Plan Review Details - Permit 09020632
Plan Review Stops For Permit 09020632
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-03-04 Cont ID  
Sent By mjacobs Date 2009-03-04 Time 15:52 Rev Time 0.00
Received By mjacobs Date 2009-03-04 Time 15:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-05-08 Cont ID  
Sent By dwise Date 2009-05-08 Time 18:15 Rev Time 0.00
Received By dwise Date 2009-05-08 Time 18:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-09 Cont ID  
Sent By btrobaug Date 2009-03-09 Time 09:09 Rev Time 0.00
Received By btrobaug Date 2009-03-09 Time 08:32 Sent To  
Notes
2009-03-09 09:09:40 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON
 THE PLANS, MUST SIGN AND SEAL THE PLAN PER
 481.221(1)(B)FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-05-11 Cont ID  
Sent By mawillia Date 2009-05-11 Time 11:25 Rev Time 0.00
Received By mawillia Date 2009-05-11 Time 10:46 Sent To B
Notes
2009-05-11 11:05:38*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEET A1.01 WAS STAMPED,
 INITIALED, AND DATED WITH THE FOLLOWING ADDED NOTE:
  
 STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATTIONS SHALL COMPLY WITH NFPA 241 -
 2004 EDITION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-03-09 Cont ID  
Sent By dwise Date 2009-05-08 Time 18:16 Rev Time 0.00
Received By mwennerg Date 2009-03-09 Time 13:28 Sent To  
Notes
2009-03-09 13:32:05***DENIED***
  
 1) ALL SUBMITTED SHEETS ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE DESIGN PROFESSIONAL IN ACCORDANCE WITH FS
 481.
  
 2) LIFE SAFETY TO COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE, 2007 THAT INCLUDES NFPA 101, 2006 AND
 NFPA 1, 2006 SINCE DECEMBER 31, 2008.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-12 Cont ID  
Sent By kstevens Date 2009-03-12 Time 10:01 Rev Time 0.00
Received By kstevens Date 2009-03-02 Time 11:38 Sent To  
Notes
2009-03-02 11:40:08TO "BOB"#7

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-05-08 Cont ID  
Sent By dwise Date 2009-05-08 Time 18:15 Rev Time 0.00
Received By dwise Date 2009-05-08 Time 18:15 Sent To FIRE
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-03-12 Cont ID  
Sent By kstevens Date 2009-03-12 Time 09:32 Rev Time 0.00
Received By kstevens Date 2009-03-11 Time 16:53 Sent To  
Notes
2009-03-12 09:54:43DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 EXISTING BUILDING
 FBC-2004 CHAPTER 1
  
 1. SHT A1.02 ACCESSIBILITY NOTE STATES "THE DRAIN AND
 WATER SUPPLY CONNECTIONS ALLOW THE UNIT TO BE SHIFTED
 IF NECESSARY TO ACCOMODATE THE REQUIRED FLOOR
 CLEAARANCES PER FACBC" PLEASE SUBMIT A DETAIL & MANUF.
 SPECIFICATIONS FOR THE DRAIN AND WATER SUPPLIES THAT
 INDICATES HOW THIS WORKS AND TO SHOW APPROVAL BY A
 THIRD PARTY TESTING & CERTIFICATION. SECTIONS 106.1.2 &
 303.4.
  
 2. SUBMIT MANUF. SEPCIFICATIONS FOR THE SINK. THE SINK
 SHALL MEET ASME A112.19.3M-87(R1996) STANDARD.
  
 3. SHT P1.01 NOTE STATES "REFER TO ATTACHED CUT SHEET"
 FOR PREFABRICATED KITCHEN COUNTER WITH RANGE,
 REFRIGERATOR, SINK, DISH WASHER ETC. CUT SHEET NOT
 ATTACHED. PLEASE SUBMIT THE MANUF. SPECIFICATION
 SHEETS. SECTIONS 106.1.2 & 303.4.
  
 4. SHT P1.01 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. THE OFFSETS SHOWN ON THE FLOOR PLAN ARE
 NOT SHOWN ON THE RISER DIAGRAM AND THE RISER SHOWS TWO
 TRAPS WHERE AS THE FLOOR PLAN SHOWS ONE TRAP. THE RISER
 DIAGRAM SHOWS A VENT AT THE SINK AREA THAT IS A DRY
 HORIZONTAL VENT WHICH IS NOT APPROVED AND NOT SHOWN ON
 THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS 106.1.1,
 905.3 & 905.4.
  
 5. SHT P1.01 WATER ISOMETRIC RISER DIAGRAM SHOWS AIR
 CHAMBERS AT THE SINK. AIR CHAMBERS ARE NOT APPROVED.
 PLEASE DELETE. SECTION 604.9 & PDI-WH 201. SECOND NOTE
 ONE INDICATES WATER HAMMER ARRESTORS ON THE HOT & COLD
 LINES BUT ONLY THE HOT LINE AT THE DISH WASHER IS
 SHOWING A WATER HAMMER ARRESTOR. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-03-02 Cont ID  
Sent By mflis Date 2009-03-02 Time 16:14 Rev Time 0.00
Received By mflis Date 2009-03-02 Time 16:14 Sent To  
Notes
***NONE***