Plan Review Details - Permit 09030390
Plan Review Stops For Permit 09030390
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-05-15 Cont ID  
Sent By shill Date 2009-05-15 Time 13:45 Rev Time 0.00
Received By shill Date 2009-05-15 Time 13:45 Sent To  
Notes
2009-05-15 13:55:51****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1-3. ADDRESSED.
  
 4. FOOTINGS WERE ADDED TO THE PLAN BUT ARE 8X8 WITH ONE
 #5. THIS IS THE FOOTING TYPICALLY USED FOR ALUMINUM
 STRUCTURES; THIS IS HEAVIER THAN AN ALUMINUM STRUCTURE.
 PLEASE PROVIDE CALCULATIONS TO SHOW THAT THE FOOTINGS
 ARE ADEQUATE FOR THE PROPOSED PATIO.
  
 5-14. ADDRESSED.
  
 15. A ROOF PERMIT WILL BE REQUIRED. FOR FLAT DECKS,
 CONTRACTOR IS TO INDICATE WHICH APPROVED ASSEMBLY WILL
 BE USED AND SPECIFY ENHANCED FASTENING FOR CORNER AND
 PERIMETER ZONES IF REQUIRED. FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED FAC9B72 FOR ROOF COVERING.
  
 THIS CAN BE A PROVISO ITEM (ROOF PERMIT REQUIRED).
  
 16. ADDRESSED.
  
 17. THIS PROPERTY RECEIVED A STOP WORK ORDER FOR
 ELECTRIC WORK PERFORMED WITHOUT A PERMIT. PLEASE
 ADDRESS THIS ISSUE AT THIS TIME OR ADVISE AS TO STATUS
 OF THIS ISSUE.
  
 NEW COMMENTS:
  
 A. SEE ATTACHED FROM IBHS GUIDELINES FOR HURRICANE
 RESISTANT RESIDENTIAL CONSTRUCTION AS AN EXAMPLE
 (ALTHOUGH THIS IS FOR SLOPE 5DEGREES, FLAT HAS MORE
 STRINGENT REQUIREMENTS). THE FOLLOWING ITEMS DO NOT
 COMPLY WITH THE PRESCRIPTIVE DESIGN REQUIREMENTS;
 THEREFORE, REQUIRE CALCULATIONS SHOWING THAT THESE
 ITEMS MEET MINIMUM CODE REQUIREMENTS:
  
 COLUMNS (4X4 POSTS, 10' SPAN, 7' SPACING)
  
 RAFTERS, 2X4 12" SPACING
  
 BEAM, DOUBLE 2X4 WITH FLITCH
  
 8X8 FOOTER (SEE ALSO ITEM 4)
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-03 Cont ID  
Sent By shill Date 2009-04-03 Time 10:48 Rev Time 0.00
Received By shill Date 2009-04-03 Time 10:48 Sent To  
Notes
2009-04-03 11:11:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. DECLARE GOVERNING CODE.
  
 2. DECLARE WIND DESIGN CRITERIA.
  
 3. INCLUDE THE NAME AND SIGNATURE OF THE INDIVIDUAL
 TAKING RESPONSIBILITY FOR THIS DESIGN.
  
 4. NO FOOTINGS ARE SHOWN. PLEASE PROVIDE CALCULATIONS
 TO SHOW THAT THE CONCRETE SLAB IS SUFFICIENT TO SUPPORT
 DEAD LOADS AND RESIST WIND LOADS. FBC R301.
  
 5. SPECIFY NAILING FOR EACH CONNECTOR OR PROVIDE SPEC
 SHEETS FOR EACH CONNECTOR (AVAILABLE ON INTERNET).
  
 6. SEVERAL SHEETS SUBMITTED WITH NO WAY TO IDENTIFY THE
 SHEETS (PAGE NUMBERS, DETAIL LABELS). THIS MAKES IT
 VERY DIFFICULT TO REFER TO SPECIFIC SHEETS OR DETAILS
 FOR PLAN REVIEW. PLEASE ADDRESS.
  
 7. SEE FBC*109, ARCHITECTURAL QUALITY PLANS REQUIRED.
 PLANS ARE TO BE TO SCALE, DIMENSIONED, AND SUFFICIENT
 CLARITY TO SHOW SCOPE OF WORK.
  
 8. DETAIL SHOWS BOTTOM OF 4X4 AT THE TOP OF A 2"
 TOPPING, BUT MANUFACTURER INFORMATION SHOWS THE POST
 RAISED. IS THE ANCHOR EMBEDDED IN THE CONCRETE? PLEASE
 REVISE DRAWING TO CORRECTLY DEPICT PROPOSED WORK OR
 PROVIDE INFORMATION FROM THE MANUFACTURER WHICH ALLOWS
 THE ANCHOR TO BE EMBEDDED AND THE RAISED POST AT
 FINISHED FLOOR LEVEL.
  
 9. PROVIDE A DETAIL, FOUNDATION THROUGH THE ROOF, TO
 SHOW HOW THIS PROPOSED IMPROVEMENT WILL BE STRUCTURALLY
 CONTINUOUS FBC R301.
  
 10. THE ROOF PRODUCT APPROVAL SUBMITTED IS AN
 UNDERLAYMENT WHICH CANNOT BE EXPOSED LONGER THAN 180
 DAYS. HOW LONG AGO WAS THIS PRODUCT INSTALLED?
  
 11. IT APPEARS THAT THE PROPOSED IMPROVEMENT IS
 ATTACHED TO FASCIA BOARD. FASCIA IS NOT A STRUCTURAL
 COMPONENT; THIS CANNOT BE USED TO SUPPORT THE PROPOSED
 IMPROVEMENT. PLEASE SHOW HOW THIS WILL RESIST LOADS,
 FBC R301.
  
 12. IT IS NOT CLEAR HOW THIS HAS BEEN DESIGNED; SEE FBC
 R301.1. IF WFCM WAS USED, PLEASE PROVIDE COPIES OF THE
 PERTINENT CHARTS AND DETAILS TO SHOW THAT THIS PROPOSED
 IMPROVEMENT CAN WITHSTAND DESIGN LOADS. IF ASCE7 WAS
 USED, PLEASE PROVIDE CALCULATIONS FOR ALL STRUCTURAL
 ELEMENTS. FOR INSTANCE, 7 4X4 POSTS WERE SHOWN TO
 SUPPORT A 176 SF STRUCTURE. 2X4 RAFTERS, WITH NO
 SPACING SHOWN, ARE PROPOSED WITH A 9'7" SPAN. PROVIDE
 ALL STRUCTURAL DETAILS, SIZE, SPACING, AND CALCULATIONS
 IF PRESCRIPTIVE DESIGN HAS NOT BEEN IMPLEMENTED FBC
 R301.
  
 13. ROOF FRAMING PLAN, SPECIFY ROOF FRAMING SPACING. IT
 APPEARS THAT THERE MAY BE AN INTERMEDIATE SUPPORTING
 MEMBER IN THE MIDDLE OF THE 9'7" SPAN; THIS SHOULD BE
 SHOWN ON THE ROOF FRAMING PLAN IF IT EXISTS. IF THERE
 IS AN INTERMEDIATE SUPPORT, IT APPEARS THAT IT SPANS
 14'2"; PROVIDE EVIDENCE (CALCULATIONS OR PRESCRIPTIVE
 DESIGN FROM WFCM) THAT THIS COMPLIES WITH DESIGN
 CRITERIA, SEE OTHER COMMENTS.
  
 14. SPECIFY NAILING PATTERN FOR ROOF SHEATHING.
  
 15. A ROOF PERMIT WILL BE REQUIRED. FOR FLAT DECKS,
 CONTRACTOR IS TO INDICATE WHICH APPROVED ASSEMBLY WILL
 BE USED AND SPECIFY ENHANCED FASTENING FOR CORNER AND
 PERIMETER ZONES IF REQUIRED. FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED FAC9B72 FOR ROOF COVERING.
  
 16. SPECIFY ROOF SLOPE; NONE SHOWN FBC R CHAPTER 9. AS
 ROOF TYPE AND PRODUCT HAS NOT BEEN DETERMINED, A
 SPECIFIC CODE SECTION CANNOT BE PROVIDED.
  
 17. THIS PROPERTY RECEIVED A STOP WORK ORDER FOR
 ELECTRIC WORK PERFORMED WITHOUT A PERMIT. PLEASE
 ADDRESS THIS ISSUE AT THIS TIME OR ADVISE AS TO STATUS
 OF THIS ISSUE.
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 11:06 Rev Time 0.00
Received By dpalmer Date 2009-04-29 Time 11:06 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-03 Cont ID  
Sent By shill Date 2009-04-03 Time 11:34 Rev Time 0.00
Received By shill Date 2009-03-18 Time 09:28 Sent To  
Notes
2009-03-18 09:28:54TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2009-05-11 Cont ID  
Sent By mcruz Date 2009-05-11 Time 12:42 Rev Time 0.00
Received By mcruz Date 2009-05-11 Time 12:13 Sent To B
Notes
2009-05-11 12:42:54ROUTED TO SH FOR BLDG REVIEW. ~MC

Review Stop Z ZONING
Rev No 1 Status F Date 2009-03-19 Cont ID  
Sent By mcruz Date 2009-03-19 Time 09:18 Rev Time 0.00
Received By mcruz Date 2009-03-19 Time 09:15 Sent To B
Notes
2009-03-19 09:17:57PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. AS THE PROPOSED CONCRETE PATIO MAY ENCROACH ONTO A
 UTILITY EASEMENT, EASEMENT CONSENT FORMS ARE REQUIRED
 FROM THE FOLLOWING UTILITY COMPANIES:
  
 WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT
 200 2ND STREET
 CITY HALL, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 (561)822-1300
  
 FLORIDA POWER AND LIGHT
 810 CHARLOTTE AVE
 WEST PALM BEACH, FL 33401
 (561)697-8000
  
 FLORIDA PUBLIC UTILITIES
 401 SOUTH DIXIE HWY
 WEST PALM BEACH, FL 33402
 (561)832-2461
  
 BELL SOUTH
 2021 SOUTH MILITARY TRAIL
 WEST PALM BEACH, FL 33415
 (561)439-9110
  
 COMCAST
 1401 NORTHPOINT PKWY
 WEST PALM BEACH, FL 33407
 (561)655-3842 - RESIDENTIAL
 (561)227-4261 - COMMERCIAL
  
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  