Plan Review Details - Permit 09020635
Plan Review Stops For Permit 09020635
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-08-31 Cont ID  
Sent By jwitmer Date 2009-08-31 Time 08:00 Rev Time 1.00
Received By jwitmer Date 2009-08-31 Time 07:07 Sent To  
Notes
2009-08-31 08:03:35REVISIONS:
 F001
 F101

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-08-27 Cont ID  
Sent By jwitmer Date 2009-08-27 Time 12:59 Rev Time 0.50
Received By jwitmer Date 2009-08-27 Time 12:30 Sent To  
Notes
2009-08-27 12:57:05REV# 6
 T.100
 G.110
 G.111

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-24 Cont ID  
Sent By jwitmer Date 2009-07-24 Time 17:30 Rev Time 1.00
Received By jwitmer Date 2009-07-24 Time 12:30 Sent To  
Notes
2009-07-24 17:22:16REVISION# 4:
 T.100
 G.110
 G.111
 D.110
 A0.10
 A.110
 A.111
 A.410
 A.601
 A.602

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-03-19 Cont ID  
Sent By jwitmer Date 2009-03-19 Time 12:24 Rev Time 1.85
Received By jwitmer Date 2009-03-19 Time 07:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-09-07 Cont ID  
Sent By dpalmer Date 2009-09-07 Time 11:09 Rev Time 0.00
Received By dpalmer Date 2009-09-07 Time 11:09 Sent To  
Notes
2009-09-07 11:09:45ELEC OK, STAMPED AND FILED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-07-24 Cont ID  
Sent By dpalmer Date 2009-07-24 Time 19:49 Rev Time 0.00
Received By dpalmer Date 2009-07-24 Time 19:49 Sent To FIRE
Notes
2009-07-24 19:49:28* DENIED REVISION **
  
 1) NOTE: FAMILY ROOM ON ORIGINAL PLANS AND REVISIONS
 INDICATING 2.1 INCLUDES THE DECRETIVE ALLOWANCES UNDER
 THE 2004 FBC. ONLY IF THIS PROJECT WAS UNDER THE 2007
 FBC WOULD THE LIGHTING ALLOWANCE BE EXCEEDED.
  
 2) NOTE: THE PREVIOUS PLANS INDICATED ROOM #241 AS
 FAMILY ROOM WITH OTHER ITEMS SUCH AS ADDITIONAL
 SWITCHES AND ADDITIONAL FIXTURES. THE ROOM 241 WAS
 REVISED FROM PLANS ON FILE HOWEVER NO REVISION HAS BEEN
 INDICATED AT THIS LOCATION. SWITCHES, FIXTURES ETC HAVE
 BEEN REMOVED.
 OTHER LOCATIONS WOULD BE HALLWAY 242 ALSO IN WHICH
 FIXTURES HAVE BEEN REMOVED HOWEVER THERE IS NOT
 INDICATION ON PLANS OF ANY REVISION.
  
 3) NOTE: PLEASE PROVIDE SPECIFIC LIGHTING FIXTURE
 INFORMATION. PLEASE REVISE CALCULATIONS AS NEEDED.
 13-415.2.ABC.1.1,.1.2.
 PROJECT IS UNDER THE 2004 FBC WITH 2007 REVISIONS.
 DETERMINATION OF LIGHTING ALLOWANCES MEETING CODE CAN
 NOT BE MADE WITHOUT FIXTURE INFORMATION.
  
 4) NOTE: PLEASE SUBMIT REVISED CIRCUITING ON REVISED
 PANEL SCHEDULES. 408.4, 220, 240.4, 310.16.
 FBC 106.3.5.1.2
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-03-19 Cont ID  
Sent By dpalmer Date 2009-03-19 Time 12:29 Rev Time 0.00
Received By dpalmer Date 2009-03-19 Time 12:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-09-02 Cont ID  
Sent By mawillia Date 2009-09-02 Time 14:40 Rev Time 0.00
Received By mawillia Date 2009-09-02 Time 13:44 Sent To  
Notes
2009-09-02 13:48:31*****REVISIONS, DATED 5/28/09 AND 8/21/09,
 APPROVED*****
  
  
 REVISED PLAN SHEETS E201 & E301, AND F101 WERE STAMPED,
 INITIALED, AND DATED. ALTHOUGH SUBMITTED AS PART OF THE
 REVISED PLAN SHEETS, SHEET F001 CONTAINED NO REVISIONS
 (THEREFORE NOT FIRE-STAMPED).

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-07-27 Cont ID  
Sent By mawillia Date 2009-07-27 Time 14:19 Rev Time 0.00
Received By mawillia Date 2009-07-27 Time 13:41 Sent To  
Notes
2009-07-27 13:59:45*****REVISION, DATED 5/28/09, PARTIAL APPROVAL*****
  
  
 REVISED PLAN SHEETS G.110, G.111, D.110, AND A.010 WERE
 STAMPED, INITIALED, AND DATED; HOWEVER SHEETS AND E201
 & E301 ARE TO BE FIRE-STAMPED WHEN THE ELECTRICAL
 COMMENT(S) HAVE BEEN ADDRESSED .

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-03-25 Cont ID  
Sent By mawillia Date 2009-03-25 Time 12:26 Rev Time 0.00
Received By mawillia Date 2009-03-25 Time 11:31 Sent To M
Notes
2009-03-25 12:26:44*****APPROVED*****
  
  
 PLAN SHEETS G.110 THRU G.113, D.110, A.010, E201, E301,
 F001 AND F101 WERE STAMPED, INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-27 Cont ID  
Sent By lmartine Date 2009-08-27 Time 08:46 Rev Time 0.00
Received By lmartine Date 2009-08-27 Time 08:46 Sent To  
Notes
2009-08-27 08:47:31****EXPEDITED****** GAVE TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-26 Cont ID  
Sent By lmartine Date 2009-08-26 Time 13:35 Rev Time 0.00
Received By lmartine Date 2009-08-26 Time 13:35 Sent To  
Notes
2009-08-26 13:52:46B-22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-25 Cont ID  
Sent By kstevens Date 2009-03-25 Time 18:28 Rev Time 0.00
Received By kstevens Date 2009-03-03 Time 11:01 Sent To  
Notes
2009-03-03 11:06:33TO "COMM" BD#34

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-09-02 Cont ID  
Sent By rregueir Date 2009-09-02 Time 17:39 Rev Time 0.00
Received By rregueir Date 2009-09-02 Time 17:38 Sent To  
Notes
2009-09-02 17:39:51REVISED M001, M101, M201, M401 DELTA 5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-08-15 Cont ID  
Sent By rregueir Date 2009-08-15 Time 15:24 Rev Time 0.00
Received By rregueir Date 2009-08-15 Time 15:24 Sent To PC
Notes
2009-08-15 15:25:06REVISED M201 DELTA 5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-03-24 Cont ID  
Sent By rregueir Date 2009-03-24 Time 19:03 Rev Time 0.00
Received By rregueir Date 2009-03-24 Time 19:02 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2009-09-09 Cont ID  
Sent By kstevens Date 2009-09-09 Time 15:13 Rev Time 0.00
Received By kstevens Date 2009-09-09 Time 15:13 Sent To  
Notes
2009-09-09 15:13:51REVISION OK -- SHT P101 MED GAS OK.

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2009-03-25 Cont ID  
Sent By kstevens Date 2009-03-25 Time 18:01 Rev Time 0.00
Received By kstevens Date 2009-03-25 Time 18:00 Sent To  
Notes
2009-03-25 18:19:12 
  
  
 SEPARATE MED-GAS PERMIT REQUIRED. CERTIFICATIONS
 REQUIRED FOR THE QUALIFER, THE INSTALLER & THE BRAZER
 PER FAC 61G4-15.031 & FS 489.1136 SHALL BE SUBMITTED
 WITH THE APPLICATION FOR THE MED-GAS PERMIT.
  
  
  
  
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-09-09 Cont ID  
Sent By kstevens Date 2009-09-09 Time 15:12 Rev Time 0.00
Received By kstevens Date 2009-09-09 Time 15:12 Sent To  
Notes
2009-09-09 15:13:12REVISIONS OK -- SHTS P101, P201 & P202. -- SHT P001 NO
 CHANGES/REVISIONS FOUND RETURNED TO CONTRACTOR.

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-03-25 Cont ID  
Sent By kstevens Date 2009-03-25 Time 18:28 Rev Time 0.00
Received By kstevens Date 2009-03-25 Time 18:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2009-03-16 Cont ID  
Sent By eschneid Date 2009-03-16 Time 17:50 Rev Time 0.25
Received By eschneid Date 2009-03-16 Time 17:50 Sent To  
Notes
2009-03-16 17:58:14PASSED
  
 NOTE: IF PERMITS WITHIN A ONE YEAR PERIOD ON THE
 BUILDING AT 2201 45TH STREET EXCEED 50% OF THE VALUE OF
 THE BUILDING, THEN A LANDSCAPE PLAN SHOWING COMPLIANCE
 WITH THE CITY'S LANDSCAPE CODE IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.