Plan Review Details - Permit 09020440
Plan Review Stops For Permit 09020440
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-04-23 Cont ID  
Sent By rmcdouga Date 2009-04-23 Time 11:22 Rev Time 0.00
Received By rmcdouga Date 2009-04-23 Time 11:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-30 Cont ID  
Sent By rmcdouga Date 2009-03-30 Time 16:48 Rev Time 0.00
Received By rmcdouga Date 2009-03-30 Time 13:27 Sent To  
Notes
2009-03-30 15:25:202004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) THE WRONG ENERGY CALCULATION WAS SUBMITTED. THE FORM
 REQUIRED FOR THE 2004 FBC IS 600C-04. PLEASE SUBMIT TWO
 COPIES OF THE CORRECT FORM.
  
 2) THE PRESCRIPTIVE METHOD C REQUIRES R-5 INSULATION ON
 THE CONCRETE BLOCK WALLS. SEE THE ENERGY CALCULATION
 FORM. THE PLANS SPECIFY R-4.2. PLEASE CORRECT.
  
 3) SHOW COMPLIANCE WITH R408.1 VENTILATION.
 THE UNDER-FLOOR SPACE BETWEEN THE BOTTOM OF THE FLOOR
 JOISTS AND THE EARTH UNDER ANY BUILDING (EXCEPT SPACE
 OCCUPIED BY A BASEMENT OR CELLAR) SHALL BE PROVIDED
 WITH VENTILATION OPENINGS THROUGH FOUNDATION WALLS OR
 EXTERIOR WALLS. THE MINIMUM NET AREA OF VENTILATION
 OPENINGS SHALL NOT BE LESS THAN 1 SQUARE FOOT FOR EACH
 150 SQUARE FEET (0.67 M2 FOR EACH 100 M2) OF
 UNDER-FLOOR SPACE AREA. ONE SUCH VENTILATING OPENING
 SHALL BE WITHIN 3 FEET (914 MM) OF EACH CORNER OF SAID
 BUILDING.
  
 4) SHOW COMPLIANCE WITH R408.3 ACCESS.
 ACCESS SHALL BE PROVIDED TO ALL UNDER-FLOOR SPACES.
 ACCESS OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF
 18 INCHES BY 24 INCHES (457 MM BY 610 MM). OPENINGS
 THROUGH A PERIMETER WALL SHALL BE 16 INCHES BY 24
 INCHES (407 MM BY 610 MM). WHEN ANY PORTION OF THE
 THROUGH WALL ACCESS IS BELOW GRADE, AN AREAWAY OF NOT
 LESS THAN 16 INCHES BY 24 INCHES (407 MM BY 610 MM)
 SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY SHALL BE
 BELOW THE THRESHOLD OF THE ACCESS OPENING. THROUGH WALL
 ACCESS OPENINGS SHALL NOT BE LOCATED UNDER A DOOR TO
 THE RESIDENCE. SEE M1305.1.4 FOR ACCESS REQUIREMENTS
 WHERE MECHANICAL EQUIPMENT IS LOCATED UNDER FLOORS.
  
 5) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 PGT WINDOWS HAVE NOT BEEN REVIEWED BY THE ARCHITECT.
  
 6) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 7) NOTE: A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-03-09 Cont ID  
Sent By btrobaug Date 2009-03-09 Time 09:41 Rev Time 0.00
Received By btrobaug Date 2009-03-09 Time 09:36 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-21 Cont ID  
Sent By shill Date 2009-04-21 Time 11:45 Rev Time 0.00
Received By shill Date 2009-04-21 Time 11:45 Sent To  
Notes
2009-04-21 11:45:50TO RM DESK (REMOVED FROM RES BOARD)
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-17 Cont ID  
Sent By swurafti Date 2009-04-17 Time 11:38 Rev Time 0.00
Received By swurafti Date 2009-04-17 Time 11:38 Sent To  
Notes
2009-04-17 11:46:50TO "R7"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-30 Cont ID  
Sent By rmcdouga Date 2009-03-30 Time 16:48 Rev Time 0.00
Received By rmcdouga Date 2009-02-24 Time 14:25 Sent To  
Notes
2009-02-24 14:27:25TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-03-24 Cont ID  
Sent By hmoser Date 2009-03-24 Time 14:57 Rev Time 0.00
Received By hmoser Date 2009-03-24 Time 14:57 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-03-27 Cont ID  
Sent By kstevens Date 2009-03-27 Time 15:19 Rev Time 0.00
Received By kstevens Date 2009-03-27 Time 15:19 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-04-23 Cont ID  
Sent By mcruz Date 2009-04-23 Time 08:43 Rev Time 0.00
Received By mcruz Date 2009-04-23 Time 08:43 Sent To B
Notes
2009-04-23 08:43:42GAVE TO RMC

Review Stop Z ZONING
Rev No 1 Status P Date 2009-03-05 Cont ID  
Sent By mcruz Date 2009-03-05 Time 11:29 Rev Time 0.00
Received By mcruz Date 2009-03-05 Time 11:21 Sent To E
Notes
2009-03-05 11:29:51PLACED ON SF RACK UNDER E.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved