Plan Review Details - Permit 09020538
Plan Review Stops For Permit 09020538
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-08 Cont ID  
Sent By adarroug Date 2009-04-08 Time 11:20 Rev Time 0.00
Received By adarroug Date 2009-04-08 Time 11:20 Sent To P
Notes
2009-04-08 11:21:08TO <5000 BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-04-15 Cont ID  
Sent By kstevens Date 2009-04-15 Time 08:53 Rev Time 0.00
Received By kstevens Date 2009-04-15 Time 08:53 Sent To  
Notes
2009-04-15 08:54:26PASSED/PROVISO: A FIXTURE SHALL NOT BE DOUBLE TRAPPED.
 SECTION 1002.1. -- A REVISIONS IS REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-03-16 Cont ID  
Sent By kstevens Date 2009-03-16 Time 11:18 Rev Time 0.00
Received By kstevens Date 2009-03-16 Time 11:18 Sent To  
Notes
2009-03-16 11:41:29DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 EXISTING BUILDING
 CITY WPB MUNICIPAL CODE
 ****FROM PREVIOUS REVIEW:
  
 1. SUBMIT AN ARCHITECTURAL QUALITY FLOOR PLAN SHOWING
 THE EXISTING FLOOR PLAN AND THE PROPOSED FLOOR PLAN SO
 THE EXTENT OF WORK CAN BE VERIFIED. SECTION 106.1.2
 (MORE INFORMATION REQUIRED). SHOW THE LOCATION OF ALL
 FIXTURES, SEATING, TOILET ROOM(S), LOCATION OF PROPOSED
 GREASE TRAP, SQUARE FOOTAGE OF THE SPACE, SANITARY AND
 WATER PIPING ETC. PER ARTICLE III SECTION 90-124(7)(B)
 THE GREASE INTERCEPTOR/TRAP CAN NOT BE LOCATED IN THE
 FOOD PREPARATION AREA.
 ****RESPONSE NOTED, BUT AN EXISTING FLOOR PLAN HAS NOT
 BEEN SUBMITTED. ALSO ALL PLANS SUBMITTED TO THE CITY
 WPB, IF NOT SIGNED, SEALED & DATED BY A DESIGN
 PROFESSIONAL SHALL HAVE THE PRINTED NAME & SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN ON EACH SHEET.
 SECTION 106.1.3.
  
 2. INDICATE ON THE PLANS THE CODE CRITERIA ON WHICH THE
 DESIGN IS BASED ON. (FBC-2004 W/2007 REVISIONS).
 SECTION 106.1.1.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 3. INDICATE ON THE PLANS THE LEVEL OF ALTERATION PER
 CHAPTER 3 OF THE EXISTING BUILDING CODE.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 4. THE GREASE INTERCEPTOR/TRAP SHALL BE SIZED BY THE
 UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH BY PHONE (561)
 822-2271, BY FAX (561) 822-2279 OR BY E-MAIL
 [email protected]. ARTICLE III SECTION 90-124(7).
 ****RESPONSE FROM H. MCGRATH INDICATES A 50 LB GREASE
 TRAP AT THE SINK BUT THE PLANS AND ISOMETRIC SHOW THE
 GREASE TRAP OUTSIDE. H. MCGRATH INDICATED IT WILL BE AT
 THE 3 COMPARTMENT SINK. PLEASE KNOW THAT IF THERE IS A
 REQUIREMENT FOR A GREASE TRAP THEN THE MOP SINK WILL BE
 REQUIRED TO DRAIN THROUGH THE GREAS TRAP ALSO.
  
 5. OK
 6. OK
  
 7. 104.6.5 BUILDING PERMIT VALUATION. IF
 IN THE OPINION OF THE BUILDING OFFICIAL
 THE CLAIMED VALUATION OF BUILDING, AL-
 TERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED ESTIMATES
 AND/OR BONA FIDED SIGNED CONTRACTS (EX-
 CLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION FOR BUILDINGS AND
 SYSTEMS SHALL BE FOUND IN MARSHALL AND
 SWIFT OR THE SOUTHERN BUILDING CODE
 CONGRESS INTERNATIONAL VALUATION TABLES,
 LATEST EDITION, AND SHALL BE BASED ON
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHAN-
 ICAL, INTERIOR FINISH, NORMAL SITE WORK
 (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, OVERHEAD
 AND PROFIT, EXCLUDING ONLY LAND VALUE. -- THE
 INSTALLATION OF A 3 COMPARTMENT SINK, A HAND SINK, A
 MOP SINK AND A GREASE TRAP WITH ALL THE REQUIRED WASTE
 & WATER PIPING, OPENING UP THE FLOOR, PATCHING THE
 FLOOR AS WELL AS THE COST OF THE FIXTURES FOR $2,400
 SEEMS TO BE UNDERESTIMATED. PLEASE SUBMIT A VALUE THAT
 WOULD BE MORE IN LINE WITH THE WORK BEING DONE.
 ****RESPONSE NOTED, BUT IT MAKES NO DIFFERENCE WHO
 SUPPLIES THE SINKS, FAUCETS, GREASE TRAP/INTERCEPTOR
 PIPING ETC. THE TOTAL VALUE OF THE PLUMBING SHALL BE
 INDICATING ON THE PERMIT APPLICATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-02-27 Cont ID  
Sent By kstevens Date 2009-02-27 Time 14:26 Rev Time 0.00
Received By kstevens Date 2009-02-27 Time 14:26 Sent To  
Notes
2009-02-27 14:55:50DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 EXISTING BUILDING
 CITY WPB MUNICIPAL CODE
  
 1. SUBMIT AN ARCHITECTURAL QUALITY FLOOR PLAN SHOWING
 THE EXISTING FLOOR PLAN AND THE PROPOSED FLOOR PLAN SO
 THE EXTENT OF WORK CAN BE VERIFIED. SECTION 106.1.2
 (MORE INFORMATION REQUIRED). SHOW THE LOCATION OF ALL
 FIXTURES, SEATING, TOILET ROOM(S), LOCATION OF PROPOSED
 GREASE TRAP, SQUARE FOOTAGE OF THE SPACE, SANITARY AND
 WATER PIPING ETC. PER ARTICLE III SECTION 90-124(7)(B)
 THE GREASE INTERCEPTOR/TRAP CAN NOT BE LOCATED IN THE
 FOOD PREPARATION AREA.
  
 2. INDICATE ON THE PLANS THE CODE CRITERIA ON WHICH THE
 DESIGN IS BASED ON. (FBC-2004 W/2007 REVISIONS).
 SECTION 106.1.1.
  
 3. INDICATE ON THE PLANS THE LEVEL OF ALTERATION PER
 CHAPTER 3 OF THE EXISTING BUILDING CODE.
  
 4. THE GREASE INTERCEPTOR/TRAP SHALL BE SIZED BY THE
 UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH BY PHONE (561)
 822-2271, BY FAX (561) 822-2279 OR BY E-MAIL
 [email protected]. ARTICLE III SECTION 90-124(7).
  
 5. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES, AND (IF REQUIRED BY 604.9), WATER HAMMER
 ARRESTORS AS WELL AS POINT OF CONNECTION. SECTIONS
 106.3.5.1.3 AND 701.1.
  
 6. PLEASE INDICATE ON THE APPLICATION IS THIS IS A
 CHANGE OF OCCUPANCY AND THE SQUARE FOOTAGE OF THE
 SPACE. SECTION 105.1.
  
 7. 104.6.5 BUILDING PERMIT VALUATION. IF
 IN THE OPINION OF THE BUILDING OFFICIAL
 THE CLAIMED VALUATION OF BUILDING, AL-
 TERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED ESTIMATES
 AND/OR BONA FIDED SIGNED CONTRACTS (EX-
 CLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION FOR BUILDINGS AND
 SYSTEMS SHALL BE FOUND IN MARSHALL AND
 SWIFT OR THE SOUTHERN BUILDING CODE
 CONGRESS INTERNATIONAL VALUATION TABLES,
 LATEST EDITION, AND SHALL BE BASED ON
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHAN-
 ICAL, INTERIOR FINISH, NORMAL SITE WORK
 (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, OVERHEAD
 AND PROFIT, EXCLUDING ONLY LAND VALUE. -- THE
 INSTALLATION OF A 3 COMPARTMENT SINK, A HAND SINK, A
 MOP SINK AND A GREASE TRAP WITH ALL THE REQUIRED WASTE
 & WATER PIPING, OPENING UP THE FLOOR, PATCHING THE
 FLOOR AS WELL AS THE COST OF THE FIXTURES FOR $2,400
 SEEMS TO BE UNDERESTIMATED. PLEASE SUBMIT A VALUE THAT
 WOULD BE MORE IN LINE WITH THE WORK BEING DONE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved