Plan Review Details - Permit 09020527
Plan Review Stops For Permit 09020527
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-30 Cont ID  
Sent By shill Date 2009-04-30 Time 11:25 Rev Time 0.00
Received By shill Date 2009-04-30 Time 11:25 Sent To E
Notes
2009-04-30 11:27:14PLANS REDLINED; WALL DETAIL DOES NOT COMPLY WITH
 FBC703.6.3.1.
  
 REDLINED AND CODE SECTION STAPED TO PLAN
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-04-10 Cont ID  
Sent By shill Date 2009-04-10 Time 09:56 Rev Time  
Received By shill Date 2009-04-08 Time 07:59 Sent To  
Notes
2009-04-10 10:16:04****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. THE COVER SHEET FOR THE PRODUCT APPROVAL FOR
 HURRICANE PANELS WAS PROVIDED. THE EVALUATION REPORT,
 INSTALLATION INSTRUCTIONS, AND INSTALLATION SCHEDULE
 FORM ARE REQUIRED. THE INSTALLATION SCHEDULE FORM IS
 AVAILABLE IN THE LOBBY OR ON THE INTERNET AT HTTP://WWW
 .CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLAT
 ION.PDF.
  
 THIS PERMIT CAN BE ISSUED WITH THE PROVISO THAT
 SHUTTERS ARE REQUIRED AS A SEPARATE PERMIT.
  
 2-4. ADDRESSED.
  
 5. A SGD IS SHOWN AS "INFILL" ON AN ELEVATION, ANOTHER
 ELEVATION SHOWS A WALL WITH A WINDOW, BUT THE WALL
 DETAIL DOESN'T SHOW A WINDOW. THE DETAIL DOES NOT MATCH
 THE SCOPE OF WORK.
  
 2ND REVIEW, NOT ADDRESSED. PROVIDE STRUCTURAL DETAILS
 FOR THE WALLS TO BE BUILT WHICH SHOW THE STRUCTURAL
 DETAIL FOR FRAMING TO SUPPORT THE WINDOW AND SLIDING
 GLASS DOOR.
  
 7. SHOW FINISHED FLOOR IN RELATION TO THE GRADE FBC
 R404.1.6.
  
 2ND REVIEW, THIS WAS ADDED BUT NOW THE DETAIL DOES NOT
 COMPLY WITH FBC R403.1.4. PLEASE REVISE THE DETAIL.
  
 8. ADDRESSED.
  
 9. SEE ITEM 1.
  
 10. BOND BREAK REQUIRED, FBC703.6.3.1.
  
 A NOTE WAS ADDED STATING BOND BREAK REQUIRED BUT THE
 DETAIL SHOWING WALL CONSTRUCTION DOES NOT COMPLY WITH
 FBC703.6.3.1. IT IS UNCLEAR WHAT THE NOTE MEANS AS THE
 SPECIFICATION FOR CONSTRUCTION DOES NOT COMPLY WITH THE
 CODE SECTION OR THE NOTE. PLEASE REVISE.
  
 11. SHOW COMPLIANCE WITH FBC704, INSPECTION FOR
 TERMITES.
  
 A NOTE WAS ADDED, BUT THE DETAIL FOR CONSTRUCTION DOES
 NOT COMPLY WITH THIS SECTION. IT IS UNCLEAR WHAT THE
 NOTE CONTRACTOR TO PROVIDE PROOF OF TERMITE PROTECTION
 MEANS OR HOW IT SHOWS COMPLIANCE WITH THIS SECTION.
 PLEASE REVISE.
  
 A SET HAS BEEN RETAINED. WHEN RESUBMITTING, PLEASE
 SUBMIT TWO SETS.
  
 NEW COMMENT:
  
 FS553.80(2)(B) A 4X PLAN REVIEW FEE WILL BE ASSESSED
 WITH COMMENTS ARE NOT ADDRESSED A THIRD TIME.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-03 Cont ID  
Sent By shill Date 2009-03-03 Time 11:43 Rev Time 0.00
Received By shill Date 2009-03-03 Time 11:43 Sent To E
Notes
2009-03-03 11:47:10****CORRECTIONS****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE APPLICATION STATES THAT THE HOMEOWNER HAS
 EXISTING HURRICANE SHUTTERS. PLEASE PROVIDE A PERMIT
 NUMBER FOR THE EXISTING SHUTTERS; SHUTTERS ARE TO BE IN
 ACCORDANCE WITH FBC, SEE FBC R 301.2.1.2, FBC EB 507.
  
 2. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 505.1.
  
 3. ON THE FLOOR PLAN, SHOW THE LOCATION OF THE PROPOSED
 STRUCTURAL WORK.
  
 4. SCOPE OF WORK IS NOT CLEAR. THE "EXISTING FLOOR PLAN
 - REMODEL" STATES THAT THE "NEW SGD TO REMAIN." IF IT'S
 NEW, HOW CAN IT REMAIN?
  
 5. A SGD IS SHOWN AS "INFILL" ON AN ELEVATION, ANOTHER
 ELEVATION SHOWS A WALL WITH A WINDOW, BUT THE WALL
 DETAIL DOESN'T SHOW A WINDOW. THE DETAIL DOES NOT MATCH
 THE SCOPE OF WORK.
  
 6. THE WALL FRAMING SECTION DOES NOT SHOW FASTENING AT
 THE TOP OF THE WALL. THE ELEVATION SHOWS A WINDOW, BUT
 NO WINDOW (OR STRUCTURAL SUPPORT) IS SHOWN ON THE WALL
 FRAMING DETAIL.
  
 7. SHOW FINISHED FLOOR IN RELATION TO THE GRADE, FBC
 R404.1.6. IT APPEARS THAT THIS SCREENED AREA IS BEING
 CONVERTED TO INTERIOR SPACE.
  
 8. PALM BEACH COUNTY IMPACT FEE ASSESSMENT REQUIRED DUE
 TO INCREASE OF HABITABLE SPACE, 561-233-5025. THE PLANS
 MUST BE STAMPED AND THE RECEIPT, IF FEES ARE DUE,
 ATTACHED TO THE APPLICATION.
  
 9. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE INSTALLATION SCHEDULE OR SUBMIT
 ALL INFORMATION IN ANOTHER FORMAT.
  
 10. BOND BREAK REQUIRED, FBC703.6.3.1.
  
 11. SHOW COMPLIANCE WITH FBC704, INSPECTION FOR
 TERMINTES.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-04-30 Cont ID  
Sent By btrobaug Date 2009-04-30 Time 16:06 Rev Time 0.00
Received By btrobaug Date 2009-04-30 Time 15:59 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-07 Cont ID  
Sent By btrobaug Date 2009-04-07 Time 13:46 Rev Time 0.00
Received By btrobaug Date 2009-04-07 Time 13:39 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-04 Cont ID  
Sent By btrobaug Date 2009-03-04 Time 11:44 Rev Time 0.00
Received By btrobaug Date 2009-03-04 Time 11:32 Sent To PC
Notes
2009-03-04 11:43:55 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} COMPLY WITH THE FOLLOWING ARTICLE 2005 NEC.
 210.52 DWELLING UNIT RECEPTACLE OUTLETS
 (A) GENERAL PROVISIONS IN EVERY KITCHEN, FAMILY ROOM,
 DINING ROOM, LIVING ROOM, PARLOR, LIBRARY, DEN,
 SUNROOM, BEDROOM, RECREATION ROOM, OR SIMILAR ROOM OR
 AREA OF DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE GENERAL PROVISIONS
 SPECIFIED IN 210.52(A)(1) THROUGH (A)(3).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-28 Cont ID  
Sent By dpalmer Date 2009-04-28 Time 16:02 Rev Time 0.00
Received By dpalmer Date 2009-04-28 Time 16:02 Sent To B
Notes
2009-04-28 16:02:30TO SH' S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-06 Cont ID  
Sent By adarroug Date 2009-04-06 Time 10:32 Rev Time 0.00
Received By adarroug Date 2009-04-06 Time 10:32 Sent To E
Notes
2009-04-06 10:33:18TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-03 Cont ID  
Sent By shill Date 2009-03-03 Time 11:47 Rev Time 0.00
Received By shill Date 2009-02-26 Time 15:15 Sent To  
Notes
2009-02-26 15:17:18TO "MISC" BOX#1