Plan Review Details - Permit 09020388
Plan Review Stops For Permit 09020388
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-07 Cont ID  
Sent By mjacobs Date 2009-04-07 Time 17:53 Rev Time 0.00
Received By mjacobs Date 2009-04-07 Time 17:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-03-06 Cont ID  
Sent By mjacobs Date 2009-03-06 Time 08:29 Rev Time 0.00
Received By mjacobs Date 2009-03-05 Time 14:38 Sent To  
Notes
2009-03-06 08:29:05BUILDING PLAN REVIEW
 PERMIT: 09020388
 ADD: 1617 N. FLAGLER DR. LPH01
 CONT: DREAM BUILDERS CORP.
 TEL: (561)716-1291
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE SHOWN ON THE PLANS.
  
 4) THE DRAWINGS SHALL STATE THE USE AND OCCUPANCY OF
 THE BUILDING PER FBC CHAPTER 3 AND TABLE 503, THE TYPE
 OF CONSTRUCTION PER FBC CHAPTER 6 AND TABLE 601.
  
 5) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. THE PLANS NEED TO STATE THE LEVEL OF
 ALTERATION.
  
 6) SUBMIT TWO SETS OF ARCHITECTURAL DIMENSIONAL PLANS
 DRAWN TO A MINIMUM OF 1/8 INCH SCALE ON SUBSTANTIAL
 PAPER INDICATING THE USE OF EACH ROOM. CONSTRUCTION
 DOCUMENTS SHALL BE PREPARED BY A DESIGN PROFESSIONAL
 REGISTERED WITH THE STATE. THE DESIGN PROFESSIONAL
 SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE AND
 DATE TO EACH SHEET PER FLORIDA STATUTES 471 AND 481.
 SUBMIT AN EXISTING FLOOR PLAN A PROPOSED FLOOR PLAN
 SHOWING ALL NEW WALLS. A WALL LEGEND IS REQUIRED TO
 SHOW THE DIFFERENT TYPES OF WALLS INCLUDING THE
 EXISTING WALLS. PROVIDE A WALL DETAIL OF EACH WALL
 SHOWING HOW THEY WILL BE FASTENED TO THE FLOOR AND
 STRUCTURE ABOVE AND WHAT MATERIALS WILL BE USE TO
 CONSTRUCT THE WALLS; ADDITIONAL INFORMATION IS REQUIRED
 106.1.2.
  
 7) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
 8) TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
  
 9) FBC 1207.3 FLOOR/ CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 SERVICE SHALL HAVE AN IMPACT INSULATION CLASS (IIC)
 RATING OF NOT LESS THAN 50 (45 IF FIELD TESTED) IN
 ACCORDANCE WITH ASTM E 492 OR THE SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR BORNE NOISE IN ACCORDANCE WITH ASTM E 90.
 PROVIDE THE INFORMATION FOR THE CORK/SOUND
 TRANSMISSION.
  
 10) NOW THE SPACE IS BEING ALTERED, SHOW HOW THE FIRE
 ALARM SYSTEM HAS BEEN AFFECTED AND HOW THE SPACE STILL
 IN COMPLIANCE WITH FBC 907.2.9. SINGLE OR
 MULTIPLE-STATION SMOKE ALARMS SHALL BE INSTALLED AND
 MAINTAINED IN R-2 OCCUPANCIES REGARDLESS OF OCCUPANT
 LOAD. THE SMOKE ALARMS SHALL BE LOCATED IN EACH
 SLEEPING ROOM, ON CEILING OR WALL OUTSIDE OF EACH
 SEPARATE SLEEPING ROOM IN THE IMMEDIATE VICINITY OF
 BEDROOMS FBC 907.2.10.1.2.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561)805-6676
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-02 Cont ID  
Sent By kconrad Date 2009-03-02 Time 11:47 Rev Time 0.00
Received By kconrad Date 2009-03-02 Time 11:47 Sent To  
Notes
2009-03-02 11:50:44PREINSPECT PERFORMED BY CHUCK JORDAN. REQUIRE PLANS AND
 MEP PERMITS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-04-09 Cont ID  
Sent By dpalmer Date 2009-04-09 Time 13:08 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2009-04-09 13:09:10REVIEW STOP FOR PROCESSING PLANS OUT ONLY. EXPEDITED,
 NO REVIEWERS LEFT

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-07 Cont ID  
Sent By btrobaug Date 2009-04-07 Time 17:43 Rev Time 0.00
Received By btrobaug Date 2009-04-07 Time 17:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-17 Cont ID  
Sent By btrobaug Date 2009-03-17 Time 08:53 Rev Time 0.00
Received By btrobaug Date 2009-03-17 Time 08:27 Sent To  
Notes
2009-03-17 08:52:47 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2007 FLORIDA BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2006, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 3} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED.
  
 4} THE ROOM (NOT LABELED) IN THE SOUTH EAST CORNER OF
 THE UNIT APPEARS TO MEET THE DEFINITION OF A BEDROOM
 PER THE FBC. SMOKE ALARMS MUST BE INSTALLED PER 313.1.1
 FBC RESIDENTIAL***.R313.1 SMOKE ALARMS.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS BUT NOT INCLUDING CRAWL SPACES AND
 UNINHABITABLE ATTICS. IN DWELLINGS OR DWELLING UNITS
 WITH SPLIT LEVELS AND WITHOUT AN INTERVENING DOOR
 BETWEEN THE ADJACENT LEVELS, A SMOKE ALARM INSTALLED ON
 THE UPPER LEVEL SHALL SUFFICE FOR THE ADJACENT LOWER
 LEVEL PROVIDED THAT THE LOWER LEVEL IS LESS THAN ONE
 FULL STORY BELOW THE UPPER LEVEL.
 WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM
 DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT
 THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE
 ALARMS IN THE INDIVIDUAL UNIT. THE ALARM SHALL BE
 CLEARLY AUDIBLE IN ALL BEDROOMS OVER BACKGROUND NOISE
 LEVELS WITH ALL INTERVENING DOORS CLOSED.
  
 5} 106.1.3 RESERVED. QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.***LABEL THE
 ROOMS, DECLARE THE SCALE SO SPACING REQUIREMENTS OF 210
 NEC CAN BE REVIEWED.
  
 AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-04-09 Cont ID  
Sent By mawillia Date 2009-04-09 Time 12:58 Rev Time 0.00
Received By mawillia Date 2009-04-09 Time 12:48 Sent To E
Notes
2009-04-09 12:51:47*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; SINGLE PLAN SHEET A.101 WAS STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-03-17 Cont ID  
Sent By mwennerg Date 2009-03-17 Time 13:08 Rev Time 0.00
Received By mwennerg Date 2009-03-17 Time 13:08 Sent To  
Notes
2009-03-17 13:19:55***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2006 EFFECTIVE
 SINCE DECEMBER 31, 2008. FAC 69A-60.004
  
 2) PLEASE SHOW THE REQUIRED SMOKE ALARMS THAT ARE TO BE
 IN ACCORDANCE WITH 101, SEC. 31.3.4.5.
  
 3) PLEASE INDICATE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
 4) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFCIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. FBC 106.1.1.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-07 Cont ID  
Sent By adarroug Date 2009-04-07 Time 16:22 Rev Time 0.00
Received By adarroug Date 2009-04-07 Time 16:22 Sent To  
Notes
2009-04-07 16:23:56TO "B1"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-25 Cont ID  
Sent By rregueir Date 2009-03-25 Time 19:58 Rev Time 0.00
Received By rregueir Date 2009-03-05 Time 11:04 Sent To PC
Notes
2009-03-05 11:09:56TO "BOB"#5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2009-04-08 Cont ID  
Sent By hmoser Date 2009-04-08 Time 16:00 Rev Time 0.00
Received By hmoser Date 2009-04-08 Time 16:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-03-25 Cont ID  
Sent By rregueir Date 2009-03-25 Time 19:55 Rev Time 0.00
Received By rregueir Date 2009-03-25 Time 19:51 Sent To PC
Notes
2009-03-25 19:55:41REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO INFORMATION WAS PROVIDED REGARDING CHANGES TO THE
 EXISTING HVAC SYSTEM. PROVIDE DETAILED DRAWING SHOWING
 ANY CHANGES BEING MADE TO ACCOMODATE THE PROPOSED
 ALTERATION OF THESE SPACES IN ACCORDANCE WITH FBC-B
 106.1.1.
  
 2. SHOW HOW BALANCED RETURN IS TO BE ACHIEVED IN THE
 NEWLY CREATED ROOMS IN ACCORDANCE WITH FBC-M 601.4.
  
 3. THIS APPEARS TO BE A LEVEL 2 ALTERATION AS DEFINED
 IN THE FBC-EB CHAPTER 2. SHOW COMPLIANCE WITH THE
 VENTILATION REQUIREMENTS FOR ALL RECONFIGURED SPACES IN
 ACCORDANCE WITH FBC-EB 709.1 AND FBC-M SECTION 402 OR
 SECTION 403.
  
 4. SEE FBC-B 106.1.3 FOR REQUIREMENTS RELATED TO
 QUALITY OF BUILDING PLANS SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2009-03-17 Cont ID  
Sent By kdfreema Date 2009-03-17 Time 08:20 Rev Time 0.00
Received By kdfreema Date 2009-03-17 Time 08:20 Sent To  
Notes
***NONE***