| Plan Review Stops For Permit 09020344 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-06-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-06-11 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-06-11 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2009-06-11 09:48:56 | NOTE: THIS BUILDING IS OF TYPE I CONSTRUCTION. | | | THEREFORE, ONLY NONCOMBUSTIBLE MATERIALS CAN BE USED | | | FOR WALL AND CEILING CONSTRUCTION EXCEPT AS ALLOWED BY | | | FBC SECTION 603. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-05-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-05-12 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-05-12 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2009-05-12 14:24:27 | 2004 FBC W/2007 REVISIONS | | | | | | 1) PLANS FROM A FLORIDA LICENSED ENGINEER SUBMITTED FOR | | | PUBLIC RECORD ARE REQUIRED TO BE SIGNED, SEALED AND | | | DATED BY THE ENGINEER. FS 471 AND FAC 61G15-23.002 | | | | | | 2) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS. 2004 | | | FBC | | | | | | 3) SPECIFY THE SUPERIMPOSED DEAD LOAD IN PSF OF THE NEW | | | MARBLE FLOORING SYSTEM. FBC 1606.1 | | | | | | 4) THIS PERMIT WAS APPLIED FOR ON FEBURARY 17, 2009. | | | THEREFORE, THE CODE THAT APPLIES IS THE 2004 FBC. | | | PLEASE CORRECT THE PLANS. | | | | | | NOTE: THIS BUILDING IS OF TYPE I CONSTRUCTION. | | | THEREFORE, ONLY NONCOMBUSTIBLE MATERIALS CAN BE USED | | | FOR WALL AND CEILING CONSTRUCTION EXCEPT AS ALLOWED BY | | | FBC SECTION 603. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-02-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-02-20 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-02-20 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2009-02-20 10:52:19 | 2004 FBC W/2007 REVISIONS | | | INTERIOR RENOVATIONS | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | | BE REQUIRED. FS 713 | | | | | | 2) SUBMIT TWO COPIES OF SIGNED AND SEALED DRAWINGS FROM | | | A FLORIDA LICENSED ARCHITECT OR ENGINEER. FS 471 AND | | | 481. PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN. | | | PLANS ARE TO BE DIMENSIONED AND DRAWN TO MINIMUM 1/8" | | | SCALE. PROVIDE WALL ELEVATIONS, WALL SECTIONS, FRAMING | | | DETAILS AND STRUCTURAL ATTACHMENT DETAILS.FBC 106* CITY | | | AMENDMENTS AND FBC 1603 | | | | | | 3) SPECIFY THE APPLICABLE CODES AND LEVEL OF ALTERATION | | | ON THE PLANS. 2004 FBC AND 2004 FBC EXISTING BUILDING | | | | | | 4) SPECIFY THE SUPERIMPOSED DEAD LOAD IN PSF OF THE NEW | | | MARBLE FLOORING SYSTEM. FBC 1606.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2009-07-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-07-20 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-07-20 |
Time |
15:10 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-06-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-06-11 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-06-11 |
Time |
15:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2009-04-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-04-28 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-04-28 |
Time |
15:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-06-12 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-06-12 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-06-12 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2009-06-12 13:51:29 | SENT TO L. MARTINEZ FOR PROCESSING. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2009-05-01 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-05-01 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-05-01 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2009-05-01 11:53:17 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 1. THE SUBMITTED DRAWINGS SHALL BE SIGNED AND SEALED BY | | | A FLORIDA LICENSED ARCHITECT OR ENGINEER. THIS COMMENT | | | WAS ONE OF THE TWO TAKEN FROM THE BUILDING EXAMINER'S | | | PREVIOUS REVIEW. | | | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3. THE 2007 FLORIDA FIRE PREVENTION CODE (BASED ON NFPA | | | 101, LIFE SAFETY CODE, 2006 EDITION AND NFPA 1, UNIFORM | | | FIRE CODE, 2006 EDITION) SHALL BE REFERENCED. | | | | | | 4. THE REMOVAL OF EXISTING AND (OR) THE STOCKING OF NEW | | | BUILDING MATERIALS/SUPPLIES SHALL NOT HINDER OR | | | INTERFERE WITH ACCESS TO OR EGRESS FROM OTHER UNITS ON | | | THE FLOOR, THE EXIT CORRIDOR OF THE FLOOR, OR ANY OTHER | | | FLOOR IN THE BUILDING. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH COMMENT HAS BEEN ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-02-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-02-23 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-02-23 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2009-02-23 13:58:52 | *****DENIED***** | | | | | | | | | 1. PLEASE ADDRESS THE BUILDING EXAMINER'S FIRST TWO | | | COMMENTS. | | | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3. THE 2007 FLORIDA FIRE PREVENTION CODE (BASED ON NFPA | | | 101, LIFE SAFETY CODE, 2006 EDITION AND NFPA 1, UNIFORM | | | FIRE CODE, 2006 EDITION) SHALL BE REFERENCED. | | | | | | 4. THE REMOVAL OF EXISTING AND (OR) THE STOCKING OF NEW | | | BUILDING MATERIALS/SUPPLIES SHALL NOT HINDER OR | | | INTERFERE WITH ACCESS TO OR EGRESS FROM OTHER UNITS ON | | | THE FLOOR, THE EXIT CORRIDOR OF THE FLOOR, OR ANY OTHER | | | FLOOR IN THE BUILDING. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH COMMENT HAS BEEN ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-07-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-14 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-14 |
Time |
13:59 |
Sent To |
E |
|
| Notes |
| 2009-07-14 13:59:20 | TO BT'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-06-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-06-02 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-06-02 |
Time |
11:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-04-17 |
|
|
Cont ID |
|
| Sent By |
swurafti |
Date |
2009-04-17 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
swurafti |
Date |
2009-04-17 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2009-04-17 11:25:13 | TO "BOB" 1 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-02-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-02-23 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-02-18 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2009-02-18 10:44:05 | TO "BOB"#4 |
|
|