| 2009-03-11 16:38:43 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 1- AS OF MARCH 1ST 2009 THE NEW 2007 FBC IS IN EFFECT. |
| | PRODUCT APPROVAL FL7279 SUBMITTED IS FOR 2004 CODE |
| | VERSION. NEED TO PROVIDE PRODUCT APPROVAL FOR 2007 CODE |
| | VERSION. |
| | |
| | 2- REVISE INSTALLATION SCHEDULE: |
| | A) ANCHOR SCHEDULE ON SHEETS 13 AND 14 OF SHUTTER |
| | DRAWINGS SUBMITTED ASSUMES 3-1/2" EDGE DISTANCE. EDGE |
| | DISTANCE SHOWN ON INSTALLATION SCHEDULE SUBMITTED |
| | SPECIFIES 3" EDGE DISTANCE. NEED TO REVISE ANCHOR |
| | SPACING AS REQUIRED BY TABLE ON SHEET 14 OF SHUTTERS |
| | DRAWINGS. |
| | |
| | B) SEE PRODUCT APPROVAL FOR SPECIFIC TYPE OF TAPCON TO |
| | BE USED AND SPECIFY EXACT SAME TYPE OF TAPCON AS |
| | REQUIRED TO MATCH PRODUCT APPROVAL. |
| | |
| | C) OPENING #1 CALLS FOR CONCRETE SUBSTRATE AT BOTTOM. |
| | PROVIDE PROOF THAT EXISTING CONCRETE HAS 3000 PSI |
| | STRENGTH AS REQUIRED BY NOTE #1 ON SHEET 14 OF SHUTTERS |
| | DRAWINGS SUBMITTED. |
| | |
| | D) COORDINATE SHUTTER SPAN IN COLUMN #6 WITH EDGE |
| | DISTANCE ON COLUMN #8 OF INSTALLATION SCHEDULE |
| | PROVIDED. |
| | |
| | E) REVISE INFORMATION ON TOP OF FORM. THIS IS A |
| | CONCRETE BLOCK HOUSE NOT CONCRETE. REVISE TYPE OF |
| | CONSTRUCTION ON TOP OF FORM. ALSO, REVISE NUMBER SHOWN |
| | ON PRODUCT COMPLIANCE REPORT. NUMBER SPECIFIED IS THE |
| | CONTRACTOR'S LICENSE NUMBER. NEED TO SPECIFY THE |
| | PRODUCT APPROVAL NUMBER. |
| | |
| | 3- SPECIFY HOW COMPLYING WITH THE EMERGENCY EGRESS |
| | REQUIREMENTS OF SEC. R310.4 OF 2007 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 4- PLEASE, IDENTIFY EACH OPENING ON THE KEY PLAN |
| | PROVIDED. |
| | |