| 2009-03-11 14:40:25 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2008 |
| | REVISIONS. |
| | |
| | 1- AS OF MARCH 1ST, 2009 THE NEW CODE IN EFFECT IS THE |
| | 2007 FLORIDA RESIDENTIAL CODE. PRODUCT APPROVAL FL6417 |
| | SUBMITTED IS FOR 2004 CODE VERSION. NEED TO PROVIDE |
| | PRODUCT APPROVAL FOR 2007 CODE VERSION. |
| | |
| | 2- REVISE INSTALLATION SCHEDULE SUBMITTED: |
| | A) ACCORDING TO PROPERTY APPRAISAL WEBSITE THIS HOUSE |
| | IS A CONCRETE BLOCK STRUCTURE, NOT WOOD FRAME. REVISE |
| | SUBSTRATE ON COLUMN #11 AS REQUIRED. |
| | |
| | B) REVISE EDGE DISTANCE ON COLUMN #8. COORDINATE WITH |
| | ITEM 2A ABOVE. |
| | **NOTE: COORDINATE SHUTTER SPAN ON COLUMN #6 AS |
| | REQUIRED TO GET MINIMUM EDGE DISTANCE REQUIRED. ALSO, |
| | TAKE INTO CONSIDERATION THAT EDGE DISTANCE EXCLUDES |
| | STUCCO THICKNESS. |
| | |
| | C) REVISE ANCHOR SPACING AS REQUIRED TO COORDINATE WITH |
| | ITEMS #2 A AND B ABOVE. |
| | ***NOTE: USE THE HOLLOW CONCRETE BLOCK TABLE FOR |
| | CONCRETE BLOCK AND STUCCO CONSTRUCTION NOT THE CONCRETE |
| | TABLE. |
| | |
| | D) REVISE INFORMATION ON TOP OF INSTALLATION SCHEDULE |
| | SUBMITTED. SEE COMMENTS. REVISE TYPE OF CONSTRUCTION OR |
| | ATTACHMENT SURFACE. THIS HOUSE IS MASONRY, NOT WOOD |
| | FRAME. ALSO, WRITE CORRECT PRODUCT APPROVAL NUMBER. |
| | INFORMATION SUBMITTED IS FOR THE CONTRACTOR LICENSE |
| | NUMBER. SEE COMMENTS ON INSTALLATION SCHEDULE. |
| | |
| | E) PROVIDE 2 COPIES OF INSTALLATION SCHEDULE. ONLY ONE |
| | SUBMITTED. |
| | |