Plan Review Details - Permit 09030575
Plan Review Stops For Permit 09030575
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-05-20 Cont ID  
Sent By rmcdouga Date 2009-05-20 Time 09:07 Rev Time 0.00
Received By rmcdouga Date 2009-05-20 Time 09:07 Sent To  
Notes
2009-05-20 09:08:52BUILDING PROVISO
  
 NOTE: ADDITIONAL ENGINEERED DETAILS MAY BE REQUESTED BY
 THE BUILDING INSPECTOR TO ADDRESS SPECIFIC FIELD
 CONDITION REPAIRS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-08 Cont ID  
Sent By rmcdouga Date 2009-04-08 Time 09:09 Rev Time 0.00
Received By rmcdouga Date 2009-04-08 Time 09:08 Sent To  
Notes
2009-04-08 09:24:392007 FBC
 LEVEL II ALTERATION
  
 DENIED BY BUILDING
  
 1) UPDATE THE REFERENCES TO THE 2004 FBC IN THE GENERAL
 NOTES AND STRUCTURAL NOTES ON SHEET CVR-1 TO THE 2007
 FBC WHICH IS THE APPLICABLE CODE. SEE REDLINED PLAN.
  
 2) SUBMIT TWO (2) COPIES OF PRODUCT APPROVALS FOR THE
 ASPHALT ROOF SHINGLES. DCA RULE 9B-72
  
 NOTE: ADDITIONAL ENGINEERED DETAILS MAY BE REQUESTED BY
 THE BUILDING INSPECTOR TO ADDRESS SPECIFIC FIELD
 CONDITION REPAIRS.
  
 NOTE: A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 WILL BE REQUIRED.FS 713
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-04-07 Cont ID  
Sent By rmcdouga Date 2009-04-07 Time 08:47 Rev Time 0.00
Received By rmcdouga Date 2009-04-07 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-11-03 Cont ID  
Sent By btrobaug Date 2009-11-03 Time 06:49 Rev Time 0.00
Received By btrobaug Date 2009-11-03 Time 06:49 Sent To Z
Notes
2009-11-03 06:50:32TO ZONING./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-10-27 Cont ID  
Sent By shill Date 2009-10-27 Time 09:51 Rev Time 0.00
Received By shill Date 2009-10-27 Time 09:51 Sent To  
Notes
2009-10-27 09:52:03MECHANICAL REVISION TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-10-22 Cont ID  
Sent By kstevens Date 2009-10-22 Time 11:18 Rev Time 0.00
Received By kstevens Date 2009-10-22 Time 11:18 Sent To  
Notes
2009-10-22 11:18:38SENT TO ZONING/LANDSCAPE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-16 Cont ID  
Sent By kstevens Date 2009-09-16 Time 08:15 Rev Time 0.00
Received By kstevens Date 2009-09-16 Time 08:14 Sent To  
Notes
2009-09-16 08:15:38SENT TO RMCDOUGAL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-30 Cont ID  
Sent By rmcdouga Date 2009-04-30 Time 08:54 Rev Time 0.00
Received By rmcdouga Date 2009-03-31 Time 11:16 Sent To  
Notes
2009-03-31 11:16:36TO "R8"

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2009-11-03 Cont ID  
Sent By rkussner Date 2009-11-03 Time 17:50 Rev Time 0.00
Received By rkussner Date 2009-11-03 Time 17:50 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2009-10-22 Cont ID  
Sent By rkussner Date 2009-10-22 Time 16:02 Rev Time 0.00
Received By rkussner Date 2009-10-22 Time 16:02 Sent To  
Notes
2009-10-22 16:13:19***LANDSCAPE REVIEW FAILED***
  
 1. FOR SINGLE FAMILY HOMES, ONE TREE IS REQUIRED FOR
 1200 SQUARE FEET OF OPEN SPACE--NOT 1600 SQUARE FEET.
 FOUR (4) TREES ARE REQUIRED. THE EXISTING FICUS TREE
 CAN COUNT TOWARD MEETING THIS REQUIREMENT .
  
 2. PLEASE PROVIDE THE XERISCAPE DESIGN TABULATIONS.
  
 3. PLACE A NOTE ON THE PLAN THAT IRRIGATION WILL BE
 PROVIDED IN THE RIGHT-OF-WAY.
  
 4. TYPICALLY, A THREE (3) INCH LAYER OF MULCH IS
 APPLIED--NOT TWO (2) INCH. THE TREES AND SHRUBS SHALL
 BE PLANTED SLIGHTLY ABOVE GRADE AND THE THREE (3) INCH
 LAYER OF MULCH IS APPLIED OUTSIDE OF THE ROOTBALL. NO
 MORE THAN A ONE INCH LAYER OF MULCH SHALL BE APPLIED
 OVER THE ROOTBALL AND IT SHALL BE PULLED BACK FROM THE
 TRUNK.
  
 5. ALL EXISTING TREES AND SHRUBS TO REMAIN SHALL BE
 FLORIDA #1 GRADE OR THEY SHALL BE REPLACED. IF THE
 TREES DO NOT MEET THIS REQUIREMENT BUT COULD BE BROUGHT
 UP TO THIS STANDARD BY CORRECTIVE PRUNING BY A
 CERTIFIED ARBORIST, THEN THEY CAN REMAIN AND BE COUNTED
 TOWARD MEETING THE REQUIREMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-05-28 Cont ID  
Sent By rkussner Date 2009-05-22 Time 14:32 Rev Time 0.00
Received By rkussner Date 2009-05-22 Time 14:30 Sent To  
Notes
2009-05-22 14:58:38***LANDSCAPE REVIEW PASSED WITH 'PROVISO'**
  
 LANDSCAPE PLAN THAT MEETS ALL MINIMUM REQUIREMENTS
 PURSUANT TO ARTICLE XIV OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS SHALL BE SUBMITTED AND APPROVED
 PRIOR TO C/O. IT SHALL CONTAIN ALL OF THE FOLLOWING:
  
 1. PUSUANT TO SECTION 94-442 (D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN
 SPACE AREAS SHALL BE PLANTED WITH GRASS. THIS INCLUDES
 THE ENTIRE SITE AND RIGHTS-OF-WAY.
  
 2. PURSUANT TO SECTION 94-445 (4)(G)(3), AUTOMATIC
 IRRIGATION SYSTEMS SHALL BE USED FOR THE CULTIVATED
 LANDSCAPE AREAS FOR ALL PROPERTIES. THIS INCLUDES THE
 RIGHTS-OF-WAY.
  
 3. THE LANDSCAPE PLAN SHALL INCLUDE ALL ITEMS FOUND IN
 SECTION 94-448 (D)(2), INCLUDING THE TABULATION CLEARLY
 DISPLAYING THE RELEVATNT STATISTICAL INFORMATION
 NECESSARY FOR THE EVALUATION OF COMPLIANCE WITH THE
 PROVISIONS OF THIS ARTICLE. THE PLANT LIST SHALL
 INCLUDE THE PLANT NAME, QUANTITY, SIZE AND SPACING OF
 ALL ESISTING AND PROPOSED PLANT MATERIAL. ALL OVERHEAD
 LINES, EASEMENTS, UTILITIES AND ANYTHING ELSE THAT
 COULD INTERFERE WITH PROPOSED LANDSCAPING.
  
 4. ALL TREES AND PLANT MATERIAL THAT WILL REMAIN SHALL
 BE FLORIDA NUMBER 1 GRADE OR BETTER. EXISTING TREES
 WILL NEED CORRECTIVE PRUNING BY A CERTIFIED ARBORIST IF
 THEY ARE NOT IN GOOD CONDITION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-10-28 Cont ID  
Sent By rmcdouga Date 2009-10-27 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2009-10-27 Time 15:40 Sent To  
Notes
2009-10-28 07:25:25MECHANICAL REVISION REVIEWED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2009-09-17 Cont ID  
Sent By rmcdouga Date 2009-09-17 Time 10:19 Rev Time 0.00
Received By rmcdouga Date 2009-09-17 Time 10:19 Sent To  
Notes
2009-09-17 10:19:21MECHANICAL REVISIONS TO SHEET M-1 ARE DENIED.
  
 1) THE MECHANICAL REVISIONS ARE REQUIRED TO BE SIGNED
 AND SEALED BY THE ARCHITECT THAT SEALED THE ORIGINAL
 MECHANICAL DRAWINGS. FS 481.
  
 2) THE PLANS ARE NOT CLEAR AND LEGIBLE. THE PLANS HAVE
 "DEMO LICENSE NOT FOR RESALE" PRINTED ALL OVER THEM.
 SUBMIT CLEAR LEGIBLE DRAWINGS. FBC 106.1.1
  
 3) THE REVISIONS ARE NOT CLEARLY IDENTIFIED ON THE
 DRAWING. ITEMS THAT APPEAR TO BE ELIMINATED OR MOVED
 ARE STILL SHOWN ON THE PLANS IN THE ORIGINAL LOCATIONS.
 PLEASE CORRECT. FBC 106.1.1
  
 4) HAND WRITTEN CHANGES AND NOTATIONS ON THE PLANS CAN
 ONLY BE DONE BY THE DESIGNER OF RECORD. FS 481
  
 5) THE REVISION NOTES THAT THE CONDENSING UNIT ON THE
 EXTERIOR IS TO BE RELOCATED. INDICATE THE NEW LOCATION
 OF THE CONDENSING UNIT ON THE PLANS. FBC 106.1.1 THE
 NEW LOCATION WILL REQUIRE THE APPROVAL OF THE ZONING
 DEPARTMENT. PROVIDE SURVEY OR SITE PLAN INDICATING THE
 NEW LOCATION AND THE DISTANCES FROM PROPERTY LINES.
 CONTACT THE ZONING DEPARTMENT FOR THEIR REQUIREMENTS AT
 561-822-1435.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-05-20 Cont ID  
Sent By rmcdouga Date 2009-05-20 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2009-05-20 Time 09:11 Sent To  
Notes
2009-05-20 09:14:04MECHANICAL PROVISO:
  
 M1305.1.3 APPLIANCES IN ATTICS. ATTICS CONTAINING
 APPLIANCES REQUIRING ACCESS SHALL BE PROVIDED WITH AN
 OPENING AND UNOBSTRUCTED PASSAGEWAY LARGE ENOUGH TO
 ALLOW REMOVAL OF THE LARGEST APPLIANCE. THE PASSAGEWAY
 SHALL NOT BE LESS THAN 30 INCHES (762 MM) HIGH AND 22
 INCHES (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM)
 IN LENGTH MEASURED ALONG THE CENTERLINE OF THE
 PASSAGEWAY FROM THE ATTIC ACCESS OPENING TO THE
 APPLIANCE'S SERVICE PANEL. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING NOT LESS THAN 24 INCHES (610
 MM) WIDE. A LEVEL SERVICE SPACE NOT LESS THAN 30 INCHES
 (762 MM) DEEP AND 30 INCHES (762 MM) WIDE SHALL BE
 PRESENT AT THE FRONT OR SERVICE SIDE OF THE APPLIANCE.
 THE CLEAR ACCESS OPENING DIMENSIONS SHALL BE A MINIMUM
 OF 20 INCHES BY 30 INCHES (508 MM BY 762 MM), WHERE
 SUCH DIMENSIONS ARE LARGE ENOUGH TO ALLOW REMOVAL OF
 THE LARGEST APPLIANCE.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-04-08 Cont ID  
Sent By rmcdouga Date 2009-04-08 Time 08:45 Rev Time 0.00
Received By rmcdouga Date 2009-04-08 Time 08:45 Sent To  
Notes
2009-04-08 09:08:402007 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO (2) COPIES OF ENERGY CALCULATIONS AND
 MANUAL J CALCULATIONS AS REQUIRED AS REQUIRED BY 2007
 FBC R N1100.
  
 2) REVISE PLANS TO COMPLY WITH 2007 FBC R M1602.4
 BALANCED RETURN AIR.
  
 3) UPDATE REFERENCES TO FMC CODE SECTIONS TO THE 2007
 FMC AS SOME HAVE BEEN CHANGED. SEE REDLINED PLAN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-04-07 Cont ID  
Sent By rmcdouga Date 2009-04-07 Time 07:39 Rev Time 0.00
Received By rmcdouga Date 2009-04-07 Time 07:39 Sent To  
Notes
2009-04-07 07:39:43FIXTURE CHANGEOUT ONLY

Review Stop Z ZONING
Rev No 3 Status P Date 2009-11-05 Cont ID  
Sent By astelly Date 2009-11-05 Time 17:28 Rev Time 0.00
Received By astelly Date 2009-11-05 Time 17:28 Sent To  
Notes
2009-11-05 17:56:22PROVISO:
 SEC. 94-305. SETBACKS.
  
 (4) MECHANICAL EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR FEET INTO A SETBACK. WINDOW
 AIR-CONDITIONING UNITS MAY NOT PROJECT MORE THAN 18
 INCHES INTO A REQUIRED SIDE SETBACK.
  
 AMY F. STELLY
 PLANNING AND ZONING
 561.822-1442

Review Stop Z ZONING
Rev No 2 Status P Date 2009-05-29 Cont ID  
Sent By mcruz Date 2009-05-29 Time 08:40 Rev Time 0.00
Received By mcruz Date 2009-05-27 Time 13:47 Sent To  
Notes
2009-05-29 08:39:59PASSED WITH PROVISOS:
 1. THE A/C EQUIPMENT SHALL BE AT LEAST 4 FEET FROM WEST
 PROPERTY LINE.
 2. THE LANDSCAPE/IRRIGATION PLANS SHALL BE APPROVED
 PRIOR TO FINAL C.O.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-04-15 Cont ID  
Sent By mcruz Date 2009-04-15 Time 12:56 Rev Time 0.00
Received By mcruz Date 2009-04-14 Time 09:37 Sent To  
Notes
2009-04-15 12:56:41PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK
 EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 3. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 4. INDICATE SETBACK DIMENSIONS FROM PROPOSED OR
 RELOCATED A/C EQUIPMENT TO ALL PROPERTY LINES. PURSUANT
 THE ZLDR, SECTION 94-305(B)(4): MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.
  
 PURSUANT TO THE ZLDR, SECTION 94-74: SINGLE FAMILY HIGH
 DENSITY (SF14) RESIDENTIAL DISTRICT - MINIMUM SETBACKS
 FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
  
 C. REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER IS
 LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  