Plan Review Details - Permit 09020366
Plan Review Stops For Permit 09020366
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-07-16 Cont ID  
Sent By shill Date 2009-07-16 Time 20:18 Rev Time 0.00
Received By shill Date 2009-07-16 Time 20:18 Sent To  
Notes
2009-07-16 20:19:18REVISION 7/10/09
 A1.01, A5.01, S1.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-05-08 Cont ID  
Sent By shill Date 2009-05-08 Time 09:23 Rev Time  
Received By shill Date 2009-05-07 Time 15:48 Sent To  
Notes
2009-05-07 16:27:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IT IS NOT CLEAR HOW THIS DETAIL "SUPPORT SPACER"
 CORRELATES WITH THE PLAN. THIS IS LABELED SECTION A1,
 NO A1 ON THE PLAN, SO IS THIS SUPPLEMENTARY INFORMATION
 OR DOES IT REPLACE ANOTHER DETAIL? PLEASE INCORPORATE
 THIS DETAIL INTO THE PLAN IF IT SUPERSEDES ANOTHER
 DETAIL (OR OTHER DETAILS).
  
 2. DETAIL PROVIDED SPECS "BRACKETS"; PLEASE PROVIDE A
 BASIC DESCRIPTION OF BRACKET. A DRAWING OF THE Z TYPE
 BRACKET WAS PROVIDED BUT NO INFORMATION REGARDING
 THICKNESS OR MATERIAL, ONLY DESCRIBED AS "BRACKETS
 SUPPLIED W/CHARGER," FBC16.
  
 3. SECTIONS TYPICALLY CORRELATE WITH A PLAN. CONCRETE
 IS SHOWN, APPEARS TO BE A PLAN VIEW AND ELEVATION, BUT
 NOT MARKED AS SUCH (BOTH VIEWS LABELED TOGETHER AS
 SECTION A1). SOME OF THE DETAILS ON S1 ARE FOR WOOD
 SUBSTRATE, STEEL SUBSTRATE. DOES THIS APPLY TO CONCRETE
 SUBSTRATE ONLY? WHY ISN'T WOULDN'T THIS BE B1-1? SEE
 SHEET S1, PLAN SPECIFIES SOME (BUT NOT ALL) OF THE
 DETAILS ON THAT SHEET. FOR INSTANCE, SECTION A1.1 DOES
 NOT APPEAR ON THE KEY PLAN. DOES THAT MEAN THAT IT'S
 NOT BEING USED? ALSO, SHOULDN'T THE KEY PLAN BE REVISED
 TO INCORPORATE THE NEW DETAIL TO SHOW WHERE THIS DETAIL
 WILL BE IMPLEMENTED? FBC16, FBC*106.
  
 4. DOCUMENTS PREPARED BY AN ENGINEER ARE TO INCLUDE ALL
 TITLE BLOCK INFORMATION REQUIRED FAC61G15-23.002
 (WWW.FBPE.ORG, LAWS & RULES).
  
 5. CALCULATIONS WERE SUPPLIED (AT TIME OF ORIGINAL
 PERMIT). IT APPEARS THAT CALCULATIONS WERE FOR WIND
 COLUMNS ONLY. PLEASE CONFIRM THAT THIS CHANGE OF
 SPECIFICATION DOES NOT AFFECT THE CALCULATIONS. IF THEY
 DO, PLEASE SUBMIT NEW CALCULATIONS FOR OUR RECORDS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-05-05 Cont ID  
Sent By shill Date 2009-05-05 Time 08:25 Rev Time 0.00
Received By shill Date 2009-05-05 Time 08:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-25 Cont ID  
Sent By shill Date 2009-03-25 Time 10:46 Rev Time 0.00
Received By shill Date 2009-03-25 Time 10:46 Sent To  
Notes
2009-03-25 10:57:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. DECLARE LEVEL OF ALTERATION, FBC EB 301.5.
  
 2. A5.01, PLEASE INCLUDE EPJ ON THE ARCHIECTURAL
 ABBREVIATION LIST. SOME CHARGERS ARE LABELED "BATTERY
 CHARGERS," SOME DETAILS USE THE PHRASE "EPJ CHARGERS,"
 AND ALSO "EPJ BATTERY CHARGERS." IT IS NOT CLEAR IF EPJ
 IS A BRAND, OR A TYPE. FBC*106.
  
 3. WILL THE FIRE SPRINKLER SYSTEM BE AFFECTED WITH THIS
 IMPROVEMENT? FIRE SPRINKLER PLANS REQUIRED IF SPRINKLER
 ALTERATION IS PROPOSED, FS553.79(2),
 FBC*106.3.5.1.1(5).
  
 4. S1, PLEASE INCLUDE MBS AND PPT IN ABBREVIATION
 LEGEND.
  
 5. S1, SEE FAC61G15-23.002; PRINTED NAME AND LICENSE
 NUMBER OF THE PERSON SEALING THE DOCUMENT TO BE
 INCLUDED IN THE TITLE BLOCK, AND CERTIFICATE OF
 AUTHORIZATION (ENGINEERING LICENSE NUMBER FOR THE
 ENGINEERING FIRM) NUMBER INCLUDED IN THE TITLE BLOCK.
 THE FAC REQUIREMENTS CAN BE VIEWED ONLINE AT
 WWW.FBPE.ORG, LAWS AND RULES.
  
 IF THIS APPLICATION HAS A "PASS" STATUS FROM ALL OTHER
 TRADES, PLEASE CONTACT ME. THE ABOVE ITEMS CAN BE
 PROVISO ITEMS (PERMIT ISSUED WITH PROVISO TO ADDRESS
 ABOVE ITEMS WITH REVISION).
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-03-10 Cont ID  
Sent By btrobaug Date 2009-03-10 Time 15:16 Rev Time 0.00
Received By btrobaug Date 2009-03-10 Time 14:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-04-21 Cont ID  
Sent By mawillia Date 2009-04-21 Time 15:28 Rev Time 0.00
Received By mawillia Date 2009-04-21 Time 15:03 Sent To  
Notes
2009-04-21 15:28:13*****APPROVED*****
  
  
 AFTER VIEWING FIRE SPRINKLER AND FIRE ALARM REFERENCE
 SHEETS, THE COMMENT FROM THE PREVIOUS FIRE PLAN REVIEW
 HAS BEEN ADDRESSED; PLAN SHEET A1.02 WAS STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-02 Cont ID  
Sent By mawillia Date 2009-04-02 Time 12:18 Rev Time 0.00
Received By mawillia Date 2009-04-02 Time 12:04 Sent To  
Notes
2009-04-02 12:17:54*****UNSAT*****
  
  
 !. PROVIDE LOCATION OF THE FIRE EXTINGUISHERS, FIRE
 ALARM DEVICES, SPRINKLER HEAD, AND EXIT DOORS IN THIS
 PROJECT SCOPE AREA.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-07-14 Cont ID  
Sent By dpalmer Date 2009-07-14 Time 14:34 Rev Time 0.00
Received By dpalmer Date 2009-07-14 Time 14:34 Sent To B
Notes
2009-07-14 14:34:34TO SH'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-05-05 Cont ID  
Sent By dpalmer Date 2009-05-05 Time 15:40 Rev Time 0.00
Received By dpalmer Date 2009-05-05 Time 15:40 Sent To B
Notes
2009-05-05 15:40:21TO SH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-17 Cont ID  
Sent By swurafti Date 2009-04-17 Time 11:59 Rev Time 0.00
Received By swurafti Date 2009-04-17 Time 11:59 Sent To  
Notes
2009-04-17 12:04:25TO "C3"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-02 Cont ID  
Sent By mawillia Date 2009-04-02 Time 12:24 Rev Time 0.00
Received By mawillia Date 2009-02-20 Time 09:43 Sent To  
Notes
2009-02-20 09:47:17TO "COMM" BD#19

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-03-27 Cont ID  
Sent By rregueir Date 2009-03-27 Time 14:41 Rev Time 0.00
Received By rregueir Date 2009-03-27 Time 14:41 Sent To  
Notes
2009-03-27 14:43:05BATTERY CHARGING STATIONS ARE FOR FORKLIFTS AND
 ELECTRIC PALLET JACKS. THE BATTERIES BEING CHARGED STAY
 MOUNTED ON THE MACHINES (NOT STATIONARY) THEREFORE
 ADDITIONAL VENTILATION IS NOT REQUIRED.

Review Stop Z ZONING
Rev No 1 Status N Date 2009-02-26 Cont ID  
Sent By kdfreema Date 2009-02-26 Time 13:50 Rev Time 0.00
Received By kdfreema Date 2009-02-26 Time 13:50 Sent To  
Notes
***NONE***