| 2009-03-16 08:32:13 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | PLEASE SEE COMMENT FROM REVIEW OF MASTER PERMIT; |
| | 09010024, AND PREVIOUS ROOF PERMIT REVIEW: |
| | |
| | |
| | 5. CONTRACTOR MUST SELECT AN APPROVED ASSEMBLY AND |
| | SPECIFY ENHANCED FASTENING. |
| | |
| | CONTRACTOR SUBMITTED NOA 060613.06 FOR THE FLAT DECK |
| | WITH THE MASTER PERMIT AND HIGHLIGHTED THE ASSEMBLY ON |
| | PAGE 12 (INSULATED DECK). THIS ASSEMBLY HAS A DESIGN |
| | PRESSURE LIMITATION OF -60PSF. SEE GENERAL LIMITATION |
| | #7 ON THE NOA, CALCULATIONS FOR ENHANCED FASTENING FOR |
| | PERIMETER AND CORNER ZONES ARE TO BE CALCULATED BY AN |
| | ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT. |
| | |
| | DELEGATED ENGINEERING (ENHANCED FASTENING CALCULATIONS) |
| | ARE TO BE REVIEWED BY ENGINEER OF RECORD FAC61G15-31. |
| | |
| | 2ND ROOF PERMIT REVIEW, ENGINEERING SPECIFYING ROOF |
| | PRESSURES WAS SUBMITTED AS WELL AS ROOF SHEATHING |
| | NAILING PATTERN. THIS SHOULD HAVE BEEN INCLUDED ON THE |
| | MASTER PERMIT; THIS DOES NOT ADDRESS THE COMMENT. |
| | CALCULATIONS IN ACCORDANCE WITH RAS117 FOR THE |
| | INSULATION BOARD IS REQUIRED. ZONES 2 AND 3 HAVE A |
| | DESIGN PRESSURE OF -79.2, BUT THE ASSEMBLY SELETED HAS |
| | A DESIGN PRESSURE LIMITATION OF -60PSF. ENHANCED |
| | FASTENING IN ACCORDANCE WITH RAS117 REQUIRED FOR THIS |
| | ASSEMBLY (-60PSF) TO MEET THE DESIGN PRESSURE (-79.2). |
| | |
| | SEE PAGE 20 OF THE NOA, ITEM 7: |
| | |
| | PERMIETER AND CORNER AREAS SHALL COMPLY WITH THE |
| | ENHANCED UPLIFT PRESSURE REQUIREMENTS OF THESE AREAS. |
| | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| | INSULATION AND BASE SHEET AS CALCULATED IN COMPLIANCE |
| | WITH ROOFING APPLICATION STANDARD RAS 117. CALCULATIONS |
| | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, OR |
| | REGISTERED ROOF CONSLUTANT. |
| | |
| | THE ENGINEERING SUBMITTED IS ENTITLED "ROOF AND WALL |
| | NAILING SCHEDULE." THIS IS ROOF SHEATHING NAILING |
| | SCHEDULE, NOT THE ROOF ASSEMBLY NAILING SCHEDULE. THIS |
| | APPLIES TO THE PLYWOOD INSTALLATION, NOT THE ROOF |
| | ASSEMBLY (TAMKO BUR ROOFING SYSTEM) INSTALLATION. |
| | |
| | |
| | |