Plan Review Details - Permit 09020504
Plan Review Stops For Permit 09020504
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-06-19 Cont ID  
Sent By lmartine Date 2009-06-19 Time 16:35 Rev Time 0.00
Received By lmartine Date 2009-06-19 Time 16:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-06-08 Cont ID  
Sent By shill Date 2009-06-08 Time 15:44 Rev Time 0.00
Received By shill Date 2009-06-08 Time 15:44 Sent To  
Notes
2009-06-08 15:45:47****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. PROVIDE A ROOF DIAGRAM SHOWING PROPOSED LOCATION AND
 EXISTING ROOF PITCH. FBC R301. THE ENGINEERING PROVIDED
 STATES THAT THE INSTALLATION COMPLIES BUT SPECIFIC
 INFORMATION REGARDING LOCATION (REQUIRED TO DETERMINE
 DESIGN PRESSURE) WAS NOT PROVIDED IN THE PLANS.
  
 2. PLEASE CLARIFY; S2 STATES THAT THIS INSTALLATION IS
 FOR A ROOF SUBJECTED TO MAXIMUM PRESSURE OF 67PSF. S3
 INCLUDES A TABLE WHICH PROVIDES ROOF PRESSURES FOR
 COMPONENTS & CLADDING FOR 20SF AND 50SF OF EFFECTIVE
 WIND AREA. IT IS NOT CLEAR WHETHER THIS DESIGN CRITERIA
 APPLIES TO THE WIND RESISTANCE OF THE SOLAR PANEL
 ITSELF OR UPLIFT PRESSURE ON THE FASTENER. WOULDN'T
 EACH FASTENER HAVE AN EFFECTIVE WIND AREA OF LESS THAN
 10SF (40SF TOTAL SF, DIVIDED BY FOUR FASTENERS)? SEE
 FBC1609.2, DEFINITION OF EFFECTIVE WIND AREA. IT
 APPEARS THAT THE DESIGN CRITERIA WIND PRESSURES REGARD
 THE SOLAR PANEL AREA AS A BUILDING COMPONENT (LIKE A
 WINDOW OR DOOR) RATHER THAN TREATING IT AS CLADDING,
 AREA TRIBUTARY TO EACH FASTENER (SUCH AS ROOF OR SIDING
 CLADDING). IT APPEARS THAT FOR EACH INSTALLATION THE
 WORST CASE (DESIGN PRESSURES ON FASTENER RATHER THAN ON
 THE PANEL) WOULD GOVERN, BUT 10SF (WHICH WOULD APPLY TO
 THIS JOB) PRESSURES WERE NOT PROVIDED. PLEASE EITHER
 CLARIFY WIND RESISTANCE STATEMENT (THAT BOTH PANEL AND
 FASTENER HAS BEEN ADDRESSED IN DETERMING THAT THE
 INSTALLATION IS COMPLIANT FOR -67PSF) AND INCLUDE 10SF
 EFFECTIVE WIND AREA ON THE CHART, OR PROVIDE RATIONALE
 FOR USING COMPONENT DESIGN PRESSURE FOR FASTENERS.
  
 THE SAME PLANS DATED 2/16/09 WERE RESUBMITTED. PLEASE
 ADDRESS COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-26 Cont ID  
Sent By shill Date 2009-03-26 Time 09:52 Rev Time 0.00
Received By shill Date 2009-03-26 Time 09:52 Sent To M
Notes
2009-03-26 10:38:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PROVIDE A ROOF DIAGRAM SHOWING PROPOSED LOCATION AND
 EXISTING ROOF PITCH. FBC R301. THE ENGINEERING PROVIDED
 STATES THAT THE INSTALLATION COMPLIES BUT SPECIFIC
 INFORMATION REGARDING LOCATION (REQUIRED TO DETERMINE
 DESIGN PRESSURE) WAS NOT PROVIDED IN THE PLANS.
  
 2. PLEASE CLARIFY; S2 STATES THAT THIS INSTALLATION IS
 FOR A ROOF SUBJECTED TO MAXIMUM PRESSURE OF 67PSF. S3
 INCLUDES A TABLE WHICH PROVIDES ROOF PRESSURES FOR
 COMPONENTS & CLADDING FOR 20SF AND 50SF OF EFFECTIVE
 WIND AREA. IT IS NOT CLEAR WHETHER THIS DESIGN CRITERIA
 APPLIES TO THE WIND RESISTANCE OF THE SOLAR PANEL
 ITSELF OR UPLIFT PRESSURE ON THE FASTENER. WOULDN'T
 EACH FASTENER HAVE AN EFFECTIVE WIND AREA OF LESS THAN
 10SF (40SF TOTAL SF, DIVIDED BY FOUR FASTENERS)? SEE
 FBC1609.2, DEFINITION OF EFFECTIVE WIND AREA. IT
 APPEARS THAT THE DESIGN CRITERIA WIND PRESSURES REGARD
 THE SOLAR PANEL AREA AS A BUILDING COMPONENT (LIKE A
 WINDOW OR DOOR) RATHER THAN TREATING IT AS CLADDING,
 AREA TRIBUTARY TO EACH FASTENER (SUCH AS ROOF OR SIDING
 CLADDING). IT APPEARS THAT FOR EACH INSTALLATION THE
 WORST CASE (DESIGN PRESSURES ON FASTENER RATHER THAN ON
 THE PANEL) WOULD GOVERN, BUT 10SF (WHICH WOULD APPLY TO
 THIS JOB) PRESSURES WERE NOT PROVIDED. PLEASE EITHER
 CLARIFY WIND RESISTANCE STATEMENT (THAT BOTH PANEL AND
 FASTENER HAS BEEN ADDRESSED IN DETERMING THAT THE
 INSTALLATION IS COMPLIANT FOR -67PSF) AND INCLUDE 10SF
 EFFECTIVE WIND AREA ON THE CHART, OR PROVIDE RATIONALE
 FOR USING COMPONENT DESIGN PRESSURE FOR FASTENERS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-03-04 Cont ID  
Sent By btrobaug Date 2009-03-04 Time 10:43 Rev Time 0.00
Received By btrobaug Date 2009-03-04 Time 10:29 Sent To B
Notes
2009-03-04 10:43:49 
  
 PROVISO
  
 61G4-15.021 CERTIFICATION OF SOLAR CONTRACTORS. (A)
 ELECTRICAL WORK. THE BRANCH CIRCUIT SUPPLYING THE
 ELECTRIC WATER HEATER, THE RECEPTACLE OUTLET FOR A
 CORD-AND-PLUG-CONNECTED SOLAR CONTROLLER, THE SWIMMING
 POOL PUMP MOTOR, AND THE PREMISES WIRING ON THE LOAD
 SIDE OF THE PREMISES SERVICE DISCONNECTING MEANS SHALL
 BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE. IF
 INSTALLATION, ALTERATION, REMOVAL, REPLACEMENT, OR
 UPGRADING OF THIS CIRCUIT IS NECESSARY, THE WORK SHALL
 BE PERFORMED BY LICENSED ELECTRICAL CONTRACTORS ONLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-05-07 Cont ID  
Sent By shill Date 2009-05-07 Time 16:23 Rev Time 0.00
Received By shill Date 2009-05-07 Time 16:23 Sent To M
Notes
2009-05-07 16:24:17TO MECHANICAL BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-07 Cont ID  
Sent By shill Date 2009-04-06 Time 16:23 Rev Time 0.00
Received By shill Date 2009-05-07 Time 16:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-06-24 Cont ID  
Sent By hmoser Date 2009-06-24 Time 15:15 Rev Time 0.00
Received By hmoser Date 2009-06-24 Time 15:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-06-08 Cont ID  
Sent By hmoser Date 2009-06-08 Time 14:25 Rev Time 0.00
Received By hmoser Date 2009-06-08 Time 14:25 Sent To B
Notes
2009-06-08 14:27:34SAME AS LAST REVIEW .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-04-06 Cont ID  
Sent By hmoser Date 2009-04-06 Time 14:34 Rev Time 0.00
Received By hmoser Date 2009-04-06 Time 14:34 Sent To  
Notes
2009-04-06 14:37:52PLEASE PROVIDE PIPING PLANS FROM SOLAR SYSTEM TO WATER
 HEATER .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-02-27 Cont ID  
Sent By kstevens Date 2009-02-27 Time 16:01 Rev Time 0.00
Received By kstevens Date 2009-02-27 Time 16:01 Sent To E
Notes
***NONE***