| 2009-04-03 12:47:56 | ** DENIED ** |
| | |
| | |
| | 1) NOTE: PLEASE PROVIDE WIRING METHODS/DETAILS ON |
| | PLANS. PLEASE ALSO SEE NEC 300.21, NFPA-221 ASTME119, |
| | ANSI/UL263 ETC MINIMUM STANDARDS FOR SPREAD OF FIRE. |
| | NEED TO PROVIDE WALL AND FLOOR DETAILS FOR THROUGH |
| | PENETRATIONS OF RATED ASSEMBLIES. |
| | |
| | 2) NOTE: FBC 1019.1.2 NO SYSTEMS SHALL PENETRATE INTO |
| | THE STAIRS. THE CAMERAS ARE NOT PERMITTED. THIS HAS |
| | BEEN CONFIRMED WITH THE FIRE MARSHAL. |
| | THIS HAS ALSO BEEN IN MULTIPLE DECLARATORY STATEMENTS |
| | FROM THE FLORIDA BUILDING COMMISSION/BOAF. |
| | |
| | 3) NOTE: PLEASE BE SURE PLANS CONTAIN THE MINIMUM |
| | RELEVANT ADOPTED CODES PER FS 553.73 |
| | 2007 FBC W/ 2009 GLITCH AMENDMENTS |
| | 2005 NFPA-70 |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |