| 2009-02-26 15:49:56 | 2004 FBC W/2007 REVISIONS |
| | REPLACE 9 WINDOWS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE VALUE SPECIFIED FOR THE WORK OF $700.00 IS TOO |
| | LOW. THE VALUE IS THE COST OF MATERIALS, LABOR, |
| | OVERHEAD AND PROFIT AS WOULD BE CHARGED BY A |
| | CONTRACTOR. FBC 108.3* CITY AMENDMENTS. PLEASE REVISE |
| | COST ON APPLICATION. |
| | |
| | 2) SUBMIT TWO COPIES OF CURRENT PRODUCT APPROVALS FOR |
| | THE NEW WINDOWS THAT WILL BE INSTALLED. DCA RULE 9B-72. |
| | THE ONES THAT WERE SUBMITTED ARE EXPIRED. |
| | |
| | 3) SUBMIT TWO COPIES OF A FLOOR PLAN OF THE HOUSE |
| | SPECIFYING EACH ROOM TYPE AND INDICATING THE LOCATION |
| | AND SIZE OF THE WINDOWS THAT WILL BE INSTALLED. IF |
| | THERE ARE ANY DOUBLE WINDOWS THAT ARE JOINED TOGETHER |
| | WITH A MULLION, SUBMIT PRODUCT APPROVALS FOR THE |
| | MULLION. FBC EXISTING BUILDING 507.3 AND DCA RULE 9B-72 |
| | |
| | 4) THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR |
| | TWO DIFFERENT WINDOW MODELS FROM DIFFERENT |
| | MANUFACTURER'S. IF THIS IS THE CASE PLEASE INDICATE THE |
| | LOCATION OF EACH DIFFERENT WINDOW TYPE. |
| | |
| | 5) IF YOU ARE REPLACING MORE THAN 25 PERCENT OF THE |
| | GLASS AREA IN THE DWELLING, IMPACT PROTECTION WILL BE |
| | REQUIRED FOR THE NEW WINDOWS. FBC EXISTING BUILDING |
| | 507.3 |
| | IF NOT USING IMPACT RATED WINDOWS, SUBMIT TWO COPIES OF |
| | STORM PANELS PRODUCT APPROVALS, INSTALLATION SCHEDULE |
| | AND KEY PLANS. SPECIFY OPENING SIZES, ANCHOR TYPE, |
| | ANCHOR SPACING, MOUNT TYPE, ETC. SEE ATTACHED SCHEDULE. |
| | |