Plan Review Details - Permit 09030460
Plan Review Stops For Permit 09030460
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-04-17 Cont ID  
Sent By lmartine Date 2009-04-17 Time 15:12 Rev Time 0.00
Received By lmartine Date 2009-04-17 Time 15:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-14 Cont ID  
Sent By shill Date 2009-04-14 Time 11:28 Rev Time 0.00
Received By shill Date 2009-04-14 Time 11:28 Sent To  
Notes
2009-04-14 11:48:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. FBC*106.3.5, MINIMUM PLAN REVIEW CRITERIA, PLEASE
 PROVIDE AN ARCHITECTURAL QUALITY PLAN WHICH SHOWS SCOPE
 OF WORK. A SKETCH WAS SUBMITTED BUT THE WORDS ARE NOT
 READABLE, SUCH AS "SHOWER INTER WALLS . . . WITH WATER
 BARREZ ON FLOOR" UNSURE OF WHAT THAT MEANS. A
 PHOTOGRAPH WAS INCLUDED BUT A PLAN IS REQUIRED; FLOOR
 PLAN, SECTIONS, ELEVATIONS, ETC. AS NEEDED TO CLEARLY
 SHOW SCOPE OF WORK, MATERIALS USED. THE SCOPE OF WORK
 SHOULD BE CLEAR; IT APPEARS THAT A WALL IS BEING BUILT,
 HOW MANY FEET? IS A WALL BEING BUILT, OR IS THIS
 EXISTING? THE APPLICATION DOES NOT MENTION ANY
 STRUCTURAL WORK, BUT A SHEET IN THE PACKAGE REFERS TO A
 WALL 2X4PT 16"OC. IT IS UNCLEAR WHERE THIS IS LOCATED,
 WIND RESISTANCE (STRAPS), HOW MANY FEET OF WALL, OR IS
 THIS IS A REPAIR?
  
 FLOOR PLAN SHOWS "OLD WASHROOM" AND "NEW WASHROOM." IS
 THIS A NEW PARTITION WALL? IT MAY BE HELPFUL TO INCLUDE
 AN "EXISTING FLOOR PLAN" AS WELL AS A "PROPOSED FLOOR
 PLAN."

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-04-10 Cont ID  
Sent By dpalmer Date 2009-04-10 Time 16:07 Rev Time 0.00
Received By dpalmer Date 2009-04-10 Time 16:07 Sent To  
Notes
2009-04-10 16:09:55WIRING AS SHOWN ON PCITURES NOT PER NEC.
  
 ALL BOX FILL SHALL BE CORRECTED. BOXES SHOWN EXCEED
 CUBIC SQ INCHES FOR BOXES SHOWN.
 DEDICATED CIRCUITS SHALL BE CORRECTED. PICTURES SHAL
 THE REQUIRED DEDICATED WASHER CIRCUIT ON WITH OTHER
 RECEPTACLES WHICH IS NOT PERMITTED.
 WIRING METHODS FOR STRAPING AND INSTALLATION OF
 PROTECTION OF CONDUCTORS PER NEC 300 SHALL BE CORRECTED
 PROTECTION FROM GALVANIC REACTION REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-16 Cont ID  
Sent By lmartine Date 2009-04-16 Time 13:34 Rev Time 0.00
Received By lmartine Date 2009-04-03 Time 08:47 Sent To  
Notes
2009-04-03 08:52:43R12

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-04-15 Cont ID  
Sent By lwagner Date 2009-04-15 Time 09:38 Rev Time 0.00
Received By lwagner Date 2009-04-15 Time 07:37 Sent To  
Notes
2009-04-15 09:38:28***********PROVISO*************
 PLUMBING INSPECTOR WILL INSURE THAT W/M IS EXISTING AND
 NOT CONNECTED TO BATHROOM WET VENT.
  