Plan Review Details - Permit 09020614
Plan Review Stops For Permit 09020614
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-03 Cont ID  
Sent By btrobaug Date 2009-03-03 Time 11:36 Rev Time 0.00
Received By btrobaug Date 2009-03-03 Time 10:43 Sent To I
Notes
2009-03-03 11:35:25 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} NO APPLICATION WAS MADE TO INSTALL A WALK IN COOLER
 AT THIS ADDRESS.AN APPLICATION MUST BE MADE FOR THE
 COOLER WHICH WILL REQUIRE PRODUCT APPROVAL FOR THE
 INTENDED LOCATION PER RULE 9B-72, FLORIDA
 ADMINISTRATIVE CODE. THERE WILL ALSO BE A BUILDING
 REVIEW FOR WIND LOADING PER SECTION 1609 FBC, AND A
 MECHANICAL REVIEW PER CHAPTER 3 OF THE MECHANICAL CODE.
 AN ELECTRICAL PERMIT CANNOT BE ISSUED TO WIRE EQUIPMENT
 THAT HAS NOT BEEN PERMITTED. THE ELECTRICAL CONTRACTOR
 SHOULD SIGN AS A SUBCONTRACTOR ON THE MECHANICAL
 APPLICATION, AND SUBMIT HIS PLANS WITH SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  