| 2009-03-06 08:29:05 | BUILDING PLAN REVIEW |
| | PERMIT: 09020388 |
| | ADD: 1617 N. FLAGLER DR. LPH01 |
| | CONT: DREAM BUILDERS CORP. |
| | TEL: (561)716-1291 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1 |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION |
| | SHALL BE SHOWN ON THE PLANS. |
| | |
| | 4) THE DRAWINGS SHALL STATE THE USE AND OCCUPANCY OF |
| | THE BUILDING PER FBC CHAPTER 3 AND TABLE 503, THE TYPE |
| | OF CONSTRUCTION PER FBC CHAPTER 6 AND TABLE 601. |
| | |
| | 5) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. THE PLANS NEED TO STATE THE LEVEL OF |
| | ALTERATION. |
| | |
| | 6) SUBMIT TWO SETS OF ARCHITECTURAL DIMENSIONAL PLANS |
| | DRAWN TO A MINIMUM OF 1/8 INCH SCALE ON SUBSTANTIAL |
| | PAPER INDICATING THE USE OF EACH ROOM. CONSTRUCTION |
| | DOCUMENTS SHALL BE PREPARED BY A DESIGN PROFESSIONAL |
| | REGISTERED WITH THE STATE. THE DESIGN PROFESSIONAL |
| | SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE AND |
| | DATE TO EACH SHEET PER FLORIDA STATUTES 471 AND 481. |
| | SUBMIT AN EXISTING FLOOR PLAN A PROPOSED FLOOR PLAN |
| | SHOWING ALL NEW WALLS. A WALL LEGEND IS REQUIRED TO |
| | SHOW THE DIFFERENT TYPES OF WALLS INCLUDING THE |
| | EXISTING WALLS. PROVIDE A WALL DETAIL OF EACH WALL |
| | SHOWING HOW THEY WILL BE FASTENED TO THE FLOOR AND |
| | STRUCTURE ABOVE AND WHAT MATERIALS WILL BE USE TO |
| | CONSTRUCT THE WALLS; ADDITIONAL INFORMATION IS REQUIRED |
| | 106.1.2. |
| | |
| | 7) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | 8) TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| | PROVIDE INFORMATION BASED ON INTERIOR FINISH |
| | REQUIREMENTS BASED ON OCCUPANCY. |
| | |
| | 9) FBC 1207.3 FLOOR/ CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | SERVICE SHALL HAVE AN IMPACT INSULATION CLASS (IIC) |
| | RATING OF NOT LESS THAN 50 (45 IF FIELD TESTED) IN |
| | ACCORDANCE WITH ASTM E 492 OR THE SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR BORNE NOISE IN ACCORDANCE WITH ASTM E 90. |
| | PROVIDE THE INFORMATION FOR THE CORK/SOUND |
| | TRANSMISSION. |
| | |
| | 10) NOW THE SPACE IS BEING ALTERED, SHOW HOW THE FIRE |
| | ALARM SYSTEM HAS BEEN AFFECTED AND HOW THE SPACE STILL |
| | IN COMPLIANCE WITH FBC 907.2.9. SINGLE OR |
| | MULTIPLE-STATION SMOKE ALARMS SHALL BE INSTALLED AND |
| | MAINTAINED IN R-2 OCCUPANCIES REGARDLESS OF OCCUPANT |
| | LOAD. THE SMOKE ALARMS SHALL BE LOCATED IN EACH |
| | SLEEPING ROOM, ON CEILING OR WALL OUTSIDE OF EACH |
| | SEPARATE SLEEPING ROOM IN THE IMMEDIATE VICINITY OF |
| | BEDROOMS FBC 907.2.10.1.2. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | PHONE (561)805-6726 |
| | FAX (561)805-6676 |
| | [email protected] |
| | |