Plan Review Details - Permit 09030017
Plan Review Stops For Permit 09030017
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-11-10 Cont ID  
Sent By shill Date 2009-11-10 Time 15:51 Rev Time 0.00
Received By shill Date 2009-11-10 Time 15:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-09-30 Cont ID  
Sent By shill Date 2009-09-30 Time 18:22 Rev Time 0.00
Received By shill Date 2009-09-30 Time 18:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-08-06 Cont ID  
Sent By shill Date 2009-08-06 Time 08:41 Rev Time 0.00
Received By shill Date 2009-08-06 Time 08:41 Sent To  
Notes
2009-08-06 08:54:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 3. PROVIDE A DETAIL FOR THE CONCRETE SLAB, FBC1603.1.
  
 THE DETAIL IS LABELED "NEW PAD FOR TRANSFER PANEL." TWO
 CONCRETE PADS ARE SHOWN ON THE SITE PLAN. I WAS UNABLE
 TO LOCATE A DETAIL FOR THE GENERATOR PAD. THE DETAIL
 PROVIDED IS NOT CLEAR; NO MINIMUM THICKNESS SHOWN. HOW
 WILL THE CONDUIT AFFECT STRUCTURAL INTEGRITY?
 FBC1604.1, PLEASE DEMONSTRATE THAT THE EQUIPMENT WILL
 RESIST OVERTURNING/SLIDING.
  
 4. DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 NOT ADDRESSED. PLEASE NOTE THAT, BASED ON AERIALS, THIS
 APPEARS TO BE EXPOSURE C (NOTE THAT DEFINITION HAS
 CHANGED EFFECTIVE MARCH 1, 2009). FBC1609, ASCE7-05.
  
 5. SPECIFY ANCHORING TO SLAB; PROVIDE LENGTH, DIAMETER,
 AND TYPE OF ANCHOR PROPOSED.
  
 NO LENGTH WAS SPECIFIED. MANUFACTURER HAS A DIAMETER
 AND TOTAL NUMBER RECOMMENDATION ONLY. HAS THE
 MANUFACTURER TAKEN INTO ACCOUNT THE WIND DESIGN
 CRITERIA FOR OUR AREA?
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-03 Cont ID  
Sent By shill Date 2009-04-03 Time 13:42 Rev Time 0.00
Received By shill Date 2009-04-03 Time 13:40 Sent To  
Notes
2009-04-03 13:58:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. TWO IDENTICAL COLLATED SETS OF PERMIT DOCUMENTS
 REQUIRED, FBC*109. PLEASE BIND DOCUMENTS TOGETHER TO
 PREVENT THEM FROM GETTING SEPARATED.
  
 2. SEE ZONING COMMENTS REGARDING ACCESSIBLE PARKING
 SPACE, FBC 11.
  
 3. PROVIDE A DETAIL FOR THE CONCRETE SLAB, FBC1603.1.
  
 4. DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 5. SPECIFY ANCHORING TO SLAB; PROVIDE LENGTH, DIAMETER,
 AND TYPE OF ANCHOR PROPOSED.
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-11-16 Cont ID  
Sent By dpalmer Date 2009-11-09 Time 07:58 Rev Time 0.00
Received By dpalmer Date 2009-11-09 Time 07:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-11-12 Cont ID  
Sent By shill Date 2009-11-12 Time 13:46 Rev Time 0.00
Received By shill Date 2009-11-12 Time 13:46 Sent To  
Notes
2009-11-12 13:46:48PER DP
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-09-15 Cont ID  
Sent By dpalmer Date 2009-09-15 Time 16:52 Rev Time 0.00
Received By dpalmer Date 2009-09-14 Time 14:47 Sent To  
Notes
2009-09-15 16:52:38 
 ** TEMPORARY DENIED PLANS **
  
  
 1) NOTE: DUE TO ZONING COMMENTS, ELECTRICAL REVIEW IS
 ON HOLD PENDING ANY CORRECTIONS ON SHEETS.
  
 CALLED AND SPOKE TO CARL WATSON.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2009-09-14 14:47:41ELECTRICAL REVIEW ON HOLD.
 CALLED AND SPOKE TO CARL WATSON, HE WILL CALL BACK ONCE
 IN OFFICE ON 9/15.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-07-24 Cont ID  
Sent By dpalmer Date 2009-07-24 Time 13:06 Rev Time 0.00
Received By dpalmer Date 2009-07-24 Time 13:06 Sent To  
Notes
2009-07-24 13:06:34 
 ** DENIED REVIEW. **
  
 1) NOTE: SITE PLANS DO NOT SHOW DIMENSIONS, DISTANCES
 LOCATIONS OF ALL EQUIPMENT ETC AS PREVIOUSLY NOTED.
 110.26 ETC
  
 2) NOTE: THE PLANS CONTAIN INSUFFICIENT DETAIL FOR
 SLABS FOR STRENGTH AND STABILITY SEE BUILDING REVIEW
 NOTES ALSO.
 IN THE SETS OF PLANS SUBMITTED SLAB IS SHOWN AS 4INCHES
 OR WHAT APPEARS TO BE 4INCHES ON SOME LOCATIONS AND
 8INCHES ON OTHER LOCATIONS SUCH AS THE ELECTRICAL
 RISER.
 THE CONDUITS ON TRANSFER PANEL SLAB SHOWS 8-3INCH
 CONDUITS WHERE RISER INDICATES 3-4INCH CONDUITS.
  
 STEEL LAYOUT AROUND CONDUITS WITH SLAB DOES NOT PROVIDE
 STRENGTH AND STABILITY AS SHOWN. SEE TECHNICAL BUILDING
 REVIEW NOTES.
  
 COORDINATION BETWEEN SLAB INFORMATION AND OTHER DETAILS
 IS NEEDED.
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-02 Cont ID  
Sent By dpalmer Date 2009-04-02 Time 09:25 Rev Time 0.00
Received By dpalmer Date 2009-04-02 Time 09:25 Sent To  
Notes
2009-04-02 09:25:26** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT SITE ELECTRICAL PLANS WHICH ARE
 DETAILED SHOWING THE LOCATION WITH ALL DIMENSIONS. THIS
 INCLUDES EXACT DISTANCES FROM ALL SURROUNDING WALLS
 ETC.
 PLEASE KNOW AT THIS TIME BASED ON ZONING COMMENTS THERE
 MAY BE A NEED FOR OTHER COMMENTS ONCE WALLS OR
 SCREENING IS INSTALLED. PLEASE SEE OTHER COMMENTS BELOW
 WITH RESPECT TO DISCONNECTING MEANS.
 110.26.
  
 2) NOTE: PLEASE PLACE ALL PLANS, SITE PLANS, AND
 SPECIFICATIONS INTO TWO NEAT SETS FOR REVIEW. ALL PLANS
 AND SHEETS ARE LOOSE PLEASE ATTACH SHEETS INTO SETS.
  
 3) NOTE: THE RISER SHOWING EXISTING CONDITIONS
 INDICATES AN EQUIPMENT GROUNDING CONDUCTOR FROM FPL TO
 THE FIRST MEANS OF DISCONNECT.
 THE REVISED PROPOSED RISER DOES NOT INDICATE ANY
 CONDUCTORS FOR THE LINE SIDE OF MAIN.
 250.6,250.24
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW PROPOSED SE RATED ATS. AS NO
 INFORMATION WAS SUBMITTED IT IS NOT POSSIBLE TO REVIEW.
 PLEASE BE SURE TO SEE 230.76, 230.79, 230.70,71 AND
 110.9 FOR EQUIPMENT REQUIREMENTS.
  
 5) NOTE: PLEASE BE SURE TO SEE COMMENTS FROM ALL OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL PLANS.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-10-01 Cont ID  
Sent By mawillia Date 2009-09-22 Time 13:50 Rev Time 0.00
Received By MAWILLIA Date 2009-10-01 Time 14:49 Sent To  
Notes
2009-09-22 13:50:00*****APPROVED*****
  
 THE COMMENTS TAKEN FROM THE PREVIOUS FIRE PLAN REVIEW
 HAVE BEEN ADDRESSED; THE GENERATOR SITE PLAN DRAWING
 WAS STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-08-05 Cont ID  
Sent By mawillia Date 2009-08-05 Time 12:32 Rev Time 0.00
Received By mawillia Date 2009-08-05 Time 11:34 Sent To  
Notes
2009-08-05 12:32:50*****DENIED*****
  
 THE FOLLOWING COMMENTS (OF FOUR) TAKEN FROM THE
 PREVIOUS FIRE PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 1. WORK TO COMPLY WITH NFPA 101, 2006 AND THE
 REQUIREMENTS OF NFPA 110, STANDARD FOR EMERGENCY AND
 STANDBY POWER SYSTEMS, 2005 EDITION.
  
 2. EQUIPMENT MAY REQUIRE MEANS OF PROTECTION AGAINST
 THE POSSIBILITY OF MECHANICAL DAMAGE
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUIDE A
 RESPONSE LETTER INDICATING HOW/WHERE THE ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-03 Cont ID  
Sent By mwennerg Date 2009-04-03 Time 11:17 Rev Time 0.00
Received By mwennerg Date 2009-04-03 Time 11:17 Sent To  
Notes
2009-04-03 13:09:55***DENIED***
  
 1) WORK TO COMPLY WITH NFPA 101, 2006 AND THE
 REQUIREMENTS OF NFPA 110, STANDARD FOR EMERGENCY AND
 STANDBY POWER SSTEMS.
  
 2) EQUIPMENT MAY REQUIRE MEANS OF PROTECTION AGAINST
 THE POSSIBILITY OF MECHANICAL DAMAGE.
  
 3) PLEASE BIND TOGETHER AND ARRANGE PLANS AND
 SUPPORTING DOCUMENTS IN A NEAT AND ORDERLY MANNER.
  
 4) WHAT FIRE PROTECTION AND LIFE SAFETY EQUIPMENT WILL
 BE TIED INTO THE GENERATOR?
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2009-07-13 Cont ID  
Sent By kstevens Date 2009-07-13 Time 12:57 Rev Time 0.00
Received By kstevens Date 2009-07-13 Time 12:57 Sent To  
Notes
2009-07-13 12:58:02SEPARATE GAS PERMIT/PLANS HAVE BEEN SUBMITTED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-04-17 Cont ID  
Sent By kstevens Date 2009-04-17 Time 09:26 Rev Time 0.00
Received By kstevens Date 2009-04-17 Time 09:25 Sent To  
Notes
2009-04-17 09:33:03DENIED
 REFERENCE:
 FBC-2007 CHAPTER 1
  
 1. CONSTRUCTION DOCUMENTS AND OTHER DATA SHALL BE
 SUBMITTED IN TWO OR MORE SETS WITH EACH APPLICATION FOR
 PERMIT. SECTION 106.1. LOOSE SHEETS SHALL BE BOUND INTO
 SETS.
  
 2. SECTION 106.1.2 MORE INFORMATION IS REQUIRED. PLEASE
 SUBMIT THE INSTALLATION INSTRUCTIONS SHOWING THE
 REQUIRED CLEARANCES FROM ALL STRUCTURES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-10-26 Cont ID  
Sent By lmartine Date 2009-10-20 Time 10:09 Rev Time 0.00
Received By lmartine Date 2009-10-20 Time 10:09 Sent To  
Notes
2009-10-26 10:10:35IN ZONING
2009-10-26 10:10:18PLANS ROUTED ON 10/26/09

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-27 Cont ID  
Sent By lmartine Date 2009-08-27 Time 11:08 Rev Time 0.00
Received By lmartine Date 2009-08-27 Time 11:08 Sent To  
Notes
2009-08-27 11:12:20C-15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-06-24 Cont ID  
Sent By shill Date 2009-06-24 Time 15:00 Rev Time 0.00
Received By shill Date 2009-06-24 Time 15:00 Sent To  
Notes
2009-06-24 15:00:49C22
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-17 Cont ID  
Sent By kstevens Date 2009-04-17 Time 09:33 Rev Time 0.00
Received By kstevens Date 2009-03-04 Time 09:18 Sent To  
Notes
2009-03-04 09:23:04TO "COMM" BD#47

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-03-30 Cont ID  
Sent By rregueir Date 2009-03-30 Time 14:48 Rev Time 0.00
Received By rregueir Date 2009-03-30 Time 14:48 Sent To  
Notes
2009-03-30 14:48:41SPECS INDICATE A GAS GENERATOR. NO MECH REVIEW
 REQUIRED.

Review Stop Z ZONING
Rev No 4 Status P Date 2009-10-29 Cont ID  
Sent By eschneid Date 2009-10-29 Time 15:46 Rev Time 0.50
Received By eschneid Date 2009-10-29 Time 15:46 Sent To E
Notes
2009-10-29 15:52:28PASSED
  
 1) THE FENCE AND LANDSCAPE SHOWN ON PERMIT NO. 09050324
 SHALL BE INSTALLED PRIOR TO THE GENERATOR
 FINAL/CERTIFICATE OF COMPLETION.

Review Stop Z ZONING
Rev No 3 Status F Date 2009-09-02 Cont ID  
Sent By eschneid Date 2009-09-02 Time 10:01 Rev Time 0.50
Received By eschneid Date 2009-09-02 Time 10:01 Sent To  
Notes
2009-09-02 10:19:03FAILED
  
 1) REPEAT COMMENT - THE PLANS SHALL SHOW THE GENERATOR
 AND ALL DIMENSIONS AND SETBACKS TO SCALE FROM THE
 ADJACENT PROPERTY LINE, THE WALL, THE LANDSCAPE AND THE
 PARKING AREA. THE EXISTING AND NEW LAYOUT PLANS SHOW
 DIFFERENT DIMENSIONS THAN THE BOB BELL SITE PLAN AND
 THE ELEVATION PLAN. THERE IS A TWO (2) FOOT
 DISCREPANCY.
  
 2) REPEAT COMMENT - THE SITE PLAN SHOWS 12 FEET FROM
 THE WALL TO THE HANDICAP PARKING SPACE. THE LAYOUT
 DRAWINGS SHOW 10 FEET FROM THE WALL TO THE HANDICAP
 PARKING SPACE. ALL PLANS AND DRAWINGS NEED TO SHOW SAME
 AND ACCURATE DIMENSIONAL CONDITIONS.
  
 3) REPEAT COMMENT - SHOW THE SCREEN HEDGE ON THE
 SUBMITTED PLANS.
  
 4) THE NEW WALL TO THE EAST OF THE GENERATOR IS
 REQUIRED TO BE ON THE WEST SIDE OF THE EXISTING PALM
 LANDSCAPE ISLAND. THE MATERIAL OF THE NEW WALL SHALL
 COMPLY WITH ANY COMBUSTIBILITY RATINGS FOR THE REQUIRED
 LOCATION.
  
 5) NOTE - THE GENERATOR PERMIT WILL NOT BE APPROVED
 UNTIL THE WALL/FENCE AND HEDGE PERMIT IS APPROVED.
 FENCE PERMIT NO. 09050324 DID NOT PASS ON INITIAL
 REVIEW. PLEASE INCLUDE THE FENCE RESUBMITTAL WITH THIS
 PERMIT.
  
 6) THE GENERATOR WILL NOT RECEIVE A CERTIFICATE OF
 COMPLETION UNTIL THE WALL/FENCE AND HEDGE ARE
 INSTALLED.
  
 7) NOTE - THE EXISTING LANDSCAPE TO THE EAST OF THE
 PROPOSED GENERATOR SHALL NOT BE REMOVED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 2 Status F Date 2009-06-29 Cont ID  
Sent By eschneid Date 2009-06-29 Time 16:20 Rev Time 0.50
Received By eschneid Date 2009-06-29 Time 16:20 Sent To  
Notes
2009-06-29 16:26:09FAILED
  
 1) REPEAT COMMENT - THE PLANS SHALL SHOW THE GENERATOR
 AND ALL DIMENSIONS AND SETBACKS TO SCALE FROM THE
 ADJACENT PROPERTY LINE, THE WALL, THE LANDSCAPE AND THE
 PARKING AREA.
  
 2) THE SITE PLAN SHOWS 12 FEET FROM THE WALL TO THE
 HANDICAP PARKING SPACE. THE NOT TO SCALE GENERATOR
 DRAWING LISTS 13 FEET FROM THE WALL TO THE HANDICAP
 PARKING SPACE. ALL PLANS AND DRAWINGS NEED TO SHOW SAME
 AND ACCURATE DIMENSIONAL CONDITIONS.
  
 3) SHOW THE PROPOSED WALL AND SCREEN HEDGE ON THE
 SUBMITTED PLANS.
  
 4) NOTE - THE GENERATOR PERMIT WILL NOT BE APPROVED
 UNTIL THE WALL/FENCE AND HEDGE PERMIT IS APPROVED. THE
 GENERATOR WILL NOT RECEIVE A CERTIFICATE OF COMPLETION
 UNTIL THE WALL/FENCE AND HEDGE ARE INSTALLED.
  
 5) NOTE - THE EXISTING LANDSCAPE TO THE EAST OF THE
 PROPOSED GENERATOR SHALL NOT BE REMOVED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-03-25 Cont ID  
Sent By eschneid Date 2009-03-25 Time 18:18 Rev Time 1.00
Received By eschneid Date 2009-03-25 Time 18:18 Sent To  
Notes
2009-03-25 18:24:36FAILED
  
 1) THE PLANS SHALL SHOW THE GENERATOR TO SCALE AND
 INCLUDE DIMENSIONS AND SETBACKS FROM THE ADJACENT
 PROPERTY LINE, THE WALL, THE LANDSCAPE AND THE PARKING
 AREA.
  
 2) THE PROPOSED GENERATOR LOCATION IS ADJACENT TO A
 HANDICAP PARKING SPACE. PROVIDE DIMENSIONS TO VERIFY
 THAT THE ACCESSIBLE ROUTE TO THE BUILDING IS BEING
 MAINTAINED.
  
 3) GENERATORS ARE REQUIRED TO BE SCREENED WITH AN
 OPAQUE WALL OR FENCE AND LANDSCAPE HEDGE. A SEPARATE
 PERMIT APPLICATION SHALL BE SUBMITTED FOR THE
 WALL/FENCE AND HEDGE.
  
 4) THE GENERATOR PERMIT WILL NOT BE APPROVED UNTIL THE
 WALL/FENCE AND HEDGE PERMIT IS APPROVED. THE GENERATOR
 WILL NOT RECEIVE A CERTIFICATE OF COMPLETION UNTIL THE
 WALL/FENCE AND HEDGE ARE INSTALLED.
  
 5) THE EXISTING LANDSCAPE TO THE EAST OF THE PROPOSED
 GENERATOR SHALL NOT BE REMOVED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.