Plan Review Details - Permit 09030430
Plan Review Stops For Permit 09030430
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-22 Cont ID  
Sent By jwitmer Date 2009-04-22 Time 14:54 Rev Time 1.22
Received By jwitmer Date 2009-04-22 Time 14:54 Sent To  
Notes
2009-04-22 14:57:05REVISION# 3 :
 A-1.0
 A-1.1
 A-1.2
 A-2.0
 A-3.0

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2009-03-30 Cont ID  
Sent By mjacobs Date 2009-03-30 Time 13:16 Rev Time 0.00
Received By mjacobs Date 2009-03-30 Time 13:16 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-03-25 Cont ID  
Sent By mjacobs Date 2009-03-25 Time 13:03 Rev Time 0.00
Received By mjacobs Date 2009-03-25 Time 06:59 Sent To  
Notes
2009-03-25 08:04:45PROVISO: THE GLAZING IN DOOR #1401 ALONG WITH THE
 SIDELITES SHALL BE LABBLED BY AN APPROVED AGENCY IN
 ACCORDANCE WITH FBC 715.4. THE NAME OF THE
 MANUFACTURER, THE THIRD-PARTY INSPECTION AGENCY AND THE
 FIRE PROTECTION RATING ETC.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-28 Cont ID  
Sent By dpalmer Date 2009-04-28 Time 14:46 Rev Time 0.00
Received By dpalmer Date 2009-04-28 Time 14:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-03-24 Cont ID  
Sent By dpalmer Date 2009-03-24 Time 17:49 Rev Time 0.00
Received By dpalmer Date 2009-03-24 Time 17:49 Sent To  
Notes
2009-03-24 17:50:35** PROVISO **
  
 1) NOTE: BATTERY BACK UP FIXTURES OF SOME SORT FOR
 MINIMUM EGRESS LIGHTING LEVEL OF 1FT CANDLE (AVERAGE)
 IS REQUIRED. THESE NEED TO BE CIRCUITED PER 700.12F TO
 LOCAL LIGHTING CIRCUIT IN AREA.
 THIS INCLUDES LOBBY, CORRIDORS AND BATH ROOM AREAS.
 AT THIS POINT IF A SINGLE MEANS OF OVER CURRENT
 PROTECTION WOULD TRIP UNDER NORMAL OR EMERGENCY
 CONDITIONS THERE WOULD BE EGRESS AREAS IN TOTAL
 DARKNESS.
 7.8.1.32, 7.9.1.2, .2.2.
 FBC 1006.1.2
 PLEASE REVISE
  
  
 2) NOTE: ALL ILLUMINATION FOR EMERGENCY LIGHTING
 CONTROL BY OCCUPANCY SENSOR TYPE DEVICE NEEDS TO MEET
 FBC 1006.1.2, NFPA-101 7.8.1.2.2 WHICH REQUIRES DEVICE
 TO BE "FAIL SAFE ON".
 PLEASE REVISE.
  
 3) NOTE: *** FOR INFORMATIONAL PURPOSE. PLEASE SEE
 ASTME-17 FOR REQUIRED MINIMUM FC LEVELS AT THE FLOOR AT
 ELEVATOR SILLS/LANDINGS. THIS IS BASED ON THE STATE
 ELEVATOR CODE AND NOT PART OF THIS REVIEW. ( REQUIRES
 10FC MIN.)
  
 4) NOTE: PER FAC 69A-60.004 THE 2006 NFPA-101 WAS
 ADOPTED ON DECEMEBR 31ST 2008. PLANS INDICATE 2003
 EDITION, PLEASE REVISE.
  
 ** PLANS NEED TO BE REVISED BEFORE ROUGH ELECTRICAL
 INSPECTION. ANY INSTALLATION NOT DONE PER PROVISO
 ISSUED ON PLANS MAY RESULT IN A DELAY OF PROJECT.
 PLEASE CALL IF THERE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-04-23 Cont ID  
Sent By mawillia Date 2009-04-23 Time 10:14 Rev Time 0.00
Received By mawillia Date 2009-04-23 Time 09:59 Sent To  
Notes
2009-04-23 10:02:41*****REVISIONS 1 THRU 3, APPROVED*****
  
  
 REVISED PLAN SHEETS A-1.0, A-1.1, E-1, AND E-2 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-03-30 Cont ID  
Sent By mawillia Date 2009-03-30 Time 11:20 Rev Time 0.00
Received By mawillia Date 2009-03-30 Time 10:28 Sent To  
Notes
2009-03-30 11:19:33*****APPROVED*****
  
  
 PLAN SHEETS A-1.0, A-1.1, FS2.1, AND E-1 & E-2 WERE
 STAMPED, INITIALED, AND DATED.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-22 Cont ID  
Sent By swurafti Date 2009-04-22 Time 09:23 Rev Time 0.00
Received By swurafti Date 2009-04-22 Time 09:23 Sent To  
Notes
2009-04-22 09:23:23TO "B8"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-30 Cont ID  
Sent By mawillia Date 2009-03-30 Time 11:24 Rev Time 0.00
Received By mawillia Date 2009-03-18 Time 17:32 Sent To  
Notes
2009-03-18 17:32:13TO "BOB"#9

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-05-29 Cont ID  
Sent By rregueir Date 2009-05-29 Time 15:46 Rev Time 0.00
Received By rregueir Date 2009-05-29 Time 15:46 Sent To PC
Notes
2009-05-29 15:47:26PAGE M2.1 REVISION 5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-04-29 Cont ID  
Sent By rregueir Date 2009-04-29 Time 16:36 Rev Time 0.00
Received By rregueir Date 2009-04-29 Time 16:36 Sent To PC
Notes
2009-04-29 16:36:26REVISED M2.1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-03-24 Cont ID  
Sent By rregueir Date 2009-03-24 Time 18:31 Rev Time 0.00
Received By rregueir Date 2009-03-24 Time 18:10 Sent To  
Notes
2009-03-24 18:31:17*****PROVISO*****
 1. SIZE OF DUCT AND FIRE DAMPER AT TRANSFER SOUND BOOTS
 NOT LEGIBLE ON PLANS. REVISE PLAN TO SHOW DUCT SIZE
 PRIOR TO INSPECTION. FBC-M 603.3, FBC-B 106.1.1
  
 2. PLANS SHOW FUTURE EXHAUST DUCT ROUTED IN CEILING
 PLENUM. FUTURE EXHAUST CONFIGURATION SHALL NOT CREATE
 POSITIVELY PRESSURIZED EXHAUST DUCT IN PLENUM IN
 ACCORDANCE WITH FBC-M 601.5.
  
 SEE CORRESPONDING REDLINED NOTES ON PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-03-26 Cont ID  
Sent By kstevens Date 2009-03-26 Time 17:23 Rev Time 0.00
Received By kstevens Date 2009-03-26 Time 17:23 Sent To  
Notes
2009-03-26 17:28:41PLUMBING FIXTURES CHANGED OUT IN EXACT LOCATION -
 CHAPTER 11 COMPLIANT.