOUND/ALERT THE OCCUPANT
 OF THE SAID DWELLING UNIT AND NOT ACTUATE THE
 BUILDING'S FIRE ALARM SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE COMMENTS WERE ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-15 Cont ID  
Sent By kstevens Date 2009-04-15 Time 15:14 Rev Time 0.00
Received By kstevens Date 2009-03-31 Time 13:45 Sent To  
Notes
2009-03-31 13:45:33TO "B9"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date 2009-04-15 Cont ID  
Sent By rregueir Date 2009-04-15 Time 10:43 Rev Time 0.00
Received By rregueir Date 2009-04-15 Time 08:44 Sent To  
Notes
2009-04-15 10:43:45REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PERMIT APPLICATION WAS SUBMITTED WITH NO CONTRACTOR
 (OWNER/BUILDER). A LICENSED CONTRACTOR IS REQUIRED TO
 APLY FOR A PERMIT AND PERFORM WORK IN THIS BUILDING IN
 ACCORDANCE WITH FS 489.103.
  
 2. BASED ON THE SUBMITTED PLANS, THIS APPEARS TO BE A
 CHANGE OF OCCUPANCY. THIS SPACE WAS CONSTRUCTED AND
 C.O. WAS ISSUED FOR THIS SPACE AS AN R-2 (RESIDENTIAL)
 OCCUPANCY. IT APPEARS THE PROPOSED NEW OCCUPANCY WOULD
 BE B (BUSINESS) IN ACCORDANCE WITH FBC-B 304.1. WHERE
 THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN
 EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO INCREASED MECHANICAL
 VENTILATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL, THE INTENT OF THE RESPECTIVE
 FLORIDA BUILDING CODE, MECHANICAL PROVISIONS SHALL BE
 COMPLIED WITH FOR THE NEW OCCUPANCY IN ACCORDANCE WITH
 FBC-EB 909.1. IF THE PROPOSED NEW USE IS TO BE A BEAUTY
 SALON OR NAIL SALON, THE VENTILATION REQUIREMENTS WOULD
 BE INCREASED IN ACCORDANCE WITH FBC-M TABLE 403.3.
 PLEASE SHOW ON PLANS HOW THE VENTILATION REQUIREMENTS
 FOR THE PROPOSED NEW OCCUPANCY CLASSIFICATION ARE TO BE
 PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-04-15 Cont ID  
Sent By kstevens Date 2009-04-15 Time 15:13 Rev Time 0.00
Received By kstevens Date 2009-04-15 Time 15:13 Sent To  
Notes
2009-04-15 15:14:37NO PLUMBING PLANS SUBMITTED, NO PLUMBING WORK
 INDICATED.