Plan Review Details - Permit 09030551
Plan Review Stops For Permit 09030551
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-23 Cont ID  
Sent By jwitmer Date 2009-07-23 Time 10:14 Rev Time 1.55
Received By jwitmer Date 2009-07-23 Time 10:14 Sent To  
Notes
2009-07-23 10:15:17PLANS PASSED WITH CORRECTED VERSION OF ENERGY CALCS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-27 Cont ID  
Sent By jwitmer Date 2009-04-27 Time 16:16 Rev Time 3.55
Received By jwitmer Date 2009-04-27 Time 14:17 Sent To  
Notes
2009-04-27 16:16:20BUILDING PLAN REVIEW
 PERMIT: 09030551
 ADD: 2497 OKEECHOBEE BLVD
 CONT: WARWICK CONSTRUCTION
 TEL: (954)553-1701 JEANETTE CAMPBELL
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009
  
 2) PLEASE CORRECT ALL REFRENCES TO THE 2004 FBC WE ARE
 CURRENTLY REVIEWING PLANS TO THE 2007 FBC WITH 2009
 SUPPLEMENTS, TENANT SPACES 2007 EXISTING BUILDING CODE/
 WITH 2009 SUPPLEMENTS.
 PLEASE IDENTIFY TO WHAT LEVEL OF ALTERATION THE PLANS
 WERE DESIGNED TO. EXISTING BUILDING CODE 401.4 A DESIGN
 PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 3) PLEASE UPDATE THE ENERGY FORMS FORM 400B- 2004
 V2.5THE NEW FORMS WOULD BE 400B-07 . 13-400.4.ABC
 REPORTING.
  
 4) SHEET A0-2 IN NOTES TRAVEL DISTANCE, NUMBER OF EXITS
 & EXIT DOOR ARRANGEMENTS ALL INDICATE THE CBC 2007 THE
 PLANS SHOULD BE DESIGNED UNDER THE FLORIDA EXISTING
 BUILDING CODE OR THE FLORIDA BUILDING CODE, BUILDING
 BUT THIS IS A TENANT BUILDOUT AND SHOULD BE DESIGNED
 UNDER THE FLORIDA EXISTING BUILDING CODE.
  
 5) SHEET A5-0 RESTROOM DETAILS INDICATE THEY ARE DRAWN
 TO A 3/4 INCH SCALE IT APPEARS THE ENTRY DOORS TO THE
 RESTROOM ARE ONLY 2'-0" WIDE, RECHECK THE SCALE DRAWN
 TO. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 6) SHEET A5-0 RESTROOM DETAIL PLEASE INDICATE THE CLEAR
 FLOOR SPACE FOR THE WATER FOUNTAIN BETWEEN THE
 RESTROOMS. 11-4.15.5.
  
 7) SHEET A6-2 THE HC FITTING ROOM PLEASE REVIEW THE
 SCALE OF THE DRAWINGS. THEY INDICATE 1"=1'-0". 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 8) ELEVATION SHEETS INDICATE REMOVAL AND NEW SIGNAGE
 REQUIRES A SEPERATE PERMIT FOR NEW SIGNAGE.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
2009-04-09 08:33:07PLANS ON HOLD FOR NON-PAYMENT. CALLED CONTRACTOR
 4/07/09
 4/09/09 PLANS PLACED OUT FRONT FOR NON PAYMENT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-24 Cont ID  
Sent By dpalmer Date 2009-07-24 Time 15:09 Rev Time 0.00
Received By dpalmer Date 2009-07-24 Time 15:08 Sent To  
Notes
2009-07-24 15:10:49REDLINED PLANS.
  
 CONTROLS FOR MAIN AREA MUST MEET 13-415.AB.1.1,.1.2. SQ
 FT ON PLANS IS OVER 10K ST FT WHICH REQUIRES MORE THAN
 ONE OVER RIDE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-06 Cont ID  
Sent By dpalmer Date 2009-05-06 Time 12:27 Rev Time 0.00
Received By dpalmer Date 2009-05-06 Time 12:27 Sent To  
Notes
2009-05-06 12:28:05**DENIED PLANS**
  
  
  
 1) NOTE: PLANS ARE BEING SUBMITTED FOR PERMIT AFTER
 MARCH 1ST, 2009 WHICH PLACES PROJECT UNDER THE 2007 FBC
 WITH 2009 AMENDMENTS.
 PLANS AND ENERGY CALCULATIONS ARE UNDER THE 2004 FBC.
 PLEASE ALSO SEE FAC 69A-60.004 WHICH REVISED THE
 NFPA-101 AND NFPA-1 TO THE 2006 EDITIONS.
  
 PLEASE REVISE ALL PLANS AND RESUBMIT FOR COMPLETE
 REVIEW FOR CODE COMPLIANCE UNDER CURRENT CODES.
 ** PLEASE BE SURE TO SEE FBC CHAPTER 13 UNDER THE NEW
 CODE ABOVE AS THIS ENTIRE CHAPTER WAS COMPLETELY
 REVISED.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-28 Cont ID  
Sent By mawillia Date 2009-07-28 Time 15:30 Rev Time 0.00
Received By mawillia Date 2009-07-28 Time 14:54 Sent To B
Notes
2009-07-28 15:27:40*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS A0-2, A1-1, A1-2, A4-0, AND
 E2-0 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-05-12 Cont ID  
Sent By mawillia Date 2009-05-12 Time 14:28 Rev Time 0.00
Received By mawillia Date 2009-05-12 Time 13:00 Sent To  
Notes
2009-05-12 13:09:15*****DENIED*****
  
  
 1. ON THE COVER SHEET (A0.0), AMEND THE FOLLOWING
 INFORMATION IN THE PROJECT TEAM SECTION: BUILDING
 DEPARTMENT - 401 CLEMATIS STREET (ADDRESS); FIRE
 DEPARTMENT - 500 NORTH DIXIE HIGHWAY (ADDRESS),
 561-804-4724 (TELEPHONE).
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED IN ADDITION TO THE 2007 FLORIDA FIRE
 PREVENTION CODE. MAKE THE NECESSARY CORRECTIONS ON
 SHEET A0-0 IN THE CODE INFORMATION SECTION.
  
 3. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION. ADD 2004 EDITION TO THE LISTED NFPA 241 IN THE
 CODE INFORMATION SECTION.
  
 4. IT IS NOTED ON SHEETS A1-1 & A1-2 THAT ALL WORK WILL
 BE CONDUCTED DURING THE SPECIFIED TIME THAT THE STORE
 CLOSES AND THEN RE-OPENS THE FOLLOWING DAY. THE FIRE
 PROTECTION SYSTEMS IN THIS BUILDING SHALL BE MAINTAINED
 OPERATIONAL AT ALL TIMES DURING THE ALTERATION. WHEN/IF
 IT IS NECESSARY FOR THE SYSTEM TO BE MODIFIED AND/OR
 SHUT DOWN, THE FIRE PREVENTION BUREAU SHALL HAVE THE
 AUTHORITY TO REQUIRE ALTERNATIVE MEASURES OF PROTECTION
 UNTIL THE SYSTEM IS RETURNED TO SERVICE.
  
 5. ON SHEET E0.0, MAKE NECESSARY CORRECTIONS TO THE
 APPLICABLE CODES SECTION AS FOLLOWS: REFERENCE 2007
 (NOT 2005) FLORIDA FIRE PREVENTION CODE, DELETE
 REFERENCE TO 2003 NFPA-72.
  
 6. SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIALS IN THE TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-06-24 Cont ID  
Sent By shill Date 2009-06-24 Time 15:10 Rev Time 0.00
Received By shill Date 2009-06-24 Time 15:10 Sent To  
Notes
2009-06-24 15:10:56C23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-17 Cont ID  
Sent By swurafti Date 2009-04-17 Time 15:21 Rev Time 0.00
Received By swurafti Date 2009-04-17 Time 15:21 Sent To  
Notes
2009-04-17 15:25:23TO "C24"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-12 Cont ID  
Sent By mawillia Date 2009-05-12 Time 13:00 Rev Time 0.00
Received By mawillia Date 2009-03-30 Time 14:27 Sent To  
Notes
2009-03-30 14:28:07TO "C34"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-04-30 Cont ID  
Sent By rregueir Date 2009-04-30 Time 11:43 Rev Time 0.00
Received By rregueir Date 2009-04-30 Time 11:36 Sent To  
Notes
2009-04-30 11:43:15NO MECHANICAL SCOPE OF WORK ASSOCIATED WITH THIS
 PERMIT. THE "M" PAGES ARE FOR PLUMBING WORK.

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-05-01 Cont ID  
Sent By kstevens Date 2009-05-01 Time 11:25 Rev Time 0.00
Received By kstevens Date 2009-05-01 Time 11:25 Sent To  
Notes
2009-05-01 11:30:36INSTALLING AUTOMATIC FLUSH VALVES -- PLUMBING PERMIT
 REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2009-04-30 Cont ID  
Sent By lfranco Date 2009-04-29 Time 11:54 Rev Time 0.00
Received By lfranco Date 2009-04-29 Time 11:53 Sent To  
Notes
***NONE***