Plan Review Details - Permit 09030248
Plan Review Stops For Permit 09030248
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-02 Cont ID  
Sent By shill Date 2009-04-02 Time 14:19 Rev Time 0.00
Received By shill Date 2009-04-02 Time 14:19 Sent To  
Notes
2009-04-02 14:37:02****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. CONSTRUCTION DOCUMENTS ARE TO BE DIMENSIONED, TO
 SCALE, AND SHOW ALL STRUCTURAL DETAILS FBC*106.1.1. FOR
 INSTANCE, INCOMPLETE ANCHOR INFORMATION (NO LENGTH
 SPECIFIED FOR LAGS). FOR INSTANCE, ON ONE SHEET A 4X6
 IS NOTED, BUT DRAWN AS A SQUARE; ORIENTATION CANNOT BE
 DETERMINED. ANOTHER EXAMPLE IS THE CANTALEVER SHOWN ON
 ONE OF THE DETAILS; NO DIMENSION FOR CANTALEVER SHOWN.
 PLEASE PROVIDE STRUCTURAL DRAWINGS INCLUDING
 ELEVATIONS, FLOOR PLAN, AND A SECTION IF NECESSARY IN
 ORDER TO SHOW NATURE OF PROPOSED WORK. IF NECESSARY,
 PROVIDE DETAILS WITH DETAIL MARKERS WHICH CORRELATE
 WITH THE FLOOR PLAN.
  
 2. DECLARE GOVERNING CODE AND WIND DESIGN CRITERIA FBC
 R 301.
  
 3. PROVIDE ALL DIMENSIONS; DISTANCE BETWEEN POSTS,
 STRUCTURE HEIGHT, ETC. NOT PROVIDED.
  
 4. SEVERAL PAGES WERE SUBMITTED BUT NOTHING TO IDENTIFY
 THE SHEETS (SUCH AS PAGE NUMBERS OR LABELS). FOR
 INSTANCE, A SHEET WAS PROVIDED SHOWING A 4X4 DIAGONAL
 SUPPORT. THIS IS NOT SHOWN ON OTHER SHEETS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-19 Cont ID  
Sent By adarroug Date 2009-03-19 Time 08:24 Rev Time 0.00
Received By adarroug Date 2009-03-19 Time 08:24 Sent To B
Notes
2009-03-19 08:24:54TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-02 Cont ID  
Sent By shill Date 2009-04-02 Time 14:49 Rev Time 0.00
Received By shill Date 2009-03-12 Time 10:36 Sent To  
Notes
2009-03-12 10:36:45TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2009-03-18 Cont ID  
Sent By mcruz Date 2009-03-18 Time 19:21 Rev Time 0.00
Received By mcruz Date 2009-03-18 Time 19:15 Sent To I
Notes
2009-03-18 19:21:43PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. WHAT IS THE HEIGHT OF THE PROPOSED TRELLIS AND
 GATES? NOTE: PURSUANT TO THE CITY OF WEST PALM BEACH
 ZONING AND LAND DEVELOPMENT REGULATIONS, SECTION
 94-302(B)(1):
 MAXIMUM HEIGHT. IN RESIDENTIAL DISTRICTS, NO FENCE OR
 WALL SHALL EXCEED SIX FEET IN HEIGHT WITHIN REQUIRED
 SIDE AND REAR SETBACKS. FENCES OR WALLS SHALL NOT BE IN
 EXCESS OF 48 INCHES IN HEIGHT WITHIN THE REQUIRED FRONT
 SETBACK. HEDGES SHALL NOT EXCEED TEN FEET IN HEIGHT IN
 ANY REQUIRED SETBACK.
  
 PURSUANT TO THE ZLDR, SECTION 94-74: MINIMUM SETBACKS
 FOR PRINCIPAL BUILDING WITHIN THE SINGLE FAMILY HIGH
 DENSITY (SF14) RESIDENTIAL DISTRICT ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
  
 C. REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER IS
 LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  