Plan Review Details - Permit 09030362
Plan Review Stops For Permit 09030362
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-20 Cont ID  
Sent By dpalmer Date 2009-04-20 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2009-04-20 Time 16:14 Sent To  
Notes
2009-04-20 16:16:52NEEDS NEW RECORDED NOC AS THE LOCATION ADDRESS IS SHOWN
 AS HOUSTON TEXAS WHICH IS ALSO OWNER/OFFICE LOCATION.
 NOT THE LOCATION OF THE SCOPE OF WORK. A NEW RECORDED
 NOC NEEDS TO BE SUBMITTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-03 Cont ID  
Sent By dpalmer Date 2009-04-03 Time 12:47 Rev Time 0.00
Received By dpalmer Date 2009-04-03 Time 12:47 Sent To PC
Notes
2009-04-03 12:47:56** DENIED **
  
  
 1) NOTE: PLEASE PROVIDE WIRING METHODS/DETAILS ON
 PLANS. PLEASE ALSO SEE NEC 300.21, NFPA-221 ASTME119,
 ANSI/UL263 ETC MINIMUM STANDARDS FOR SPREAD OF FIRE.
 NEED TO PROVIDE WALL AND FLOOR DETAILS FOR THROUGH
 PENETRATIONS OF RATED ASSEMBLIES.
  
 2) NOTE: FBC 1019.1.2 NO SYSTEMS SHALL PENETRATE INTO
 THE STAIRS. THE CAMERAS ARE NOT PERMITTED. THIS HAS
 BEEN CONFIRMED WITH THE FIRE MARSHAL.
 THIS HAS ALSO BEEN IN MULTIPLE DECLARATORY STATEMENTS
 FROM THE FLORIDA BUILDING COMMISSION/BOAF.
  
 3) NOTE: PLEASE BE SURE PLANS CONTAIN THE MINIMUM
 RELEVANT ADOPTED CODES PER FS 553.73
 2007 FBC W/ 2009 GLITCH AMENDMENTS
 2005 NFPA-70
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-17 Cont ID  
Sent By swurafti Date 2009-04-17 Time 16:35 Rev Time 0.00
Received By swurafti Date 2009-04-17 Time 16:35 Sent To E
Notes
2009-04-17 16:36:14TO "DPALMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-03 Cont ID  
Sent By   Date 2009-04-03 Time   Rev Time 0.00
Received By shill Date 2009-03-16 Time 16:47 Sent To  
Notes
2009-03-16 16:47:58TO "E" BOX