| Plan Review Stops For Permit 09030161 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-03-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-03-09 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-03-09 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2009-03-09 13:34:30 | 2007 FBC W/CITY AMENDMENT | | | RECOVER DECK (ROOF OVER) | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT PRODUCT APPROVALS FOR THE 2007 EDITION OF THE | | | FLORIDA BUILDING CODE WHICH WENT INTO EFFECT ON MARCH | | | 1, 2009. | | | | | | 2) AS THERE IS NO FLORIDA PRODUCT APPROVAL FOR THIS | | | SYSTEM LISTED FOR THE 2007 FBC ON THE STATE WEBSITE, | | | YOU CAN SUBMIT TWO COPIES OF MIAMI-DADE PRODUCT | | | APPROVALS FOR THE PRODUCT. (SEE NOA NO.05-1214.01) IF | | | MORE THAN ONE APPROVED SYSTEM IS LISTED IN THE NOA, | | | SPECIFY THE ONE YOU PLAN TO INSTALL. ALSO SPECIFY THE | | | FASTENING OPTION AND DESIGN PRESSURE THAT WILL BE USED. | | | | | | 3) IF ENHANCED FASTENING IS REQUIRED TO MEET UPLIFT | | | PRESSURES AT THE CORNER AND PERIMETER AREAS, SUBMIT RAS | | | 117 CALCULATIONS. SEE GENERAL LIMITATION NUMBER 7 ON | | | THE LAST PAGE OF THE NOA. | | | | | | 4) A PRE-INSPECTION OF THE EXISTING ROOF BY THE | | | BUILDING INSPECTOR TO VERIFY THE CONDITION OF THE | | | EXISTING ROOF COVER WILL BE REQUIRED BEFORE THE PERMIT | | | IS ISSUED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
|