Plan Review Details - Permit 09030469
Plan Review Stops For Permit 09030469
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-19 Cont ID  
Sent By dwise Date 2009-06-19 Time 13:23 Rev Time 0.00
Received By dwise Date 2009-06-19 Time 13:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-09 Cont ID  
Sent By jwitmer Date 2009-04-09 Time 16:14 Rev Time 1.25
Received By jwitmer Date 2009-04-09 Time 16:14 Sent To  
Notes
2009-04-09 17:25:36BUILDING PLAN REVIEW
 PERMIT: 09030469
 ADD: 3071 CONTINENTAIL DR.
 CONT: VAN'S ELECTRIC
 TEL: (561)584-1077
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 APRIL 9/09
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH THE 2009 SUPPLEMENTS.
  
 1F) (2007 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2) IT APPEARS THE INSTALATION OF THIS GENERATOR AND
 TANK ARE ON THE EXTERIOR OF THE BUILDING AND EXPOSED TO
 WIND. PLEASE PROVIDE THE WIND DESIGN CRITERIA. 1603.1.4
 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 2A). BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2B). WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2C) . WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2D). THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 3) THE PLAN INDICATES THE REUSE OF AN EXISTING SLAB.
 2702.1 INSTALLATION.
  
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL BE INSTALLED
 IN ACCORDANCE WITH THE NFPA 70, NATIONAL ELECTRICAL
 CODE, NFPA 110 AND NFPA 111.
 NFPA 110:
 3A) 7.4 MOUNTING.
  
 7.4.1 ROTATING ENERGY CONVERTERS SHALL BE INSTALLED ON
 SOLID FOUNDATIONS TO PROHIBIT SAGGING OF FUEL, EXHAUST,
 OR LUBRICATING-OIL PIPING AND DAMAGE TO PARTS RESULTING
 IN LEAKAGE AT JOINTS.
  
 7.4.1.1 SUCH FOUNDATIONS OR STRUCTURAL BASES SHALL
 RAISE THE ENGINE AT LEAST 150 MM (6 IN.) ABOVE THE
 FLOOR OR GRADE LEVEL AND BE OF SUFFICIENT ELEVATION TO
 FACILITATE LUBRICATING-OIL DRAINAGE AND
 EASE OF MAINTENANCE.
  
 7.4.2 FOUNDATIONS SHALL BE OF THE SIZE (MASS) AND TYPE
 RECOMMENDED BY THE ENERGY CONVERTER MANUFACTURER.
  
 7.4.3 WHERE REQUIRED TO PREVENT TRANSMISSION OF
 VIBRATION DURING OPERATION, THE FOUNDATION SHALL BE
 ISOLATED FROM THE SURROUNDING FLOOR OR OTHER
 FOUNDATIONS, OR BOTH, IN ACCORDANCE WITH THE
 MANUFACTURER'S RECOMMENDATIONS AND ACCEPTED STRUCTURAL
 ENGINEERING PRACTICES.
  
 7.4.4 THE EPS SHALL BE MOUNTED ON A FABRICATED METAL
 SKID BASE OF THE TYPE THAT SHALL RESIST DAMAGE DURING
 SHIPPING AND HANDLING. AFTER INSTALLATION, THE BASE
 SHALL MAINTAIN ALIGNMENT OF THE
 UNIT DURING OPERATION. PLANS DO NOT PROVIDE INFORMATION
 FOR SECONDARY CONTAINMENT. NFPA 110: 7.9.12 LISTED
 GENERATOR SUBBASE SECONDARY CONTAINMENT FUEL TANKS OF
 2498 L (660 GAL)
 CAPACITY AND BELOW SHALL BE PERMITTED TO BE INSTALLED
 OUTDOORS OR INDOORS WITHOUT DIKING OR REMOTE
 IMPOUNDING. PLANS INDICATE 1200 GALLON CAPACITY.
  
 4) PLANS FAIL TO PROVIDE INFORMATION FOR THE FOUNDATION
 AND SLAB FOR GENERATOR A TANK, PLEASE PROVIDE DETAILS
 FOR ANCHORING OF TANK AND GENERATOR AGAINST OVERTURNING
 ,UPLIFT AND SLIPPAGE FBC
 BUILDING 1609.1.3.
  
 5) FOR MAINTENANCE AND WEEKLY VISUAL INSPECTION OF
 GENERATOR A ELEVATED PLATFORM, STAIR AND GUARDRAIL
 SYSTEM WILL BE REQUIRED. NFPA 110: 8.4 OPERATIONAL
 INSPECTION AND TESTING.
  
 8.4.1* EPSSS, INCLUDING ALL APPURTENANT COMPONENTS,
 SHALL BE INSPECTED WEEKLY AND EXERCISED UNDER LOAD AT
 LEAST MONTHLY.
  
 6) STAIRS 1009.3 EXCEPTION# 7. INDUSTRIAL EQUIPMENT
 ACCESS STAIRS AND LANDINGS THAT SERVE AS A COMPONENT OF
 THE MEANS OF EGRESS FROM THE INVOLVED EQUIPMENT AND DO
 NOT SERVE MORE THAN
 20 PEOPLE SHALL BE PERMITTED TO HAVE A MINIMUM CLEAR
 WIDTH OF 22 INCHES (559 MM), MINIMUM TREAD DEPTH OF 10
 INCHES (254 MM), MAXIMUM RISER HEIGHT OF 9 INCHES (229
 MM), MINIMUM
 HEADROOM OF 6 FEET 8 INCHES (2032 MM), AND A MAXIMUM
 HEIGHT BETWEEN LANDINGS OF 12 FEET (36 576 MM).
  
 7) GAURDRAILS: 1012.1 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INDUSTRIAL EQUIPMENT PLATFORMS, LANDINGS
 WHICH ARE LOCATED MORE THAN 30 INCHES (762 MM) ABOVE
 THE FLOOR OR GRADE BELOW.
 GUARDS SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN
 ACCORDANCE WITH SECTION 1607.7.
  
 8) GUARD 1012.3 OPENING LIMITATIONS. EXCEPTIONS:
 2. AT ELEVATED WALKING SURFACES FOR ACCESS TO AND USE
 OF ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS OR
 EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE OF SOLID
 MATERIALS SUCH THAT A
 SPHERE WITH A DIAMETER OF 21 INCHES (533 MM) CANNOT
 PASS THROUGH ANY OPENING.
 3. IN AREAS WHICH ARE NOT OPEN TO THE PUBLIC WITHIN
 OCCUPANCIES IN GROUP I-3, F, H OR S, BALUSTERS,
 HORIZONTAL INTERMEDIATE RAILS OR OTHER CONSTRUCTION
 SHALL NOT PERMIT A SPHERE WITH A
 DIAMETER OF 21 INCHES (533 MM) TO PASS THROUGH ANY
 OPENING.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-07-20 Cont ID  
Sent By dpalmer Date 2009-07-20 Time 14:45 Rev Time 0.00
Received By dpalmer Date 2009-07-20 Time 14:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-06-19 Cont ID  
Sent By dwise Date 2009-06-19 Time 13:23 Rev Time 0.00
Received By dwise Date 2009-06-19 Time 13:23 Sent To  
Notes
2009-06-19 13:24:41PREVIOUSLY REQUESTED CORRECTIONS HAVE NOT BEEN MADE.
 PLEASE CONTACT ME AT 805-6650
 THANK YOU, DOUG WISE

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-17 Cont ID  
Sent By dpalmer Date 2009-04-17 Time 15:51 Rev Time 0.00
Received By dpalmer Date 2009-04-17 Time 15:51 Sent To  
Notes
2009-04-17 15:51:49** DENIED**
  
  
  
 1) NOTE: ALL PLANS SHALL CONTAIN THE MINIMUM CODES
 UNDER WHICH DESIGNED.
 PLEASE KNOW THAT ALL PROJECTS SUBMITTED AFTER MARCH
 1ST, 2009 SHALL BE UNDER THE FOLLOWING CODES.
 2007 FBC W/ 2009 AMENDMENTS
 2002 NFPA-110
 2005 NFPA70
  
 ** AS PLANS DO NOT INDICATE WHETHER OR NOT ANY LIFE
 SAFETY SYSTEMS ARE FED FROM THE NEW PROPOSED UNIT, SOME
 ITEMS CAN NOT BE REVIEWED FOR CODE COMPLIANCE.
 PLEASE ALSO SEE 2006 NFPA-101 FOR MINIMUM REQUIREMENTS.
 FS 553.73
  
 2) NOTE: PLEASE SEE FS 471.003 AND 481.229. ANY
 PROJECTS UNDER THE EXEMPTION SHALL CONTAIN THE PRINTED
 NAME AND SIGNATURE OF THE PERSON UNDER WHICH LICENSE IS
 APPLIED FOR TAKING RESPONSIBILITY OF SAID PLANS.
  
 3) NOTE: PLEASE SEE 250.6, 250.24 AS EQUIPMENT
 GROUNDING CONDUCTORS ARE NOT PERMITTED BEFORE THE FIRST
 MEANS OF DISCONNECT.
  
 4) NOTE: PLEASE PROVIDE ANY INFORMATION FOR ANY 700-701
 SYSTEMS.
  
 5) NOTE: PLEASE BE AWARE OF COMMENTS WITH RESPECT TO
 SERVICE PLATFORMS, ACCESS, GUARD RAILS ETC.
 PLEASE BE AWARE OF COMMENTS REGARDING DERM APPROVAL FOR
 THE 1200 GALLON TANK.
 PLEASE BE AWARE OF COMMENTS WITH RESPECT TO MINIMUM
 ELEVATIONS AND SLAB INFORMATION.
 ** NO INFORMATION SUBMITTED OR SHOWN FOR MANY OF THE
 ABOVE ITEMS.
 PLEASE SEE NFPA-110 2002 CHAPTER 7 FOR REQUIRED MINIMUM
 CODE COMPLIANCE.
  
 6) NOTE: PLANS NEED TO BE COMPLETE AND SHOW SUFFICIENT
 DETAILS FOR MINIMUM CODES AS NOTED ABOVE.
 PLEASE SEE NFPA-110 , FBC CHAPTER 10, 27, AND NEC
 700,701,702.
 ** THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW
 WHICH CAN NOT BE MADE AT THIS TIME.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-24 Cont ID  
Sent By mawillia Date 2009-07-24 Time 12:23 Rev Time 0.00
Received By mawillia Date 2009-07-24 Time 12:09 Sent To  
Notes
2009-07-24 12:23:42*****PROVISO*****
  
 PLAN SHEET S.1 WAS STAMPED, INITIALED, AND DATED WITH
 THE FOLLOWING PROVISO(S):
  
 **THE ENTIRE INSTALLATION TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 **EMERGENCY GENERATORS AND/OR STANDBY GENERATORS SHALL
 BE INSTALLED, TESTED, AND MAINTAINED IN ACCORDANCE WITH
 NFPA 110, STANDARD FOR EMERGENCY AND STANDBY
 GENERATORS.
  
 **IF NECESSARY, THE APPROPIATE DEVICES SHALL BE
 INSTALLED TO PREVENT POSSIBLE COLLISION TO THE
 GENERATOR FROM PASSING VEHICLES AND/OR OTHER MACHINERY.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-23 Cont ID  
Sent By mawillia Date 2009-04-23 Time 11:03 Rev Time 0.00
Received By mawillia Date 2009-04-23 Time 10:15 Sent To  
Notes
2009-04-23 10:57:44*****DENIED*****
  
 1. THE ENTIRE INSTALLATION TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 2. PLEASE INDICATE WHAT EQUIPMENT THE NEW GENERATOR
 WILL SUPPLY. IS/ARE ANY EMERGENCY EQUIPMENT ( EXIT
 LIGHTS, EMERGENCY LIGHTS, FIRE ALARM SYSTEM, ETC.)
 BEING SUPPLIED POWER FROM THIS GENERATOR?
  
 3. EMERGENCY GENERATORS AND/OR STANDBY GENERATORS SHALL
 BE INSTALLED, TESTED, AND MAINTAINED IN ACCORDANCE WITH
 NFPA 110, STANDARD FOR EMERGENCY AND STANDBY
 GENERATORS.
  
 4. SHOW/DISPLAY DEVICES PLANNED TO PREVENT POSSIBLE
 COLLISION TO THE GENERATOR FROM PASSING VEHICLES.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status P Date 2009-06-19 Cont ID  
Sent By dwise Date 2009-06-19 Time 13:23 Rev Time 0.00
Received By dwise Date 2009-06-19 Time 13:23 Sent To  
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2009-04-21 Cont ID  
Sent By rregueir Date 2009-04-21 Time 16:04 Rev Time 0.00
Received By rregueir Date 2009-04-21 Time 15:59 Sent To  
Notes
2009-04-21 16:04:04PROPOSED ABOVE GROUND FUEL TANKS IN EXCESS OF 550
 GALLONS MUST BE APPROVED BY PALM BEACH COUNTY
 DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT (DERM)
 PRIOR TO PERMIT ISSUANCE. PROVIDE TWO SETS OF PBC DERM
 APPORVED PLANS FOR REVIEW WITH PERMIT APPLICATION. FOR
 MORE INFORMATION ABOUT THE DERM APPROVAL PROCESS,
 PLEASE CONTACT PBC DERM AT HTTP://WWW.PBCGOV.COM/ERM
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-08-27 Cont ID  
Sent By lmartine Date 2009-08-27 Time 11:05 Rev Time 0.00
Received By lmartine Date 2009-08-27 Time 11:05 Sent To  
Notes
2009-08-27 11:06:23IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-06-05 Cont ID  
Sent By lmartine Date 2009-06-04 Time 11:51 Rev Time 0.00
Received By lmartine Date 2009-06-04 Time 11:51 Sent To  
Notes
2009-06-05 11:51:58C-13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-07 Cont ID  
Sent By adarroug Date 2009-04-07 Time 09:32 Rev Time 0.00
Received By adarroug Date 2009-04-07 Time 09:32 Sent To  
Notes
2009-04-07 09:33:23TO "C10" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-27 Cont ID  
Sent By mcruz Date 2009-03-27 Time 08:51 Rev Time 0.00
Received By mcruz Date 2009-03-24 Time 08:51 Sent To  
Notes
2009-03-27 08:51:54DELIVERED TO KF IN ZONING.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-04-21 Cont ID  
Sent By rregueir Date 2009-04-21 Time 15:59 Rev Time 0.00
Received By rregueir Date 2009-04-21 Time 15:59 Sent To FUEL
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2009-09-01 Cont ID  
Sent By kdfreema Date 2009-09-01 Time 08:08 Rev Time 0.00
Received By kdfreema Date 2009-09-01 Time 08:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2009-07-27 Cont ID  
Sent By kdfreema Date 2009-07-27 Time 12:19 Rev Time 0.00
Received By kdfreema Date 2009-07-27 Time 12:19 Sent To  
Notes
2009-07-27 12:22:54PLAN REVIEW UPDATE
  
 MET WITH DAVID HOUGE FROM VAN'S ELECTRIC JULY 27 TO
 DISCUSS ZONING ISSUES WHICH REMAIN UNADDRESSED FROM THE
 FIRST TWO ROUNDS OF COMMENTS ISSUED APRIL 1 AND JUNE
 15. NOTED THAT A MINOR PD AMENDMENT IS REQUIRED PRIOR
 TO ZONING APPROVAL AS WELL IS ADEQUATE SCREENING FOR
 THE GENERATOR. WILL UPDATE WHEN APPLICANT SUBMITS A
 COMPLETE APPLICATION FOR MINOR PD AMENDMENT. THIS
 REVIEW WILL REMAIN IN FAILED STATUS UNTIL ZONING ISSUES
 ARE ADDRESSED.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1458
 OR [email protected] WITH QUESTIONS.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2009-06-15 Cont ID  
Sent By kdfreema Date 2009-06-15 Time 08:28 Rev Time 0.00
Received By kdfreema Date 2009-06-15 Time 08:28 Sent To  
Notes
2009-06-15 10:16:44***FAILED***
  
 **REPEAT COMMENT**
 1. A MINOR PLANNED DEVELOPMENT AMENDMENT IS REQUIRED.
 PLEASE CONTACT ME AT 561-822-1458 OR [email protected]
 TO BEGIN THE PROCESS.
  
 2. THE SITE PLAN DOES NOT SATISFY THE REQUIREMENT THAT
 A SURVEY BE PROVIDED. NOTE THAT THE SURVEY MUST BE
 SIGNED AND SEALED AND NOT OLDER THAN ONE YEAR.
  
 3. THE PLANNING AND ZONING DEPT. VISITED THE SITE TO
 ASSESS CONDITIONS AND NOTED THE GENERATOR HAS ALREADY
 BEEN INSTALLED. THE ACTUAL LOCATION OF THE GENERATOR
 DID NOT APPEAR TO BE IN THE SAME PLACE AS IT WAS SHOWN
 ON THE PLAN. PLEASE MAKE SURE THE PLANS SHOW THE ACTUAL
 LOCATION OF THE GENERATOR.
  
 4. THE PROPOSED SCREENING DOES NOT ADEQUATELY SATISFY
 THE REQUIREMENTS OF THE ZONING CODE. THE GENERATOR
 ITSELF MUST BE SCREENED BY MEANS OF A SOLID, OPAQUE
 WALL OR FENCE WITH A HEDGE AROUND THE EXTERIOR OF THE
 FENCE/WALL.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1458
 OR [email protected] WITH QUESTIONS.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-04-01 Cont ID  
Sent By kdfreema Date 2009-04-01 Time 15:06 Rev Time 0.00
Received By kdfreema Date 2009-04-01 Time 15:06 Sent To  
Notes
2009-04-01 15:11:33***FAILED***
  
 1. A MINOR PLANNED DEVELOPMENT AMENDMENT IS REQUIRED.
 PLEASE CONTACT ME TO BEGIN THE PROCESS.
  
 2. PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE
 GENERATOR INCLUDING ACTUAL SETBACK DISTANCES.
  
 3. THE GENERATOR IS REQUIRED TO BE SCREENED BY A
 WALL/FENCE WITH A HEDGE. THIS MUST BE SHOWN ON THE
 PLANS.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1458
 OR [email protected] WITH QUESTIONS.