| 2009-04-15 10:19:47 | RESIDENTIAL (R3) NEW SINGLE FAMILY RESIDENCE, BUILDING |
| | REVIEW CHECKLIST. |
| | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 1- SHEET 3: |
| | A) REVISE ROOF SHEATHING SPECIFICATIONS. NEED TO REVISE |
| | TYPE OF NAIL AND NAIL SPACING. NEED MIN. 8D RING SHANK |
| | NAILS AND NAIL SPACING TO BE MIN. 4"O.C. FOR ZONE 3. |
| | SEE SEC. R803.2.3.1 AND FIGURE R803.2.3.1 OF 2007 |
| | FLORIDA RESIDENTIAL CODE. NOTE THAT GABLE ENDS ARE ZONE |
| | 3 FOR THE FIRST 5'. REVISE AND IDENTIFY ROOF ZONES AS |
| | REQUIRED. |
| | |
| | B) GABLE END DETAIL NEEDS TO COMPLY WITH THE |
| | REQUIREMENTS OF SECTIONS R609.4 THRU R609.4.4 OF 2007 |
| | FLORIDA RESIDENTIAL CODE. SEE REFERENCED FIGURES AND |
| | REVISE AS REQUIRED. |
| | |
| | C) SPECIFY FIREBLOCKING MATERIAL AND LOCATION ON GABLE |
| | END DETAIL AS REQUIRED BY SEC. R602.1.2 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | D) SPECIFY 2 LAYERS OF VAPOR BARRIER WHEN APPLYING |
| | STUCCO AS REQUIRED BY SEC. R703.6.3 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. REVISE NOTE #2 AS REQUIRED. |
| | |
| | 2- SHEET 4: |
| | |
| | A) PROVIDE MANUFACTURER CUT SHEETS FOR WINDOW #4 IN |
| | MASTER BEDROOM TO VERIFY COMPLIANCE WITH MIN. SIZE |
| | REQUIRED BY SEC. R310 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | B) REVISE SIZE OF DOOR BUCK AS REQUIRED TO COMPLY WITH |
| | SEC. R613.6. SIZE OF BUCK NEED TO PROVIDE FULL SUPPORT |
| | TO THE DOOR FRAME. SEE SIZE OF DOOR FRAME ON PRODUCT |
| | APPROVAL AND REVISE AS REQUIRED. |
| | |
| | C) DESIGN PARAMETERS: SPECIFY ALL LOADS AS REQUIRED BY |
| | SEC. R301.1 AND TABLE R301.5 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. NEED TO SPECIFY THE ATTIC LIVE LOAD |
| | AS REQUIRED BY TABLE R301.5. |
| | |
| | D) UPDATE THE CODE EDITION SPECIFIED ON WIND LOADS. |
| | NEED TO SPECIFY 2007 FLORIDA RESIDENTIAL CODE, NOT |
| | 2004. |
| | |
| | E) COMPONENTS AND CLADDING WIND PRESSURES SHOWN ON WIND |
| | LOADS DON'T MATCH COMPONENTS AND CLADDING WIND |
| | PRESSURES SPECIFIED ON DOOR AND WINDOW SCHEDULE. REVISE |
| | AS REQUIRED. |
| | |
| | F) SPECIFY SAFETY GLASS ON FOR WINDOW #5 ON MASTER |
| | BATHROOM AS REQUIRED BY SEC. R308.4 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 3- SURVEY TO HAVE ORIGINAL SIGNATURE (NOT RUBBER STAMP) |
| | AS REQUIRED BY CHAPTER 472 FLORIDA STATUTE. |
| | |
| | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL SITE PREPARATION, LABOR |
| | AND MATERIALS, PROFESSIONAL FEES AS REQUIRED BY SEC. |
| | 108.3 CITY AMENDMENTS TO FBC. OWES $3066.98 FOR UPDATED |
| | VALUATION AND RADON FEES. |
| | |
| | 5- CLARIFY TYPE OF WINDOW TO BE USED IN MASTER |
| | BATHROOM. WINDOW SCHEDULE CALLS FOR SINGLE HUNG WINDOW, |
| | WHILE EXTERIOR ELEVATION SHOWS FIXED WINDOW. REVISE AS |
| | REQUIRED. IF USING FIXED WINDOW, THEN PROVIDE |
| | CORRESPONDING PRODUCT APPROVAL. |
| | |
| | 6- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ROOF SHINGLES. PRODUCT APPROVAL FL10674-R1 SUBMITTED |
| | IS MISSING THE DRAWINGS THAT WERE SUBMITTED TO GET THE |
| | PRODUCT APPROVAL. |
| | |
| | B) SINGLE HUNG/DOUBLE HUNG WINDOWS. PRODUCT APPROVAL |
| | FL5043 SUBMITTED IS FOR 2004 CODE VERSION. CURRENT CODE |
| | IN EFFECT IS THE 2007 CODE VERSION. |
| | ALSO, PROVIDE DRAWINGS THAT WERE SUBMITTED FOR APPROVAL |
| | ALONG WITH THE TECHNICAL INFORMATION SHOWING THE DESIGN |
| | PRESSURES FOR SELECTED WINDOWS TO VERIFY COMPLIANCE |
| | WITH ENGINEER'S CALCULATED DESIGN PRESSURES. |
| | |
| | C) EXTERIOR SWING DOORS. PRODUCT APPROVAL FL7551 |
| | SUBMITTED IS FOR 2004 CODE VERSION. NEED 2007 CODE |
| | VERSION. |
| | ALSO, PROVIDE INFORMATION SHOWING THE DESIGN PRESSURES |
| | FOR SELECTED DOORS. |
| | |
| | D) SLIDING GLASS DOORS. PRODUCT APPROVAL FL1824-R0 |
| | SUBMITTED IS FOR 2001 CODE VERSION. NEED TO PROVIDE |
| | 2007 CODE VERSION. |
| | ALSO, PROVIDE DRAWINGS SHOWING THE DESIGN PRESSURES FOR |
| | SELECTED DOORS. |
| | |
| | E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE SELECTED ANCHOR. THIS |
| | APPLIES TO STRUCTURAL CONNECTORS ONLY. COMPLETE PRODUCT |
| | APPROVAL REPORT IS REQUIRED FOR ALL OTHER PRODUCT |
| | APPROVALS. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 8- ENERGY CALCULATIONS: |
| | A) PAGE 1 OF 5 STATES THAT THIS IS NOT A WORST CASE |
| | SCENARIO. ORIENTATION OF WINDOWS SHOWN ON PAGE 3 OF 5 |
| | DOESN'T MATCH ORIENTATION OF BUILDING. SEE SURVEY AND |
| | REVISE AS REQUIRED. |
| | |
| | B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE BUILDER NAME AND PERMIT OFFICE. |
| | |
| | C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| | |
| | D) PROVIDE INFORMATION FOR WINDOWS SHOWING COMPLIANCE |
| | WITH THE U-FACTOR AND SHGC FACTOR SHOWN ON ITEM #7. |
| | NOTE: THIS IS REQUIRED WHEN CALCULATIONS ARE DONE USING |
| | SPECIFIC FACTORS AND NOT THE DEFAULT FACTOR OF THE |
| | PROGRAM USED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |
| | |
| | |