Plan Review Details - Permit 09030356
| Plan Review Stops For Permit 09030356 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-10-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-10-01 |
Time |
08:07 |
Rev Time |
0.25 |
| Received By |
jwitmer |
Date |
2009-10-01 |
Time |
08:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-05-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-05-06 |
Time |
15:46 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2009-05-06 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2009-05-06 16:40:27 | BUILDING PLAN REVIEW | | | PERMIT: 09030356 | | | ADD: 2730 S DIXIE HWY | | | CONT: RUSSELL W CLARK, LLC | | | TEL: (561)306-3634 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER | | | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC | | | BUILDING WITH 2009, 2007 EXISTING BUILDING CODEW/ 2009 | | | SUPPLEMENTS. PLEASE INDICATE TO WHAT LEVEL OF | | | ALTERATION IS TO TAKE PLACE OR HAS TAKEN PLACE UNDER | | | THIS PERMIT. 401.4 A DESIGN PROFESSIONAL OR AN OWNER | | | MUST ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION | | | PURSUANT TO SECTIONS 403, 404 AND 405 OF THIS CODE. | | | | | | 3) THE PRE-INSPECT INDICATED WORK HAS ALREADY STARTED, | | | PLEASE INDICATE THE SCOPE OF WORK TO BE REVIEWED UNDER | | | THIS PERMIT. DEPENDING ON THE SCOPE OF WORK THE DOLLAR | | | AMOUNT LISTED ON THE PERMIT APPLICATION WILL CHANGE. W | | | P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. | | | ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, | | | AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, | | | A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN | | | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE | | | APPLICABLE GOVERNING AUTHORITY. | | | | | | 108.3* BUILDING PERMIT VALUATION. | | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE | | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | 4) PLEASE PROVIDE THE FOLLOWING INFORMATION TO | | | DETERMINE THE MINIMUM BASE BUILDING REQUIREMENTS (TABLE | | | 503/ 601. 110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & | | | FOR CERTIFICATE OF OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | | DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503/ | | | CHAPTER 6, TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED | | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | | BUILDING PERMIT | | | .H ) NUMBER OF FLOORS/ OCCUPANCY SEPERATION? | | | I ) SQ. FT. FOOTPRINT | | | | | | 5) PLEASE PROVIDE A LIFE SAFET PLAN INDICATING EXIT | | | ROUTES WITH TABLES AND CHAIRS. 106.3.5(6). | | | | | | 6) PROVIDE A PLAN WITH ACCESSIBLE SEATING. 11-5.1 | | | GENERAL. EXCEPT AS SPECIFIED OR MODIFIED IN THIS | | | SECTION, RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH | | | THE REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35. | | | WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS | | | CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT | | | LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED | | | TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE | | | ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS | | | REQUIRED IN SECTION 11-4.1.3(18). | | | | | | 7) PLANS FAIL TO IDENTY ANY FLOOR, WALL OR CEILING | | | FINISHES, PLEASE PROVIDE IN COMPLIANCE WITH 803.1 | | | GENERAL. INTERIOR WALL AND CEILING FINISHES SHALL BE | | | CLASSIFIED IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR | | | FINISH MATERIALS SHALL BE GROUPED IN THE FOLLOWING | | | CLASSES IN ACCORDANCE WITH THEIR FLAME SPREAD AND | | | SMOKE-DEVELOPED INDEXES. | | | | | | CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED 0-450. | | | | | | CLASS B: FLAME SPREAD 26-75; SMOKE-DEVELOPED 0-450. | | | | | | CLASS C: FLAME SPREAD 76-200; SMOKE-DEVELOPED 0-450. | | | | | | EXCEPTION: MATERIALS, OTHER THAN TEXTILES, TESTED IN | | | ACCORDANCE WITH SECTION 803.2. | | | | | | 8) PLANS INDICATE WITHIN TITLEBLOCK DOUG MCINTEE DESIGN | | | GROUP IS INVOLVED WITH THIS PROJECT, BEING COMMERCIAL | | | THE DESIGN GROUP CAN NOT WORK IN THE COMMERCIAL MARKET. | | | FL | | | S S 481.229(6)(A). | | | | | | 9) PLEASE PROVIDE WHO IS THE ARCHITECT OF RECORD, PLANS | | | HAVE A RAISED SEAL OF THE CORPORATE SEAL NOT THE | | | DESIGNER OF RECORD. | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE | | | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.FL ADMIN | | | CODE 61G16.003 ARCHITECTS | | | 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A | | | REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH | | | MUST: | | | - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER | | | - STATE THE FIRM LICENSE NUMBER | | | - STATE PROJECT NAME OR IDENTIFICATION | | | - STATE DATE PREPARED | | | - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED | | | INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE | | | PLANS | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B1 |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
N |
Date |
2009-10-14 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-10-14 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-10-14 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2009-10-14 16:41:23 | SEE APPROVAL ON 10/1/09 |
|
|
| Review Stop |
B1 |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-08-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-08-11 |
Time |
08:41 |
Rev Time |
0.66 |
| Received By |
jwitmer |
Date |
2009-08-11 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2009-08-11 08:46:52 | BUILDING PLAN REVIEW | | | PERMIT: 09030356 | | | ADD: 2730 S DIXIE HWY | | | CONT: RUSSELL W CLARK, LLC | | | TEL: (561)306-3634 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | AUGUST 11/2009 | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 2) 2ND REQUEST, PLANS SUBMITTED FOR PERMIT (FIRST TIME | | | REVIEW) AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE | | | 2007 FBC BUILDING WITH 2009, 2007 EXISTING BUILDING | | | CODEW/ 2009 SUPPLEMENTS. PLEASE INDICATE TO WHAT LEVEL | | | OF ALTERATION IS TO TAKE PLACE OR HAS TAKEN PLACE UNDER | | | THIS PERMIT. 401.4 A DESIGN PROFESSIONAL OR AN OWNER | | | MUST ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION | | | PURSUANT TO SECTIONS 403, 404 AND 405 OF THIS CODE.2007 | | | EXISTING BUILDING CODE W/ 2009 SUPPLEMENETS | | | | | | 3) 2ND REQUEST,THE FEE OF $500.00 IS LOW FOR THE SCOPE | | | OF WORK LISTED ON THE PERMIT APPLICATION, THE | | | EVALUATION IS MORE IN THE NEIGHBORHOOD OF $7,000.00. | | | THE PRE-INSPECT INDICATED WORK HAS ALREADY STARTED, | | | PLEASE INDICATE THE SCOPE OF WORK TO BE REVIEWED UNDER | | | THIS PERMIT. DEPENDING ON THE SCOPE OF WORK THE DOLLAR | | | AMOUNT LISTED ON THE PERMIT APPLICATION WILL CHANGE. W | | | P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. | | | ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, | | | AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, | | | A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN | | | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE | | | APPLICABLE GOVERNING AUTHORITY. | | | | | | 108.3* BUILDING PERMIT VALUATION. | | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE | | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | 4) 2ND REQUEST, PLEASE PROVIDE THE FOLLOWING | | | INFORMATION TO DETERMINE THE MINIMUM BASE BUILDING | | | REQUIREMENTS (TABLE 503/ 601. 110.2* W. P. B. | | | ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & | | | FOR CERTIFICATE OF OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | | DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503/ | | | CHAPTER 6, TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED | | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | | BUILDING PERMIT | | | .H ) NUMBER OF FLOORS/ OCCUPANCY SEPERATION? | | | I ) SQ. FT. FOOTPRINT | | | | | | 5) 2ND REQUEST, PLEASE PROVIDE A LIFE SAFET PLAN | | | INDICATING EXIT ROUTES WITH TABLES AND CHAIRS. | | | 106.3.5(6). | | | | | | 6) 2ND REQUEST, PROVIDE A PLAN WITH ACCESSIBLE SEATING. | | | 11-5.1 GENERAL. EXCEPT AS SPECIFIED OR MODIFIED IN THIS | | | SECTION, RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH | | | THE REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35. | | | WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS | | | CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT | | | LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED | | | TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE | | | ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS | | | REQUIRED IN SECTION 11-4.1.3(18). | | | | | | 7) 2ND REQUEST, PLANS FAIL TO IDENTY ANY FLOOR, WALL OR | | | CEILING FINISHES, PLEASE PROVIDE IN COMPLIANCE WITH | | | 803.1 GENERAL. INTERIOR WALL AND CEILING FINISHES SHALL | | | BE CLASSIFIED IN ACCORDANCE WITH ASTM E 84. SUCH | | | INTERIOR FINISH MATERIALS SHALL BE GROUPED IN THE | | | FOLLOWING CLASSES IN ACCORDANCE WITH THEIR FLAME SPREAD | | | AND SMOKE-DEVELOPED INDEXES. | | | | | | CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED 0-450. | | | | | | CLASS B: FLAME SPREAD 26-75; SMOKE-DEVELOPED 0-450. | | | | | | CLASS C: FLAME SPREAD 76-200; SMOKE-DEVELOPED 0-450. | | | | | | EXCEPTION: MATERIALS, OTHER THAN TEXTILES, TESTED IN | | | ACCORDANCE WITH SECTION 803.2. | | | | | | 8) COMPLIED. | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-08-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-08-24 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-08-24 |
Time |
12:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-05-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-05-08 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-05-08 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2009-05-08 10:02:27 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} SEE PLUMBING COMMENTS 1,2 AND 3 REGARDING SEALS AND | | | TITLE BLOCK. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-10-08 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-10-08 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-10-08 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2009-10-08 16:28:22 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED; PLAN SHEETS A1 AND A2 WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2009-08-18 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-08-18 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-08-18 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2009-08-18 12:11:52 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STAILL NEED TO BE ADDRESSED: | | | | | | 1. BASED ON PREVIOUS FIELD INSPECTIONS CONDUCTED BY | | | WEST PALM BEACH FIRE PREVENTION BUREAU, THE GENERAL | | | SEATING AREA SHOWN ON THE FLOOR PLAN, LOCATED AT THE | | | SOUTHWEST CORNER OF THE BUILDING - TO THE SOUTH OF THE | | | KITCHEN WAS ONCE A TAKE OUT FOOD ESTABLISHMENT. PLEASE | | | EXPLAIN IF/WHEN THIS CHANGE OF USE OCCURRED. | | | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 3. THE 2007 EDITION OF FLORIDA FIRE PREVENTION CODE | | | (BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION AND | | | NFPA 101, UNIFORM FIRE CODE, 2006 EDITION) SHALL BE | | | REFERENCED. | | | | | | 4. SHOW THE LOCATION OF THE EXIT LIGHTS AND EMERGENCY | | | LIGHTS FOR THIS FLOOR LAYOUT. HOW WILL THE SCOPE OF | | | ELECTRICAL WORK HAVE CAUSE FOR ANY OF THESE DEVICES TO | | | BE REMODELED AND/OR RECONFIGURED? | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-05-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-05-05 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-05-05 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2009-05-05 10:08:29 | *****DENIED***** | | | | | | 1. BASED ON PREVIOUS FIELD INSPECTIONS CONDUCTED BY | | | WEST PALM BEACH FIRE PREVENTION BUREAU, THE GENERAL | | | SEATING AREA SHOWN ON THE FLOOR PLAN, LOCATED AT THE | | | SOUTHWEST CORNER OF THE BUILDING - TO THE SOUTH OF THE | | | KITCHEN WAS ONCE A TAKE OUT FOOD ESTABLISHMENT. PLEASE | | | EXPLAIN IF/WHEN THIS CHANGE OF USE OCCURRED. | | | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 3. THE 2007 EDITION OF FLORIDA FIRE PREVENTION CODE | | | (BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION AND | | | NFPA 101, UNIFORM FIRE CODE, 2006 EDITION) SHALL BE | | | REFERENCED. | | | | | | 4. SHOW THE LOCATION OF THE EXIT LIGHTS AND EMERGENCY | | | LIGHTS FOR THIS FLOOR LAYOUT. HOW WILL THE SCOPE OF | | | ELECTRICAL WORK HAVE CAUSE FOR ANY OF THESE DEVICES TO | | | BE REMODELED AND/OR RECONFIGURED? | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-09-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-09-15 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-09-15 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2009-09-15 10:57:39 | SENT TO B-11. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-08-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-08-07 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-08-07 |
Time |
15:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2009-04-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-28 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2009-04-28 16:09:37 | TO B-9 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-09-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-09-17 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-09-17 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2009-09-17 10:21:19 | | | | | | | PASSED PROVISO: | | | | | | WATER HEATER SHALL HAVE ACCESS PER SECTION 501.4. | | | TOILET ROOM SHALL BE ACCESSIBLE AND COMPLY WITH | | | SECTIONS 11-4.16, 11-4.19 & 11-4.22 AS WELL AS FIGURES | | | 28, 29, 31 & 32. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2009-08-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-08-10 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-08-10 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2009-08-10 11:37:34 | DENIED | | | REFERENCE: | | | FBC-2007 PLUMBING | | | FBC-2007 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. THE TOILET ROOM WITH THE WALL MOVED, (SEE NOTE #2 | | | UNDER SCOPE OF WORK, WALL/CEILING NOTES), WILL REQUIRE | | | THE LAV TO BE MOVED AS 36" MINIMUM OPENING IS REQUIRED | | | FOR THE W/C. SEE FIGURE 28 IN CHAPTER 11. | | | | | | 2. SUBMIT A DETAIL FOR THE ACCESSIBLE TOILET ROOM | | | SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & | | | 11-4.22 WITH ALL SUBSECTIONS. SECTION 11-4.1.3(11). | | | | | | 3. INDICATE THE FOLLOWING ON THE PLANS: | | | A. CODE CYCLE | | | B. OCCUPANCY | | | | | | 4. THE FIRM LICENSE NUMBER IN THE TITLE BLOCK IS | | | INCORRECT. PER DBPR WEBSITE THE CORRECT FIRM LICENSE | | | NUMBER IS AA26001196. PLEASE CORRECT FIRM LICENSE | | | NUMBER IN TITLE BLOCK. FAC 61G1-16.004(2) & FS | | | 481.2055. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-05-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-05 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-05-05 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2009-05-05 13:24:18 | DENIED | | | REFERENCE: | | | FBC-2007 W/2009 SUPPLEMENTS | | | FBC-2007 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHT 1 OF 1 HAS A TITLE BLOCK WITH DOUG MCINTEE | | | DESIGN GROUP. PER FS 481.229(6)(A) THE DESIGN GROUP | | | SHALL NOT DO COMMERCIAL WORK. | | | | | | 2. SHT 1 OF 1 THE BUSINESS NUMBER, (CERTIFICATE OF | | | AUTHORIZATION), DOES NOT REFLECT THE NUMBER ON THE | | | STATE OF FLORIDA DBPR WEBSITE. SEE ATTACHED SHEET. FAC | | | 61G1-16.004(2) & FS 481.219. | | | | | | 3. SHT 1 OF 1 THE SEAL AFFIXED TO THE SHEET IS A | | | CORPORATE SEAL. THE SEAL REQUIRED TO BE AFFIXED TO THE | | | PLAN IS THE SEAL OF THE ARCHITECT OF RECORD. FAC | | | 61G1-002 & FS 481.2055. | | | | | | 4. SHT 1 OF 1 PLUMBING NOTES INDICATES A NEW WATER | | | HEATER. PER SECTION 501.4 THE WATER HEATER SHALL BE | | | LOCATED AND CONNECTED SO AS TO PROVIDE ACCESS FOR | | | OBSERVATION, MAINTENANCE, SERVICING & REPLACEMENT. ALSO | | | SEE SECTION 504.6, 504.7, 504.7.1 & 5094.7.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
N |
Date |
2009-08-26 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2009-08-26 |
Time |
09:21 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2009-08-26 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2009-08-26 09:23:17 | RENOVATION OF INTERIOR OF BUILDING HAS BEEN ESTIMATED | | | AT $7,000 BY THE STRUCTURAL REVIEWER. THIS IS WELL | | | BELOW 50% OF THE BUILDINGS VALUE, THEREFORE ZONING DOES | | | NOT NEED TO REVIEW THE INTERIOR RENOVATION PERMIT. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2009-08-11 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2009-08-11 |
Time |
18:38 |
Rev Time |
0.10 |
| Received By |
eschneid |
Date |
2009-08-11 |
Time |
18:38 |
Sent To |
|
|
| Notes |
| 2009-08-11 18:39:20 | FAILED - REPEAT COMMENTS | | | | | | 1) ACCORDING TO THE PALM BEACH COUNTY PROPERTY | | | APPRAISER, THE BUILDING IS WORTH $362,438, THUS IF THE | | | RENOVATIONS TO THE BUILDING EXCEED 50% OF THE VALUE OF | | | THE BUILDING, OR $181,219, THEN THE ENTIRE SITE SHALL | | | BE BROUGHT INTO CONFORMITY WITH THE PROVISIONS OF THE | | | LANDSCAPE CODE. | | | | | | 2) THE STRUCTURAL REVIEWER COMMENT #3 STILL INDICATES | | | THE VALUE OF WORK STATED ON THIS PERMIT IS LOW. IF THE | | | REVISED VALUE DOES NOT EXCEED $181,219 THEN THE ZONING | | | REVIEW WILL PASS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-05-08 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2009-05-08 |
Time |
13:41 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2009-05-08 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2009-05-08 13:55:38 | FAILED | | | | | | 1) ACCORDING TO THE PALM BEACH COUNTY PROPERTY | | | APPRAISER, THE BUILDING IS WORTH $362,438, THUS IF THE | | | RENOVATIONS TO THE BUILDING EXCEED 50% OF THE VALUE OF | | | THE BUILDING, OR $181,219, THEN THE ENTIRE SITE SHALL | | | BE BROUGHT INTO CONFORMITY WITH THE PROVISIONS OF THE | | | LANDSCAPE CODE. | | | | | | 2) THE STRUCTURAL REVIEWER COMMENT #3 INDICATES THE | | | VALUE OF WORK STATED ON THIS PERMIT IS LOW. IF THE | | | REVISED VALUE DOES NOT EXCEED $181,219 THEN THE ZONING | | | REVIEW WILL PASS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|
|