Plan Review Details - Permit 09030496
Plan Review Stops For Permit 09030496
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-08-14 Cont ID  
Sent By shill Date 2009-08-14 Time 18:35 Rev Time 0.00
Received By shill Date 2009-08-14 Time 18:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-08-13 Cont ID  
Sent By shill Date 2009-08-13 Time 08:24 Rev Time 0.00
Received By shill Date 2009-08-13 Time 08:24 Sent To FIRE
Notes
2009-08-13 08:24:55NEW SHEET A16
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-07-29 Cont ID  
Sent By shill Date 2009-07-29 Time 15:11 Rev Time 0.00
Received By shill Date 2009-07-29 Time 15:10 Sent To  
Notes
2009-07-29 15:20:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IT IS NOT CLEAR WHY THIS HAS BEEN SUBMITTED. A
 REDUCED 11X17 SHEET A11 WAS SUBMITTED. NO CHANGES WERE
 SHOWN. THIS WAS SUBMITTED AS A REVISION.
  
 PLEASE CLEARLY INDICATE ALL CHANGES. PLEASE SUBMIT
 REVISIONS ON FULL SIZE PLAN SHEETS AS THE INFORMATION
 IS TOO SMALL TO PROPERLY DIGITIZE. PLEASE FEEL FREE TO
 CONTACT ME TO DISCUSS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-06-02 Cont ID  
Sent By dwise Date 2009-06-02 Time 21:29 Rev Time 0.00
Received By dwise Date 2009-06-02 Time 21:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-06-01 Cont ID  
Sent By dwise Date 2009-05-11 Time 17:23 Rev Time 0.00
Received By mawillia Date 2009-05-11 Time 17:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-07 Cont ID  
Sent By shill Date 2009-04-07 Time 13:11 Rev Time 0.00
Received By shill Date 2009-04-07 Time 13:11 Sent To  
Notes
2009-04-07 13:17:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. SHOW MANEUVERING CLEARANCE, JANITOR'S CLOSET, PULL
 SIDE, FBC FIGURE 11-25; THIS APPEARS TO BE A WORK AREA.
  
 2. VISUAL ALARMS TO BE PROVIDED IN BREAK ROOM AND
 RESTROOMS, FBC11-4.28.1.
  
 3. PLEASE CLARIFY; THIS HAS BEEN DECLARED A LEVEL III
 ALTERATION. ISN'T THIS A TENANT BUILDOUT, FIRST
 OCCUPANCY? PLEASE PROVIDE INFORMATION REGARDING THE
 SHELL STRUCTURE.
  
 4. IF THIS IS FIRST OCCUPANCY (TENANT BUILDOUT IN A
 SHELL BUILDING), PLEASE PROVIDE ENERGY CALCS
 FBC13-101.1.6.
  
 5. SHOW ACCESSIBLE PARKING; TOTAL SPACES, NUMBER OF
 PROPOSED SPACES, LOCATION FBC11-4.1.2, FBC11-4.6. NOTE
 THAT PARKING SPACES ARE SHOWN ON THE PLAN BUT NO
 ACCESSIBLE SPACES ARE SHOWN. ALSO PLEASE NOTE THE
 REQUIREMENT THAT REQUIRED PARKING SPACES BE DISPERSED,
 FBC11-4.6.2.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2009-09-01 Cont ID  
Sent By dpalmer Date 2009-09-01 Time 13:07 Rev Time 0.00
Received By dpalmer Date 2009-09-01 Time 13:07 Sent To PC
Notes
2009-09-01 13:08:59** REDLINED
  
  
 STILL HAS NOT APPLIED FOR FIRE ALARM PERMIT. ( HOLD ON
 CO
 ALSO STILL NEEDS TO UPDATE VALUE AS NOTED ON PREVIOUS
 REVIEWS. FBC108.3. HOLD ON CO.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2009-08-28 Cont ID  
Sent By dpalmer Date 2009-08-28 Time 10:15 Rev Time 0.00
Received By dpalmer Date 2009-08-28 Time 10:15 Sent To PC
Notes
2009-08-28 10:15:36** TEMPORARY FAILED**
  
 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS FOR LIGHTING
 PERFORMANCE CALCULATIONS ARE NOT SEALED BY THE DESIGN
 PROFESSIONAL AS REQUIRED PER FS 481.221/471.025.
 BOTH COPIES ARE SIGNED AND DATED. CALLED AND LEFT
 MESSAGE ON ARCHITECT*S CELL PHONE.
  
  
  
 ** PROVISO/REDLINED PLANS**
  
 *** THE FOLLOWING ARE SET FORTH AS A PROVISO. ALL
 REVISIONS AND CORRECTIONS SHALL BE MADE BEFORE FINAL
 INSPECTIONS AND SOME ITEMS MUST BE DONE BE TCO.
  
  
 ** SPOKE TO ARCHITECT, CORRECTIONS WILL MOST LIKELY BE
 SUBMITTED ON MONDAY 8/31 AS CORRECTED REVISIONS INSTEAD
 OF PROVISO.
  
 1) NOTE: THE VALUE FOR THE COMPLETE SCOPE OF WORK
 INCLUDING ALL LABOR, MATERIALS, EQUIPMENT MUST BE
 UPDATED. THE INCREASE IN THE ELECTRICAL SCOPE OF WORK,
 EQUIPMENT AND MATERIALS IS SUBSTANTIAL. PROVIDE ALL
 SIGNED, CONTRACTS, EQUIPMENT, MATERIAL INVOICES OR
 ADJUST VALUE ACCORDINGLY TO APPROPRIATE VALUE.
 FBC 108.3
  
 2) NOTE: TO DATE AFTER PREVIOUS REVIEWS AND MEETING THE
 MINIMUM LEVELS, HEIGHTS, INTENSITY OF HORN, STROBES,
 HORN/STROBE DEVICES IS STILL NOT SHOWN ON PLANS MEETING
 MINIMUM COMPLIANCE FOR ADA. PLEASE SEE FBC 11-4.28.1,.2
 AND .3(4)
 ** TO DATE NO FIRE ALARM PERMIT HAS BEEN APPLIED.
 BASE PLANS MUST SHOW MINIMUM DESIGN REQUIRED FOR LIFE
 SAFETY AND OTHER APPLICABLE CODES. FS 633
  
 3) NOTE: THE OCCUPANCY SENSORS IN RECEIVING AREA ON
 LIGHTING PLANS ARE NOT THE SAME AS SHOWN ON E2.1. PLANS
 SHOW WITH CEILING DEVICES ON E-2 AND WALL DEVICES ON
 SHEET E2.1.
  
 4) NOTE: THE RECESSED LIGHTS AT FRONT ENTRANCE STILL
 INDICATE TO A PANEL P2. HOWEVER THIS SHOULD BE P-2.
 SPOKE TO ARCHITECT.
 408.4, 310.16.
  
 5) NOTE: LOADS SHOWN ON PANEL P WHICH FEED PANEL P-1 DO
 NOT COORDINATE. LOAD ON P-1 IS HIGHER THAN LOAD ON
 PANEL P.
 THE CALCULATIONS ON P-1 INDICATE LOAD AT 125% HOWEVER
 THE LOAD ON PANEL IS HIGHER THAN THE TOTAL. PANEL
 INDICATES 8400 AND THE CALCULATION AFTER THE 125% IS
 ONLY AT 8000.
 PLEASE EXPLAIN LOAD SHOWN ON MDP FOR PANEL P WHICH IS
 SHOWN AT 8600VA.
 ** BOTH OF THESE ITEMS WERE GONE OVER IN PREVIOUS
 MEETING.
 215.3,230.42, 220, 408.4
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS.
  
 6) NOTE: THE METHOD OF CONTROLS ON THE IDR IS STILL
 SHOWN AS MANUAL ON/OFF.
 13-415.B.1.
  
 7) NOTE: NEW 600AMP MAIN DISCONNECT INDICATES A NEW
 SEPARATE GROUNDING ELECTRODE SYSTEM HOWEVER AS THIS
 MAIN IS TAPPED FROM EXISTING GUTTED THE GROUNDING
 ELECTRODE SYSTEM IS ALREADY EXISTING DONE UNDER THE
 SHELL PERMIT. IF ADDING ADDITIONAL GROUNDING ELECTRODE
 CONDUCTOR AND GROUNDING ELECTRODE THEN THESE MUST BE
 BONDED TO THE EXISTING SYSTEM.
 PLEASE VERIFY THIS AND REVISE AS NEEDED.
 250.50, 220.58
  
  
 **** IMPORTANT:
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2009-08-21 Cont ID  
Sent By dpalmer Date 2009-08-21 Time 13:57 Rev Time 0.00
Received By dpalmer Date 2009-08-21 Time 13:57 Sent To  
Notes
2009-08-21 13:57:49 
 ** DENIED REVISION **
  
 ** ELECTRICAL PERMIT ISSUED TO DATE IS ONLY FOR
 ELECTRICAL CONDUITS IN SLAB.
  
 ** SEPARATE PERMIT(S) STILL REQUIRED FOR LV.
  
 ** NO FIRE ALARM PERMIT HAS BEEN APPLIED/OR SUBMITTED.
 SEE NOTES BELOW WITH RESPECT TO MINIMUM FBC ADA
 REQUIREMENTS.
  
 1) NOTE: PLANS SUBMITTED CONTAIN *WHITE-OUT* AND HAND
 DRAWN CHANGES TO PLANS WHICH ARE SIGNED, DATED AND
 SEALED BY AN ENGINEER. THIS IS NOT PERMITTED.
 PLANS SHALL BE REVISED, SIGNED, DATED AND SEALED BY THE
 ENGINEER OF RECORD.
 FS 471
 PLEASE ALSO SEE FAC 61G15-23.002.
  
 2) NOTE: THE LIGHTING CONTROLS ON PLANS STILL DO NOT
 MEET THE FLORIDA BUILDING CODE MINIMUM.
 13-415.AB.1.1,.1.2, .1.3 AND .1.4
  
 A) THE POWER PLANS STILL INDICATE STANDARD SINGLE POLE
 SWITCHES FOR LIGHTING CONTROLS.
  
 B) THERE ARE OTHER STANDARD SWITCH DEVICES SHOWN FOR
 OTHER ITEMS SUCH AS REAR EXTERIOR LIGHTS WHICH IS NOT
 PERMITTED.
  
 C) ZONES, AND OVER RIDES PER SECTIONS GIVEN ARE NOT
 SHOWN ON PLANS. IN FACT THE PLANS DO NOT INDICATE ANY
 SPECIFIC DETAILS OR MINIMUMS. THE RISER NOTES MENTIONS
 TO SEE LEGEND FOR DETAILS HOWEVER THERE ARE NO
 DETAILS??
  
 D) OVER RIDES FOR THE OCCUPANTS AND MAXIMUM OVER RIDE
 TIMES ARE NOT SHOWN. AN OCCUPANT MUST SEE ALL LIGHTING
 WHICH IS BEING OVER RIDDEN OR MEET EXCEPTIONS. IF
 MEETING EXCEPTIONS, THEN PLEASE BE SURE TO SHOW
 INFORMATION ON PLANS.
 PLEASE BE SURE ZONES FOR MAXIMUM SPACE CONTROLS ARE
 SHOWN. PLEASE BE SURE TO THE LOCATIONS ARE SHOWN.
  
 E) THERE ARE SOME OCCUPANCY SENSOR DEVICES SHOWN ON
 SYMBOL LEGEND. HOWEVER NONE OF THESE DEVICES ARE SHOWN
 ON PLANS.
  
 F) SOME DEVICES STATE *SWITCH/ TIMER*. SEE FBC CHAPTER
 11 FOR ADA COMPLIANCE. TWIST TYPE TIMERS ARE NOT
 PERMITTED. 11.4-.27.4
  
  
  
 4) NOTE: THE SUBMITTED LIGHTING PERFORMANCE
 CALCULATIONS DO NOT MEET THE MINIMUM PER FBC
 13-415.AB.5.
 THERE IS ANOTHER NEW SUBMITTED METHOD *B* HOWEVER THE
 METHOD *B* SUBMITTED IS FOR SHELL ONLY. THIS IS NOT A
 SHELL. THIS IS A TENANT BUILDING OUT. THE DESIGN AND
 CRITERIA WILL BE LISTED ON THE SUMMARY SHEETS.
 PLEASE SEE 13-400.B.0.4, 13-415.B.1, .2.2 ETC
 *** PLEASE CALL TO GO OVER CALCULATIONS.
 THE EXTERIOR LIGHTS ON THE IDR INDICATES ONE FIXTURE AT
 2000WATTS. THIS IS NOT POSSIBLE.
 PLEASE ALSO SEE THAT ALL SPACES NEED TO BE SHOWN. OTHER
 SPACES SUCH AS STORAGE CLOSETS AND OTHER AREAS ARE NOT
 SHOWN.
 ** FIXTURE LEGEND NEEDS TO BE COMPLETED WITH ALL
 SPECIFIC FIXTURES. STATING A 1X4 FLUORESCENT FIXTURE OR
 2X4 FIXTURE DOES NOT GIVE INFORMATION NEEDED. THESE
 COULD HAVE WATTAGES OF 28, 32 , 64, 56, 86, 92, 96,
 110, 120, OR GREATER. SEE E-3 FOR EXAMPLE; FIXTURE
 LISTED FOR * BACK OFFICES STATES THERE ARE 2-32WATT
 BULBS WITH A POWER FACTOR OF 1.1, YET THE TOTAL PER
 FIXTURE IS SHOWN AS 35.2. THIS IS NOT POSSIBLE.
 A FIXTURE WITH 2-32W BULBS WITH A POWER FACTOR OF 1.1
 WOULD BE A TOTAL FIXTURE VA OF 70.4 PER FIXTURE, NOT
 35.2. THIS WOULD BRING THE TOTAL UP TO 140.8WATTS.
 ** PLEASE GO OVER ALL OF THE FIXTURES, OBTAIN SPECIFIC
 INFORMATION AND ADJUST.
  
 ** PLEASE SEE THE IDR OF THE SUBMITTED ENERGY
 CALCULATIONS. THE CONTROLS ARE SHOWN AS *MANUAL
 ON/OFF*. THIS WOULD BE BASED ON THE TYPE OF CONTROLS
 FOR EACH SPACE ON PLANS. IE: TIME SCHEDULING, OCCUPANCY
 SENSORS ETC.
  
 ** CALL IF THERE ARE QUESTIONS.
  
  
 5) NOTE: PLEASE SEE 250.20,250.30,250.50, AS THE
 PREVIOUS PLANS STATED THE GEC TO CWP AND GROUND ROD FOR
 TRANSFORMER ATTACHMENT. HOWEVER PER SECTIONS ABOVE,
 BUILDING STEEL WAS NOTED AS BEING REQUIRED. NOW THE
 RISER WAS REVISE REMOVING CWP ??
  
 6) NOTE: SHOW WINDOW LOADS NEED TO BE SHOWN PER 220.14,
 220.43
 LOAD CALCULATIONS SUBMITTED STILL DO NOT MEET NEC
 SECTION 220.
 220.12,220.14,220.42,220.44 ETC
  
 7) NOTE: TO DATE NO FIRE ALARM PERMIT APPLICATION HAS
 BEEN SUBMITTED. THE DEVICES INSTALLED ON SHELL PERMIT
 WERE ONLY FOR SHELL. WITH THE INSTALLATION OF WALLS AND
 OTHER OBSTACLES THE DEVICE LOCATIONS SHOWN AND
 INSTALLED ON SHELL DO NOT MEET MINIMUM FOR ADA FOR
 TENANT BUILD OUT. PLEASE SEE FBC 11-4.28.1,.2 AND .3
 FOR MINIMUM LOCATIONS, HEIGHTS, LEVELS, CANDELA LEVELS,
 DB LEVELS ETC.
 LOCATIONS SUCH AS RECEIVING, BATHROOMS, RETAIL SALES
 FLOOR AREAS, OFFICE ETC.
  
 8) NOTE: PLANS ARE NOW SHOWING A COMPLETELY NEW
 SERVICE. THIS IS NOT PERMITTED. THE SHELL BUILDING HAD
 SERVICE FOR BUILDING AND EQUIPMENT/MAINS FOR FUTURE
 TENANTS. NOW RISER INDICATES A NEW SERVICE. PLEASE SHOW
 ALL SERVICE EQUIPMENT, RISER EQUIPMENT ETC AS
 PREVIOUSLY REQUESTED. PLEASE BE SURE TO OBTAIN
 ELECTRICAL RISER INFORMATION FROM SHELL PLANS.
 PLEASE ADJUST EQUIPMENT AND SERVICE. 230.2E,
 230.70,230.71,230.72. PLEASE SHALL LOCATIONS OF ALL
 MAINS.
  
 9) NOTE: THIS NOTE REMAINS AS PLANS CONTAINS *WHITE
 OUT* FOR REVISING THIS INFORMATION.
 THE PANEL ON THE SECONDARY SIDE OF THE TRANSFORMER DOES
 NOT INDICATE ANY MAIN. ALL TAPPED CONDUCTORS SHALL
 TERMINATE IN OVER CURRENT PROTECTION. 240.21. PLEASE
 ALSO SEE 408.36, 240.4, 310.16 ETC
  
 10) NOTE: PLANS NOW INDICATE SHOW WINDOW RECEPTACLES ON
 A PANEL SCHEDULE P1, HOWEVER THE CIRCUITING ON PLANS
 INDICATES CIRCUITS TO PANEL *P*> SUCH AS *P-38, P-40.
 NEITHER PANEL *P* NOR PANEL *P1* HAVE ANY CIRCUITS 38,
 OR 40 FOR SHOW WINDOWS.
 THE FACT IS THAT PANEL *P* SHOWS SPARES CIRCUITS FOR 38
 AND 40, AND PANEL P1 IS ONLY SHOWN AS A 24 CIRCUIT
 PANEL.
  
 11) NOTE: NO EGRESS LIGHTING SHOWN ON PLANS FOR
 RECEIVING AREA? PLEASE SEE FBC CHAPTER 10, NFPA-101
 LIFE SAFETY CODE 7.8.1.3, 7.9.1.2, .2.2. PLEASE SEE
 700.12F FOR CIRCUITING TO LOCAL LIGHTING BRANCH
 CIRCUITS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-07-17 Cont ID  
Sent By dpalmer Date 2009-07-17 Time 17:06 Rev Time 0.00
Received By dpalmer Date 2009-07-17 Time 17:05 Sent To PC
Notes
2009-07-17 17:06:10 
 ** DENIED REVISION **
  
 ** ELECTRICAL PERMIT ISSUED TO DATE IS ONLY FOR
 ELECTRICAL CONDUITS IN SLAB.
  
 ** SEPARATE PERMIT(S) STILL REQUIRED FOR LV.
  
 1) NOTE: PLANS SHALL BE REVISED, SIGNED, DATED AND
 SEALED BY THE ENGINEER OF RECORD.
 FS 471
 PLEASE ALSO SEE FAC 61G15-23.002 FOR MISSING REQUIRED
 INFORMATION ON TITLE BLOCKS. THE PRINTED LICENSE NUMBER
 AS WELL AS CERTIFICATE OF AUTHORIZATION NUMBER PER FS
 471.023.
  
 2) NOTE: PLEASE SEE 450.3 AS THE OVER CURRENT
 PROTECTION SHOWN ON PANEL FEEDING TRANSFORMER EXCEEDS
 THE 125% PERMITTED. ONLY IF MEETING NOTE #5 CAN THIS BE
 DONE.
 IF MEETING NOTE #5 SUBMIT MANUFACTURES SPECS/CUT SHEETS
 ON THIS SPECIALIZED TYPE OF TRANSFORMER.
 110.3, 90.7
  
 3) NOTE: THE NOTE ON THE PLANS FOR THE LIGHTING
 CONTROLS DOES NOT MEET FBC 13-415.1.AB.1.1,.1.2, .1.3
 OR .1.4. SEE THE FOLLOWING NOTES BELOW:
 A) ZONES, AND OVER RIDES PER SECTIONS GIVEN ARE NOT
 SHOWN ON PLANS.
  
 B) OVER RIDES FOR THE OCCUPANTS AND MAXIMUM OVER RIDE
 TIMES ARE NOT SHOWN.
  
 C) THE SYMBOL LEGEND ONLY INDICATES STANDARD SINGLE
 POLE SWITCHES FOR ALL SEPARATE SPACES. THESE ARE NOT
 PERMITTED AND DO NOT MEET THE MINIMUM FBC REQUIREMENTS.
  
 D) THE PLANS INDICATE STANDARD SINGLE POLE SWITCHES FOR
 OUTSIDE LIGHTING CONTROLS WHICH ARE NOT PERMITTED.
 PLEASE SEE 13-415.1.AB.1.4 AS ONE OF THE TWO TYPES OF
 CONTROLS MEETING MINIMUM IS REQUIRED.
  
 4) NOTE: THE SUBMITTED LIGHTING PERFORMANCE
 CALCULATIONS DO NOT MEET THE MINIMUM PER FBC
 13-415.AB.5. ALL FIXTURES, THE NUMBER OF FIXTURES, THE
 TYPES OF FIXTURES ETC SHALL BE SPECIFIC ON THE INPUT
 DATE REPORT. IT IS NOT PERMITTED TO STATE FOR EXAMPLE *
 1-FIXTURE AT 3500 WATTS*.
 ALSO THE FIXTURES SHALL BE SPECIFIC. PLANS MAY NOT ONLY
 STATE FOR EXAMPLE A *2X4 FLUORESCENT FIXTURE*. THERE
 ARE FIXTURES WITH MANY POWER FACTORS RATINGS WHICH WILL
 HAVE AN AFFECT ON THE CALCULATIONS. THERE ARE ALSO THE
 SAME TYPE OF FIXTURES WHICH COULD BE 2LT, 3LT OR 4LT.
 THIS IS THE NSAME
 THERE ARE OTHER EXAMPLES ON THE IDR THAT DO NOT MINIMUM
 REQUIRED.
 THE TOTAL ON THE IDR AND SUMMARY DO NOT COORDINATE WITH
 THE PLANS.
 THE CODE TABLE REFERENCED ON PLANS IS NOT IN THE FBC
 SECTION NOTED ABOVE FOR THE LIGHTING PERFORMANCE
 LEVELS.
  
 5) NOTE: THE TRANSFORMER IS A SEPARATELY DERIVED
 SYSTEM. THE RISER INDICATES A NEUTRAL CONDUCTOR FROM
 THE 277/480V PANEL TO THE TRANSFORMER. THIS IS NOT
 PERMITTED.
 250.6,250.20,250.30 ETC
  
 6) NOTE: PLEASE SEE 250.20,250.30,250.50, AS THE PLANS
 STATE THE GEC TO CWP AND GROUND ROD FOR TRANSFORMER
 ATTACHMENT. HOWEVER PER SECTIONS ABOVE, BUILDING STEEL
 IS REQUIRED. PLEASE ALSO SEE 250.56 FOR RESISTANCE
 REQUIRED.
  
 7) NOTE: SHOW WINDOW LOADS NEED TO BE SHOWN PER 220.14,
 220.43
  
 8) NOTE: CIRCUITING FOR EMERGENCY AND EXIT LIGHTS SHALL
 BE SHOWN PER 700.12F
 (SHALL BE CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT).
  
 9) NOTE: PLEASE VERIFY SIGN CIRCUIT VOLTAGE DROP
 SHOWING 3-#6 CONDUCTORS? THIS IS NOT A CODE VIOLATION
 HOWEVER IF PLANS INDICATE #6 THEN THIS MUST BE
 INSTALLED. PLEASE CALL TO GO OVER.
  
 10) NOTE: MAINS FOR BUILDING SHALL BE LABELED. 230.2E,
 230.70,230.71,230.72. PLEASE SHALL LOCATIONS OF ALL
 MAINS.
  
 11) NOTE: PLANS STATE 2007 EDITION OF THE FBC HOWEVER
 THE CODE IN ADOPTION BY FS 553.73 AS OF MARCH 1ST ,
 2009 IS THE 2007 FBC WITH THE 2009 SUPPLEMENTS. THIS IS
 IMPORTANT AS THE 2009 GLITCH REVISIONS TO THE 2007 FBC
 SUBSTANTIALLY REVISED MOST IF NOT ALL OF CHAPTER 13
 ALONE.
  
 12) NOTE: THE PANEL ON THE SECONDARY SIDE OF THE
 TRANSFORMER DOES NOT INDICATE ANY MAIN. ALL TAPPED
 CONDUCTORS SHALL TERMINATE IN OVER CURRETN PROTECTION.
 240.21. PLEASE ALSO SEE 408.36, 240.4, 310.16 ETC
  
 *** AS THERE ARE SOME ITEMS NOT YET SUBMITTED THERE MAY
 BE NEW COMMENTS WHICH MAY FOLLOW.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-06-02 Cont ID  
Sent By dwise Date 2009-06-02 Time 21:06 Rev Time 0.00
Received By dwise Date 2009-05-26 Time 21:05 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-05-11 Cont ID  
Sent By dwise Date 2009-05-11 Time 17:22 Rev Time 0.00
Received By dwise Date 2009-05-11 Time 17:21 Sent To  
Notes
2009-05-11 17:23:02SEE PREVIOUS CORRECTIONS DATED 4/7/09 BY DEWEY PALMER.
 NONE OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-07 Cont ID  
Sent By dpalmer Date 2009-04-07 Time 20:40 Rev Time 0.00
Received By dpalmer Date 2009-04-07 Time 20:39 Sent To  
Notes
2009-04-07 20:40:32** DENIED REVIEW **
  
 ** THERE ARE NUMEROUS ITEMS MISSING FOR MINIMUM CODE
 COMPLIANCE. AS MANY ITEMS ARE NOT SHOWN THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN
 NOT BE MADE AT THIS TIME.
  
  
 1A) NOTE: *** IT IS IMPORTANT TO KNOW BASED ON THE PLAN
 COMMENTS BELOW THE APPLIED VALUE FOR A CODE COMPLIANT
 BUILD OUT WILL NEED TO BE INCREASED. THE COMMENTS FOR
 NOTE #7 ALONE WILL INCREASE THE SCOPE OF WORK
 SUBSTANTIALLY.
 VALUE SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT,
 DESIGN COSTS ETC EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED. THE ADJUSTED VALUE TO $169,850.00 IS STILL
 LOW BASED ON MINIMUM CODE COMPLIANCE REQUIRED AND ALL
 EQUIPMENT ON PLANS.
 ** EQUIPMENT TO BE INCLUDED IN VALUE SHALL BE LIGHTING,
 LIGHTING CONTROLS, A/C EQUIPMENT, ELECTRICAL SERVICE
 EQUIPMENT ETC.
  
  
 1) NOTE: PLANS MUST CONTAIN THE RAISED SEAL WITH ALL
 INFORMATION ON RAISED SEAL CLEAR AND VISIBLE WITH ALL
 INFORMATION ON SAID SEAL PER FAC 61G1-16.002,003,004.
 FS 481.221
 SEALS ARE VERY FAINT AND NOT EASILY READ. INFORMATION
 CAN NOT BE SEEN EVEN USING LEAD RUB.
 ** THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADE
 REVIEWER. ** SEE THE NEXT COMMENT FOR MEP PLANS.
  
 2) NOTE: THE COVER SHEET STATES MEP DESIGN TEAM TO BE
 BUCHANNAN ENGINEERING INC HOWEVER MEP PLANS IS DONE BY
 THE ARCHITECT LISTED.
 IN ANY CASE AN ARCHITECT IS NOT PERMITTED TO DESIGN OR
 SIGN, DATE AND SEAL 277/480 SYSTEMS DESIGNED AS SHOWN
 PER FS 471.003.
 ** PLEASE KNOW BASED ON THIS COMMENT AND THE COMMENTS
 BELOW ONE SET OF PLANS ARE BEING RETAINED BY THIS
 OFFICE.
 ** THE ELECTRICAL MUST BE DONE BY AND ELECTRICAL
 ENGINEER. PLEASE SEE SAME SECTION FOR MECHANICAL
 SYSTEMS AND DESIGNS.
 ** THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS
 MADE BY ANY OTHER TRADE.
  
 3) NOTE: PLANS SUBMITTED CONTAIN NUMEROUS REFERENCES ON
 THE ELECTRICAL PLANS FOR CODES WHICH ARE NO LONGER IN
 EFFECT. IN FACT THE NFPA-70 REFLECTED ON PLANS HAS NO
 LONGER IN EFFECT IN THE STATE OF FLORIDA IN DECEMBER OF
 2006.
 PLEASE KNOW THE OTHER CODES AS STATED SUCH AS THE LIFE
 SAFETY CODE, THE FLORIDA BUILDING CODE AND OTHERS ARE
 ALSO NO LONGER IN EFFECT.
 PLEASE SEE FS 553.73, FBC CHAPTER 35. ALL PROJECTS
 SUBMITTED FOR PERMIT ON OR AFTER MARCH 1ST, 2009 ARE
 UNDER THE 2007 FBC WITH ALL OTHER ADOPTED MINIMUM CODES
 AND STANDARDS.
 PLEASE SEE FAC 69A-60.003 AND .004 AS THE LIFE SAFETY
 CODE ( NFPA-101) AND NFPA-1 WAS REVISED ON DECEMBER
 31ST, 2008.
 THE NFPA-101 AND NFPA-1 IN EFFECT AT THAT TIME PER
 ADOPTED FLORIDA ADMINISTRATIVE CODE SECTION GIVEN WAS
 THE 2006 EDITION OF EACH.
  
 THE PLANS SHALL CONTAIN THE FOLLOWING;
 2007 FBC W/ 2009 REVISIONS.
 2006 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
  
 4) NOTE: PLEASE COMPLY WITH FBC CHAPTER 13 FOR ALL
 TRADES. COOLING LOAD CALCULATIONS MAY BE REQUIRED. SEE
 COMMENTS FROM OTHER TRADES. PLEASE SUBMIT LIGHTING
 PERFORMANCE CALCULATIONS/ ENERGY CALCULATIONS PER FBC
 CHAPTER 13. AS NO CALCULATIONS FOR COMPLIANCE WITH
 CHAPTER 13 WAS SUBMITTED THERE MAY BE NEW COMMENTS ON
 THE NEXT REVIEW. THE CALCULATIONS ON E-3 DO NOT MEET
 MINIMUM CODE. THE CODE REFERENCE IS FROM THE PREVIOUS
 CODE NO LONGER IN EFFECT. THE CODE SECTION SPECIFIC AS
 STATED ON PLANS IS 13-414.2.B. THIS SECTION DOES NOT
 EXIST UNDER NEW CODE OR THE PREVIOUS ADOPTED CODE.
 PLEASE SEE 13-400, 13-101.1.6, 13-400, 13-103.1,
 13-400.2.A.2, 13-400.3, 13-400.2, 13-415.AB.5.
 SEVERAL SECTIONS WERE GIVEN HOWEVER ALL ITEMS AND ALL
 POSSIBLE SECTIONS ARE IN NO WAY. MINIMUM COMPLIANCE
 WITH ALL OF CHAPTER 13 MUST BE DONE.
 ** PLEASE BE SURE TO SUBMIT A COMPLETE FIXTURE LEGEND
 SO THAT MINIMUM COMPLIANCE WITH THE LIGHTING
 PERFORMANCE CALCULATIONS CAN BE REVIEWED. ALL FIXTURES
 MUST BE SPECIFIC AND COMPLETE.
  
 5) NOTE: PLEASE SEE 13-413.ABC.2 FOR NOTES REQUIRED ON
 PLANS FOR COMPLETION OF PROJECT.
 ** NOTES IN THE FBC ARE REQUIRED ON PLANS.
  
 6) NOTE: PLEASE SEE 13-413.AB.1 FOR MINIMUM VOLTAGE
 DROP CALCULATIONS FOR FEEDERS AND BRANCH CIRCUITS.
  
 7) NOTE: PLEASE SEE FBC 13-415.1.AB.1.1, .1.2, .1.3 AND
 .1.4.
 PLANS WERE SUBMITTED WITH NO MINIMUM COMPLIANCE FOR ANY
 LIGHTING CONTROLS REQUIRED PER CODE. THIS IS A BUILDING
 GREATER THAN 5K SQ FT A COMPLETE SYSTEM AND OR
 AUTOMATED LIGHTING SYSTEMS WITH OVER RIDES MUST BE
 DESIGNED.
 ** AS NO COMPLIANCE WITH THESE SECTIONS OF THE CODE ARE
 SHOWN, WHEN PLANS ARE RESUBMITTED THIS WILL BE THE
 FIRST REVIEW UNDER NEW DESIGN.
  
 8) NOTE: ALL CIRCUITING ON PLANS SHALL BE COMPLETE WITH
 ALL CIRCUIT NUMBERS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES. ALL PANEL SCHEDULES SHALL BE SPECIFIC
 TO ALL ROOMS AND AREAS IN WHICH THEY FEED. STATING
 *LIGHTING* OR RECEPTACLES* IS NOT ACCEPTABLE. PLEASE
 SEE NEC 408.4 AS THE 2005 NEC WAS REVISED TO STATE THE
 USE OF SUCH TERMS IS NOT PERMITTED.
 PLEASE SEE COMMENTARY IN THE HANDBOOK.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2
  
 9) NOTE: ALL EXIT SIGNS AND EMERGENCY LIGHTING SHALL BE
 COMPLETE PER 700.12F . ALL UNIT EQUIPMENT SHALL BE
 CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT.
  
 10) NOTE: SHOW WINDOW RECEPTACLES REQUIRED PER 210.62.
  
 11) NOTE: PLEASE SEE 220.14G AND 220.43 FOR LOAD
 CALCULATIONS WITH RESPECT TO SHOW WINDOWS.
  
 12) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS PER
 NEC 220. 220.12,220.14,220.42,220.44,220.50, ETC
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN PER
 215.3, 230.42 AT 125%.
  
 13) NOTE: PLEASE SEE 424.3 FOR MINIMUM OCP FOR AIR
 CONDITIONING EQUIPMENT.
 AS INFORMATION IS NOT COMPLETE, MINIMUM OVER CURRENT
 PROTECTION CAN NOT BE VERIFIED.
  
 14) NOTE: ALL SERVICE EQUIPMENT AND SERVICE RISER
 EQUIPMENT NEEDS TO MEET MINIMUM CODES. AS THE DESIGN
 SHOWN IS NOT COMPLETE ONLY SOME ITEMS WILL BE GIVEN AS
 EXAMPLES;
  
 EXAMPLE: COMPLETE RISER, PANELS ETC NEED TO BE SPECIFIC
 AND SHOWN. AN EXAMPLE WOULD BE PANEL ON THE SECONDARY
 SIDE OF THE TRANSFORMER DOES NOT SHOW ANY COMPLIANCE
 WITH 240.21 FOR TAPPED CONDUCTORS ON THE SECONDARY SIDE
 OF TRANSFORMERS.
  
 EXAMPLE: COMPLIANCE FOR 408.36 FOR LIGHTING AND
 APPLIANCE PANELS IS ALSO NOT SHOWN.
  
 EXAMPLE: NO GROUNDING FOR TRANSFORMER PER
 250.50,250.66,250.20,250.30 IS SHOWN. IN FACT NO
 GROUNDING ELECTRODE IS SHOWN WITH REQUIRED CONDUCTORS.
  
 EXAMPLE: COMPLETE AIC RATINGS FOR ALL SERVICE EQUIPMENT
 MEETING FPL AVAILABLE FAULT CURRENTS PER 110.9
  
 ** THESE ARE SOME EXAMPLES ONLY, THERE ARE OTHER ITEMS.
  
 15) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND.3. PLEASE
 SHOW COMPLETE DEVICES FOR ADA COMPLIANCE.
  
 16) NOTE: AS STATED IN BEGINNING OF REVIEW AT LEAST ONE
 SET OF PLANS ARE BEING RETAINED DUE TO NOTES ABOVE AND
 STATUTORY REQUIREMENTS.
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-08-17 Cont ID  
Sent By mawillia Date 2009-08-17 Time 11:14 Rev Time 0.00
Received By mawillia Date 2009-08-17 Time 10:36 Sent To  
Notes
2009-08-17 11:09:48*****REVISION APPROVED*****
  
 REVIEWED REVISED SHEET A-3, A-4, AND FIRE-STAMPED A-16;
 THE PLANS WERE REDLINED AS FOLLOWS:
  
 * A-16 WAS ADDED TO THE INDEX OF DRAWING ON THE COVER
 SHEET (CITY'S FILE SET)
 * A-16'S DIRECTIONAL ARROW WAS CORRECTED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2009-08-13 Cont ID  
Sent By mawillia Date 2009-08-13 Time 11:25 Rev Time 0.00
Received By mawillia Date 2009-08-13 Time 10:37 Sent To B1
Notes
2009-08-13 11:25:27*****DENIED*****
  
  
 1. THE FLOOR LAYOUT OF THE NEWLY SUBMITTED SHEET A-16
 DOES NOT CORRESPOND WITH THE FLOOR LAYOUT OF THE
 ARCHITECTURAL SHEETS IN THE CITY'S FILED SET.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-06-01 Cont ID  
Sent By mawillia Date 2009-06-01 Time 15:54 Rev Time 0.00
Received By mawillia Date 2009-06-01 Time 14:13 Sent To  
Notes
2009-06-02 10:21:21*****APPROVED*****
  
 THE PLANS WERE REDLINED WITH THE FOLLOWING:
  
 ON THE COVER SHEET:
  
 1. THE CORRECT NUMBER FOR WEST PALM BEACH FIRE RESCUE
 OF 561-804-4700 WAS REFLECTED.
 2. THE CORRECT ADDRESS FOR CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES WAS LISTED.
 3. FA-1 SHEET ADDED TO THE INDEX OF DRAWING
  
 ON SHEET A-2:
  
 1. CHANGED INCORRECT EDITION OF NFPA 70 IS TO THE 2005
 EDITION WHICH SHALL BE REFERENCED.
  
 ON SHEET FA-1:
  
 1. THE CORRECT NUMERICAL ADDRESS ADDED IN THE TITLE
 BLOCK.
  
 *******************************************************
 *******************************************************
 **********
  
 PLAN SHEETS A-5, A-13, E-2, FS-1, AND FA-1 WERE
 STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-05-11 Cont ID  
Sent By mawillia Date 2009-05-11 Time 13:25 Rev Time 0.00
Received By mawillia Date 2009-05-11 Time 12:19 Sent To  
Notes
2009-05-11 13:25:13*****DENIED*****
  
 *PREVIOUS FIRE PLAN REVIEW COMMENTS WHICH STILL NEED TO
 BE ADDRESSED:
  
 1. ON SHEET A-1 UNDER APPLICABLE CODES, AMEND CODES TO
 CURRENT EDITIONS SUCH AS: 2006 NFPA 101 AND FLORIDA
 FIRE PREVENTION CODE 2007. PLEASE ADDRESS
  
 2. ON SHEET A-5, AMEND NOTES TO REFLECT CURRENT CODES
 SUCH AS: NFPA 101 (2006 EDITION), FLORIDA FIRE
 PREVENTION CODE (2007 EDITION), AND NFPA 241 - 2004
 EDITION. THE PREVIOUSLY SUBMITTED PLAN SHEET A-5 WAS
 THE LIFE SAFETY DRAWING, WHEREAS THE A-5 SHEET
 SUBMITTED WITH THIS REVIEW INDICATES THE DRAWING FOR
 THE ROOF AND CEILING. WHERE IS THE LIFE SAFETY PLAN
 DRAWING?
  
 3. OK
  
 4. ON SHEET E-3, AMEND GENERAL ELECTRIC NOTES (NOTE #1)
 TO REFLECT NFPA 70 - 2005 EDITION AND NFPA 101 - 2006
 EDITION. PLEASE ADDRESS
  
 5. LIST THE OCCUPANT LOAD FOR THIS PROPOSED PROJECT
 SITE. PLEASE ADDRESS
  
 6. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THE
 PROPOSED PROJECT SITE. PLEASE ADDRESS
  
 7. SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A OR CLASS B. PLEASE ADDRESS
  
 8. SPECIFY INTERIOR FLOOR FINISH IN EXIT ENCLOSURES IN
 TERMS OF CLASS I OR CLASS II. PLEASE ADDRESS
  
 9. OK
  
 *NEW COMMENTS:
  
 A. THE PREVIOUSLY SUBMITTED PLAN SHEET A-4 (AND ALSO
 WHAT IS IS SHOWN IN THE INDEX OF DRAWINGS SECTION OF
 THE COVER SHEET) INDICATES THAT THIS IS THE FLOOR PLAN
 - DETAILS (PARTIAL) DRAWING; HOWEVER THE ACTUAL
 SUBMITTED PLAN SHEET A-4 DISPLAYS AN EXTERIOR ELEVATION
 DRAWING.
  
 B. ON THE APPROPIATE EXTERIOR ELEVATION FRONTING
 OKEECHOBEE BOULEVARD, DISPALY/SHOW THE NUMERICAL
 ADDRESS OF THE PROJECT SITE. AS PER WEST PALM BEACH
 CODE, THE ADDRESS NUMBERS SHALL BE NO LESS THAN 6" IN
 HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-09 Cont ID  
Sent By mawillia Date 2009-04-09 Time 12:38 Rev Time 0.00
Received By mawillia Date 2009-04-09 Time 11:18 Sent To  
Notes
2009-04-09 12:38:39*****DENIED*****
  
 1. ON SHEET A-2 UNDER APPLICABLE CODES, AMEND CODES TO
 CURRENT EDITIONS SUCH AS: 2006 NFPA 101 AND FLORIDA
 FIRE PREVENTION CODE 2007.
  
 2. ON SHEET A-5, AMEND NOTES TO REFLECT CURRENT CODES
 SUCH AS: NFPA 101 (2006 EDITION), FLORIDA FIRE
 PREVENTION CODE (2007 EDITION), AND NFPA 241 - 2004
 EDITION.
  
 3. ON SHEET A-7, INDICATE IN DOOR SCHEDULE WHICH DOORS
 ARE TO BE FIRE RATED AND HAVE DOOR CLOSERS (SEE DOOR #3
 - MECHANICAL ROOM & DOOR #6 - JANITOR'S CLOSET. PLEASE
 BE ADVISED THAT FIRE DOORS AND WINDOWS SHALL COMPLY
 WITH NFPA 80 - 1999 EDITION.
  
 4. ON SHEET E-3, AMEND GENERAL ELECTRIC NOTES (NOTE #1)
 TO REFLECT NFPA 70 - 2005 EDITION AND NFPA 101 - 2006
 EDITION.
  
 5. LIST THE OCCUPANCY TYPE (I.E. BUSINESS, MERCANTILE,
 ASSEMBLY) AND OCCUPANT LOAD FOR THIS PROPOSED PROJECT
 SITE.
  
 6. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THE
 PROPOSED PROJECT SITE.
  
 7. SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A OR CLASS B.
  
 8. SPECIFY INTERIOR FLOOR FINISH IN EXIT ENCLOSURES IN
 TERMS OF CLASS I OR CLASS II.
  
 9. BE ADVISED THAT CITY HALL (FORMERLY 200 2ND STREET)
 IS CURRENTLY ADDRESSED/LOCATED AT 401 CLEMATIS STREET,
 WEST PALM BEACH, 33401. AMEND JURISDICTIONAL AUTHORIES
 INFORMATION ON THE COVER SHEET.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-08-26 Cont ID  
Sent By lmartine Date 2009-08-26 Time 17:23 Rev Time 0.00
Received By lmartine Date 2009-08-26 Time 17:23 Sent To  
Notes
2009-08-26 17:23:38GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-08-19 Cont ID  
Sent By lmartine Date 2009-08-19 Time 11:26 Rev Time 0.00
Received By lmartine Date 2009-08-19 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-19 Cont ID  
Sent By lmartine Date 2009-08-03 Time 11:24 Rev Time 0.00
Received By lmartine Date 2009-08-03 Time 10:25 Sent To  
Notes
2009-08-04 10:28:00TO S. HILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-05-05 Cont ID  
Sent By rregueir Date 2009-05-05 Time 08:40 Rev Time 0.00
Received By rregueir Date 2009-05-05 Time 08:39 Sent To B
Notes
2009-05-05 08:39:59ROUTED TO DOUG WISE DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-09 Cont ID  
Sent By mawillia Date 2009-04-09 Time 12:40 Rev Time 0.00
Received By mawillia Date 2009-03-27 Time 16:06 Sent To  
Notes
2009-03-27 16:06:28TO IN-BOX "C21"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-24 Cont ID  
Sent By rregueir Date 2009-07-24 Time 16:00 Rev Time 0.00
Received By rregueir Date 2009-07-24 Time 16:00 Sent To PC
Notes
2009-07-24 16:00:45REVISED M1 DELTA 3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-03-31 Cont ID  
Sent By rregueir Date 2009-03-31 Time 13:37 Rev Time 0.00
Received By rregueir Date 2009-03-31 Time 10:20 Sent To  
Notes
2009-03-31 13:37:14******PROVISO******
 1. OUTDOOR APPLIANCES (ROOFTOP UNITS) SHALL BE DESIGNED
 AND INSTALLED FOR WIND RESISTANCE IN ACCORDANCE WITH
 FBC-M 301.12. PROVIDE DATA SHOWING UNITS AR3E DESIGNED
 FOR WIND RESISTANCE PRIOR TO MECHANICAL INSPECTION.
  
 2. PROVIDE DETAIL WITH SUPPORTING WIND LOAD
 CALCULATIONS FOR ATTACHMENT OF RTU AND CURB IN
 ACCORDANCE WITH FBC-M 301.12.
  
 3. RTU DETAIL ON M-2 SHOWS FLOAT SWITCH OUTSIDE UNIT IN
 THE PRIMARY DRAIN LINE. ON DOWN-FLOW UNITS THE
 WATER-LEVEL MONITORING DEVICE SHALL BE INSTALLED INSIDE
 THE PRIMARY DRAIN PAN IN ACCORDANCE WITH FBC-M
 307.2.3.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-07-13 Cont ID  
Sent By kstevens Date 2009-07-13 Time 09:24 Rev Time 0.00
Received By kstevens Date 2009-07-13 Time 09:24 Sent To  
Notes
2009-07-13 09:25:10REVISIONS OK -- SHTS P-3 & P-4

Review Stop P PLUMBING
Rev No 4 Status F Date 2009-07-07 Cont ID  
Sent By kstevens Date 2009-07-07 Time 13:25 Rev Time 0.00
Received By kstevens Date 2009-07-07 Time 13:25 Sent To  
Notes
2009-07-07 13:30:13DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 PDI-WH 201
  
 1. SHT P-3 NEW PLUMBING NOTES #13. AIR CHAMBERS ARE NOT
 APPROVED. PDI-WH 201 PLEASE DELETE FROM NOTES.
  
 2. SHT P-4 WATER ISOMETRIC RISER DIAGRAM. THE WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-07-07 Cont ID  
Sent By kstevens Date 2009-07-07 Time 13:25 Rev Time 0.00
Received By kstevens Date 2009-07-07 Time 13:24 Sent To  
Notes
2009-07-07 13:25:57REVISIONS OK -- SHTS P-1 & P-2.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-05-11 Cont ID  
Sent By dwise Date 2009-05-11 Time 17:23 Rev Time 0.00
Received By dwise Date 2009-05-11 Time 17:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-04-08 Cont ID  
Sent By kstevens Date 2009-04-08 Time 17:53 Rev Time 0.00
Received By kstevens Date 2009-04-08 Time 17:53 Sent To  
Notes
2009-04-08 18:21:26DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE SEAL FOR THE ARCHITECT DOES NOT IMPRESS ALL
 INFORMATION REQUIRED BY FAC 61G1-16.001 &
 61G1-16.002(2) & FS 481.2055. PLEASE RESEAL ALL SHEETS
 WHICH DO NOT IMPRESS THE REQUIRED INFORMATION.
  
 2. SHT A-8 ADA BATHROOM CLEARANCE PLAN. THE LAVS SHALL
 NOT BE IN THE CLEAR FLOOR SPACE FOR THE WATER CLOSETS.
 SEE FIGURE 11-30E. LAVS SHALL BE A MINIMUM 15" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE TO BE CENTERED ON
 THE 30" DIMENTION OF THE CLEAR FLOOR SPACE REQUIRED FOR
 THE LAV. PLEASE INDICATE ON PLANS.
  
 3. SHT A-8 DETAIL FOR THE W/C GRAB BARS DOES NOT SHOW
 THE GRAB BAR LENGTH BEHIND THE WATER CLOSET. MINIMUM 36
 INCH GRAB BAR IS REQUIRED, SECTION 11-4.16.4. PLEASE
 INDICATE ON PLANS.
  
 4. SHT P-4 WATER ISOMETRIC RISER DIAGRAM SHOW WHAT
 APPEAR TO BE AIR CHAMBERS AT EACH FIXTURE. AIR CHAMBERS
 ARE NOT APPROVED. PLEASE DELETE. SECTION 604.9 WATER
 HAMMER ARRESTORS ARE REQUIRED ONLY ON QUICK CLOSING
 VALVES AND SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING IF USED. PDI-WH
 201.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-04-08 Cont ID  
Sent By kdfreema Date 2009-04-08 Time 13:44 Rev Time 0.00
Received By kdfreema Date 2009-04-08 Time 13:44 Sent To  
Notes
***NONE***