Plan Review Details - Permit 09020319
Plan Review Stops For Permit 09020319
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-03-03 Cont ID  
Sent By jnguyen Date 2009-03-03 Time 09:24 Rev Time 0.00
Received By JNGUYEN Date 2009-03-03 Time 12:51 Sent To  
Notes
2009-03-03 09:24:06FOR PERMIT# 09020319 (EMERGENCY ROOM PROJECT), I HAVE
 TAKEN A LOOK AT THE SITE PLANS FROM COMMUNITY BOARD #59
 & TALKED TO THE CONTRACTOR, NAT HEALY TO VERIFY THE
 RIGHT ADDRESS. THE AREA OF ALTERATION SHOWS IT TAKING
 PLACE ON THE FRONT HALF OF COLUMBIA HOSPITAL & THE
 ADDRESS IS ALREADY CORRECT. ABOUT A MONTH AGO, I WENT
 OUT ON SITE TO THE PHYSICAL LOCATION TO VERIFY THE
 ADDRESSES BECAUSE WE HAD THEM WRONG IN THIS AREA FOR
 OUR DATABASES INITIALLY (I.E., INCORRECTLY HAD THE
 COLUMBIA HOSPITAL AS 4631 N CONGRESS AVE). I WORKED
 WITH ADRIANNA & ANGASH TO FIX THE CORRESPONDING RECORDS
 IN OUR GIS & COMMUNITYPLUS DATABASES. PERMIT# 09020319
 DOES INDEED TAKE PLACE AT COLUMBIA HOSPITAL ON PCN#
 74434306000001030 WITH THE CORRECT PRIMARY ADDRESS OF
 2201 45TH ST. ON THE OTHER HAND, 4631 N CONGRESS AVE ON
 PCN# 74434306000001210 APPLIES TO THE BUILDING TO THE
 SOUTHEAST (COLUMBIA MEDICAL ARTS PREMIER RESEARCH
 INSTITUTE). THE SITE PLANS HAVE BEEN RETURNED TO THE
 BOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-08-22 Cont ID  
Sent By jwitmer Date 2009-08-22 Time 12:58 Rev Time 1.50
Received By jwitmer Date 2009-08-22 Time 11:30 Sent To  
Notes
2009-08-22 12:59:30ARCHITECTURAL SHEETS REVISION# 3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-07-07 Cont ID  
Sent By jwitmer Date 2009-07-07 Time 10:30 Rev Time 1.00
Received By jwitmer Date 2009-07-07 Time 09:30 Sent To  
Notes
2009-07-07 10:20:05 
  
 PERMIT # 09020319
 2201 45TH STREET
 COLUMBIA HOSPITAL/ 1ST FLOOR EMERGENCY DEPART
 ALTERATIONS
 2007 FBC
 07/07/09
  
 BUILDING PROVISO:
 SHEET A3.51
 1)ALTERNATE EFIS SYSTEM 08-0709.05 THIS PRODUCT
 APPROVAL WAS TESTED WITH
 PLYWOOD BACKING PROVIDING HIGHER PRESSURES. TYPE I,
 TYPE II BUILDINGS ARE NOT ALLOWED
 TO HAVE PLYWOOD SHEATHING UNLESS FIRE RESISTANT TREATED
 PLYWOOD WAS INSTALLED.SECTION
 603.1(1)(1.2). SHEET A3.51INDICATES 1/2 INCH SHEATHING
 IS TO BE INSTALLED OR DENSEGLASS GOLD.
 THIS PARTICULAR NOA WAS TESTED USING A 5/8 INCH
 EXTERIOR GRADE PLYWOOD, NOT 1/2 INCH.
  
 08-0709.05 ALTERNATE EFIS NOA TO BE SUBMITTED BEFORE
 INSPECTION.
  
 07-0108.01 EFIS NOA TO BE SUBMITTED BEFORE INSPECTION.
  
  
 2) WINDOW NOA 07-0817.04 TO BE SUBMITTED BEFORE
 INSPECTION.
  
 3) LINTEL PRODUCT APPROVAL TO BE SUBMITTED BEFORE
 INSPECTION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR
 FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE PUBLIC
 RECORD, AVAILABLE TO THE PUBLIC UPON
 REQUEST. YOUR E-MAIL COMMUNICATIONS ARE THEREFORE
 SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-11 Cont ID  
Sent By jwitmer Date 2009-06-11 Time 10:04 Rev Time 10.00
Received By jwitmer Date 2009-06-10 Time 10:14 Sent To  
Notes
2009-06-11 10:29:14PERMIT # 09020319
 2201 45TH STREET
 COLUMBIA HOSPITAL/ 1ST FLOOR EMERGENCY DEPART
 ALTERATIONS
 2007 FBC
  
 BUILDING PROVISO:
 1) PLEASE SUBMIT NEW PRODUCT APPROVAL FOR REVIEW THIS
 PARTICULAR PRODUCT WAS TESTED WITH
 PLYWOOD BACKING PROVIDING HIGHER PRESSURES. TYPE I,
 TYPE II BUILDINGS ARE NOT ALLOWED
 TO HAVE PLYWOOD SHEATHING UNLESS FIRE RESISTANT TREATED
 PLYWOOD WAS INSTALLED.SECTION
 603.1(1)(1.2). PLANS A4.55 DO NOT PROVIDE WHAT TYPE OF
 SHEATHING IS INSTALLED ON THE
 EXTERIOR OF THE BUILDING. EITHER PROVIDE TYPE OF
 EXISTING SHEATHING OR PROVIDE NEW PRODUCT
 APPROVAL WITH AN APPROVED SHEATHING BEFORE INSPECTIONS.
  
 2) WINDOW NOA 07-0817.04 TO BE SUBMITTED BEFORE
 INSPECTION.
  
 3) LINTEL PRODUCT APPROVAL TO BE SUBMITTED BEFORE
 INSPECTION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR
 FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE PUBLIC
 RECORD, AVAILABLE TO THE PUBLIC UPON
 REQUEST. YOUR E-MAIL COMMUNICATIONS ARE THEREFORE
 SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-16 Cont ID  
Sent By shill Date 2009-03-16 Time 15:50 Rev Time 0.00
Received By shill Date 2009-03-16 Time 15:50 Sent To  
Notes
2009-03-16 15:50:54****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THIS IS A PLAN CHECK ONLY. THIS REVIEW WILL REMAIN
 IN FAILED STATUS UNTIL PERMIT APPLICATION SUBMITTED.
  
 2. GOVERNING CODE EFFECTIVE MARCH 1, 2009 IS FBC 2007
 WITH 2009 SUPPLEMENTS, FS553. PLEASE REVISE.
  
 3. PLEASE INDICATE WHICH METHOD OF COMPLIANCE UNDER
 WHICH THIS PROPOSED ALTERATION HAS BEEN DESIGNED, FBC
 EB 101.5.
  
 4. FBC TABLE 601, SHEET A0.00, BUILDING TYPE 1A
 DECLARED, I2 OCCUPANCY. 3 HOUR FIRE RESISTANCE REQUIRED
 FOR TYPE 1A, I2 OCCUPANCY; 2 HOUR SPECIFIED ON PLAN
 (PLEASE NOTE THAT THE FOOTNOTE RE: 1 HOUR REDUCTION IS
 NOT APPLICABLE IN THIS CASE).
  
 5. REVISE BUILDING INFORMATION TO INCLUDE BUILDING
 HEIGHT, FBC 6.
  
 6. A0.0, UL ASSEMBLY DETAILS, SPECIFY FLOOR AND CEILING
 RUNNER TRACKS AND FASTENING, FBC706.5.
  
 7. PROVIDE A HEAD OF WALL DETAIL, FBC706.5.
  
 8. SHEET A0.01 IS NOT SEALED AND DATED, FS481. WHEN
 SUBMITTING FOR PERMIT, PLEASE CONFIRM THAT ALL SHEETS
 ARE SIGNED, SEALED, AND DATED.
  
 9. ARCHITECT???S TITLE BLOCK TO BE IN COMPLIANCE WITH
 FAC61G1-16.004.
  
 10. FBC1004.1.1, SHEET A0.10, PLEASE CLARIFY USE OF
 TREATMENT AREAS. OCCUPANT LOAD WAS DETERMINED BASED ON
 240SF PER OCCUPANT; THIS IS THE MINIMUM FOR INPATIENT
 TREATMENT AREAS. ISN???T AN EMERGENCY ROOM AREA OFTEN
 AN OUTPATIENT TREATMENT AREA? PLEASE CLARIFY USE OF
 SPACE AND RATIONALE FOR USE OF 240SF FOR OCCUPANT LOAD.
 TABLE 1004.1.1 REQUIRES 100SF FOR OUTPATIENT.
  
 11. FBC407.3, CORRIDOR WALLS SHALL BE CONSTRUCTED AS
 SMOKE PARTITIONS IN ACCORDANCE WITH FBC710. CORRIDORS
 1-101, 1-105, ETC. DO NOT NOTE SMOKE PARTITION
 REQUIRED. THE WALL BETWEEN 1 208 AND CORRIDOR E 103 IS
 NOT NOTED AS A SMOKE PARTITION. PLEASE CLARIFY.
  
 12. FBC407.2, EXAM 9 THROUGH 11 ARE OPEN TO CORRIDOR
 1-105; IT IS NOT CLEAR WHICH EXCEPTION APPLIES, SEE
 FBC407.2.1(1).
  
 13. MANEUVERING CLEARANCE, PULL SIDE FBC FIGURE 11-25
 REQUIRED FOR ALL DOORS REQUIRED TO BE ACCESSIBLE.
 PLEASE NOTE DIMENSION TO SHOW COMPLIANCE:
  
 1053, 1055, 1020, 1022
 DOOR FROM ROOM 1-217 TO LAB, 1044, NOTED AS EXISTING
  
 PLEASE CHECK ALL AND CONFIRM COMPLIANCE FOR ALL DOORS
 IN THE RENOVATED AREA FBC11-4.1.6(1)(B). ONLY DOORS
 WHICH APPEAR NONCOMPLIANT ARE REFERENCED BUT OTHER
 DOORS MAY BE AFFECTED.
  
 14. FBC407.2, CORRIDORS SHALL BE CONTINUOUS TO EXIT
 UNLESS ONE OF THE EXCEPTIONS NOTED.
  
 15. A1.02, A NOTE STATES THAT TOILET ROOM WALLS WILL BE
 UPGRADED TO 2HR SMOKE/FIRE PARTITIONS. IT IS NOT CLEAR
 WHY THE SMOKE PARTITION IS NOT ALONG THE CORRIDOR WALL
 FBC407.2; PLEASE CLARIFY DESIGN INTENT.
  
 16. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR COMPONENTS & CLADDING; EIFS, WINDOWS.
  
 17. A6 01 WINDOW A STATES THAT THIS WINDOW IS EXISTING
 (WITH AN EXPIRED NOA REFERENCE), SHEET A3.51 STATES
 THIS IS A NEW WINDOW, A1.02 STATES THIS IS NEW
 EXISTING. PLEASE CLARIFY SCOPE.
  
 18. A1.02, I AM UNABLE TO LOCATE COILING SECURITY DOORS
 1045 THROUGH 1050. MY APOLOGIES; PLEASE ADVISE.
  
 19. FOR FIRE RATED WALLS, PLEASE NOTE METHOD OF
 COMPLIANCE FBC703.3. THE DETAILS DO NOT REFER TO AN
 ASSEMBLY NUMBER OR TIME FOR BUILDING ELEMENTS.
  
 20. PLEASE NOTE CONCEALED SPACE SIGNAGE REQUIREMENT ON
 PLAN, FBC 419.3.9.7.
  
 21. FBC407.2.2, NURSE???S AREA (AND SIMILAR SPACES) TO
 BE CONSTRUCTED AS REQUIRED FOR CORRIDORS.
  
 22. FBC419.1.1, PLEASE SHOW COMPLIANCE WITH STATE
 REVIEW REQUIREMENTS (LETTER OR STAMPED PLAN). THIS ITEM
 MAY BE DONE PRIOR TO FIRST INSPECTION AS A REVISION, AT
 CONTRACTOR???S/OWNER???S RISK.
  
 23. FBC11 4.13.7, DOORS AT ROOM 1 106, RECEPT/TRIAGE,
 REQUIREMENT FOR DOORS IN A SERIES.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-08-21 Cont ID  
Sent By dpalmer Date 2009-08-21 Time 20:51 Rev Time 0.00
Received By dpalmer Date 2009-08-21 Time 19:15 Sent To  
Notes
2009-08-21 20:53:52STAMPED ELECTRICAL SHEETS. IF OK WITH FIRE REVIEW ONE
 SET TO BE RETAINED FOR FILE.
 FILED COORDINATION STUDY
  
 ** SEPARATE PERMITS REQUIRED FOR LOW VOLTAGE SYSTEMS
 SUCH AS CATV, PHONE, CAMERAS.
 THE ABOVE MAY REFERENCE BACK TO THIS PLAN FOR TURN
 AROUND PERMITS.
  
 ** FIRE ALARM, ANY ACCESS CONTROLS, ARE UNDER SEPARATE
 PLANS AND PERMIT APPLICATIONS.
2009-08-21 20:15:18*** REVIEW SKIPPED REVIEW #4 STOP AS NOTES WERE PLACED
 IN ERROR. STOP HAD TO BE DELETED. THIS IS ACTUALLY THE
 FORTH REVIEW STOP.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-07-07 Cont ID  
Sent By dpalmer Date 2009-07-07 Time 11:51 Rev Time 0.00
Received By dpalmer Date 2009-07-07 Time 11:51 Sent To  
Notes
2009-07-07 11:54:242ND SET OF CALCS SUBMITTED.
  
 SECTION TITLE II OF THE SELECTIVE COORDINATION STUDY
 SHEETS DATED FROM APRIL 2009 ARE STAPLED TOGETHER AS
 N/A. ONLY REPORT FOR NORMAL AND EMERGENCY DATED 6/2009
 ARE PART OF THE CURRENT STUDY.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-06-11 Cont ID  
Sent By dpalmer Date 2009-06-11 Time 16:24 Rev Time 0.00
Received By dpalmer Date 2009-06-11 Time 16:24 Sent To  
Notes
2009-06-11 16:24:44 
 ** DENIED 2ND REVIEW**
  
 ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION.
  
 ** THERE ARE STILL COMMENTS FROM PREVIOUS REVIEW WHICH
 ARE IN NEED OF ADDRESSING. THERE ARE ALSO SEVERAL NEW
 COMMENTS BASED ON INFORMATION ONLY NOW SUBMITTED FOR
 REVIEW.
  
  
  
 1) NOTE: PLEASE SEE FBC CHAPTER 13 2007 EDITION WITH
 2009 GLITCH AMENDMENTS. THIS CHAPTER WAS COMPLETELY
 REVISED FROM THE FIRST PRINTING OF THE 2007 FBC. THERE
 ARE SUBSTANTIAL CHANGES WHICH WILL AFFECT THIS PROJECT.
  
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.AB.5. THIS IS NOT A WHOLE BUILDING AS DEFINED IN
 SECTION 202. THE METHOD WHICH MUST BE USED IS METHOD
 *B* FOR SPACE BY SPACE. THE SUBMITTED CALCULATIONS AND
 THE INPUT DATA REPORT IS NOT CODE COMPLIANCE.
 THIS REQUIRES THE SPACES TO BE LISTED AND CHOSEN FOR
 THE USE AND LOCATION. THERE ARE NUMEROUS EXAMPLES WHERE
 THE SPACE DESIGNATION GIVEN WAS FOR AN EMERGENCY ROOM
 WHEN THE SPACE OR LOCATION IS SOMETHING OTHER LIKE A
 JANITOR CLOSET, EXAM ROOM, NURSE STATION, TOILET ETC.
 THE DESIGNATION AND ALLOWANCE IS BASED ON THE LOCATION
 AND USE. THE TOILET MAY NO BE CALLED AN EMERGENCY ROOM
 TO USE THE ALLOWANCE OF 2.7 WHEN THE CODE HAS AN
 ALLOWANCE OF .09. ANOTHER EXAMPLE WOULD BE THE CORRIDOR
 WHICH IS SHOWN FOR A 2.7 ALLOWANCE AND WHEN HOSPITAL
 CORRIDOR HAS AN ALLOWANCE OF 1.0.
 THERE ARE MANY DESIGNATIONS WHICH MAY NOT BE USED.
 PLEASE ALSO CHECK THE CONTROL TYPE. THERE ARE SEVERAL
 LISTED AS * EXCEPTION FOR AREA USED AS A WHOLE*. PLEASE
 PROVIDE WHERE IN THE CODE THESE AREAS ARE LISTED.
  
  
 2) NOTE: ALL WORKING CLEARANCE SHALL MEET 110.26. BASED
 ON THE NURSE STATION ELEVATION ALONE THERE ARE SEVERAL
 ITEMS WHICH REQUIRE CLEARANCE HOWEVER DO NOT MEET THE
 SECTIONS.
 THE RESPONSE MENTIONS THE EXCEPTION IN 110.26. PLEASE
 EXPLAIN HOW THIS MEETS THE EXCEPTION. IT DOES NOT MEET
 THE EXCEPTION. IT IS CLEAR AN ELECTRICIAN COULD VERY
 WELL NEED TO CHECK FOR VOLTAGE, CIRCUIT TRACING AND
 NUMEROUS OTHER TASKS IN WHICH POWER WOULD BE PRESENT
 FOR TROUBLE SHOOTING. THESE PANELS MUST MEET
 CLEARANCES. THE EXCEPTION MAY NOT BE USED.
  
 3) NOTE: PLEASE SEE 240.12,700.27, 701.18. PLEASE
 PROVIDE COMPLETE SELECTIVE COORDINATION FOR SYSTEMS
 INCLUDING NEW EQUIPMENT BEING INSTALLED. THIS STUDY
 NEEDS TO INCLUDE TIME CURVES. SOME INFORMATION SHOWN
 AND SUBMITTED HOWEVER BASED ON E7.01 NOT MATCHING RISER
 COMPLETELY AND NOT TIME CURVES SUBMITTED IT IS NOT
 KNOWN IF MINIMUM CODE COMPLIANCE IS MET. SEE COMMENT #8
 ALSO.
 ** THIS IS A REPEATED COMMENT. THE RESPONSE MENTIONS TO
 SEE THE ATTACHED STUDY WHICH WAS SUBMITTED TO ACHA.
 THERE ARE NO STAMPS ON THE SUBMITTED DOCUMENTATION. IT
 IS ALSO NOT CLEAR HOW THE STUDY SUBMITTED ALONG WITH
 THE TIME CURVES WOULD PASS THE REVIEW FROM ACHA WHEN
 THERE ARE INCONSISTENCIES FROM THE RISER AND PLANS.
 ONE EXAMPLE OF THIS IS THE FACT THE CONDUCTORS ON STUDY
 RISER TO BOTH TRANSFORMERS T-EDCRL AND T-EDNL ARE 1/0
 ON SELECTIVE COORDINATION RISER AND #1 ON THE LISTED
 FEEDERS. SEE NOTES BELOW ALSO FOR THE COORDINATION OF
 ALL RISER EQUIPMENT.
 PLEASE SEE THE TIME CURVES SUBMITTED ARE INDICATING A
 VERY CLOSE AND ALSO OVER-LAPPING ON SEVERAL ITEMS.
 PLEASE SUBMIT THE REVIEWED AND STAMPED SETS FROM ACHA.
  
 4) NOTE: PLEASE SEE 517.17. PLEASE PROVIDE COMPLIANCE
 BY SHOWING THE PROTECTION OF SYSTEM. THE RESPONSE
 MENTIONS THIS IS REVISED ON RISER HOWEVER THE RISER
 ONLY INDICATES TWO ITEMS WITH THE GFCI PROTECTION.
 PLEASE SEE THE SECTION OF THE CODE GIVEN ABOVE WHICH
 REQUIRES THE PROTECTION OF OTHER LOCATIONS.
 ** THE INTENT IS NOT TO HAVE A SINGLE SITUATION CAUSE A
 SHUT DOWN OF A MAIN. IT WOULD BE BETTER TO LOSE ONE
 PANEL THAN THE ENTIRE RISER FEED. THE FOLLOWING IS THE
 EXACT WORDING TAKEN FROM THE NEC.
  
 ****WHEREVER GROUND-FAULT PROTECTION OF EQUIPMENT IS
 APPLIED TO THE SERVICE PROVIDING POWER TO A HEALTH CARE
 FACILITY, WHETHER BY DESIGN OR BY REASON OF THE
 REQUIREMENTS OF 215.10 OR 230.95, AN ADDITIONAL LEVEL
 OF GROUND-FAULT PROTECTION IS REQUIRED DOWNSTREAM.
 UNDER THIS RULE, GROUND-FAULT PROTECTION MUST BE
 APPLIED TO EVERY FEEDER, AND ADDITIONAL GROUND-FAULT
 PROTECTIVE DEVICES MAY BE APPLIED FARTHER DOWNSTREAM AT
 THE OPTION OF THE GOVERNING BODY OF THE HEALTH CARE
 FACILITY. UNLIKE THE REQUIREMENTS OF 215.10 AND 230.95
 WHERE MANDATORY GFPE PROTECTION IS PREDICATED ON THE
 RATING OF THE DISCONNECTING MEANS (1000 AMPERES OR
 MORE), THE SECOND LEVEL OF GFPE IS NOT BASED ON THE
 RATING OF THE FEEDER DISCONNECTING MEANS, BECAUSE THE
 FUNCTION OF THE SECOND LEVEL OF GFPE IS TO PROVIDE THE
 DESIRED SELECTIVITY BETWEEN THE FEEDER PROTECTIVE
 DEVICES AND THE SERVICE OR BUILDING SUPPLY PROTECTIVE
 DEVICES.
 WITH PROPER COORDINATION, THIS ADDITIONAL GROUND-FAULT
 PROTECTION IS INTENDED TO LIMIT A GROUND FAULT TO A
 SINGLE FEEDER AND THEREBY PREVENT A TOTAL POWER OUTAGE
 OF THE ENTIRE HEALTH FACILITY. COORDINATION INCLUDES
 CONSIDERATION OF THE TRIP SETTING, THE TIME SETTING,
 AND THE TIME REQUIRED FOR OPERATION (OPENING TIME) OF
 EACH LEVEL OF THE GROUND-FAULT PROTECTION SYSTEM.
 *** PLEASE PROVIDE THE INFORMATION.
  
 5) NOTE: PLEASE GO THROUGH RISER, CONDUCTORS AND ALL
 OVER CURRENT PROTECTION DEVICES. THERE ARE ITEMS WHICH
 DO NOT COORDINATE.
 215.5, 110.9, 240.4, 310.16, 240.12 ETC THESE CODE
 SECTIONS ARE GIVEN IN GENERAL AS COORDINATION OF
 CONDUCTORS, OVER CURRENT PROTECTION, PANELS ETC EFFECT
 ALL SECTIONS.
 THIS IS A REPEAT COMMENT ARE THERE ARE ITEMS STILL NOT
 PROVIDED.
 AN EXAMPLE ABOVE WAS GIVEN FOR THE DIFFERENCES IN THE
 FEEDERS TO EACH TRANSFORMER.
 ANOTHER EXAMPLE WOULD BE THE PANEL SCHEDULE FOR EDEQH
 WHICH DOES NOT LIST ANY BRANCH BREAKER FOR THE FEEDERS
 TO THE TRANSFORMER.
 **THESE ARE TWO ITEMS GIVEN AS EXAMPLES ONLY.
  
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-26 Cont ID  
Sent By dpalmer Date 2009-03-26 Time 08:53 Rev Time 0.00
Received By dpalmer Date 2009-03-26 Time 08:53 Sent To  
Notes
2009-03-26 08:54:00** DENIED REVIEW **
  
 1) NOTE: IT IS IMPORTANT TO KNOW THAT PLANS WERE ONLY
 SUBMITTED FOR PLAN REVIEW ONLY. THIS DOES NOT *LOCK* A
 PROJECT UNDER ANY SPECIFIC CODE EDITIONS UNLESS PERMIT
 APPLICATION IS MADE. AS THE PROJECT WAS ONLY SUBMITTED
 FOR PLAN REVIEW AND IS DESIGNED UNDER THE 2004 FBC AS
 OF MARCH 1, 2009 THE STATE OF FLORIDA UNDER FS 553.73
 HAS ADOPTED THE 2007 FBC WITH 2009 REVISIONS.
 PLEASE ALSO KNOW SOME OTHER CODES SUCH AS THE LIFE
 SAFETY CODE AND STATE FIRE CODE WERE ALSO REVISED PER
 FLORIDA ADMINISTRATIVE CODE 69A-60.003 AND .004 BY THE
 STATE FIRE MARSHAL.
 THE FOLLOWING CODES NEED TO BE ON PLANS. PLEASE BE SURE
 THE FOLLOWING ARE ON ELECTRICAL AS WELL. SOME CODES
 STATED ON PLANS ARE OK AND IN EFFECT. PLEASE BE SURE
 THE FOLLOWING ARE UPDATED ON ALL RELEVANT SHEETS.
  
 2007 FBC W/2009 REVISIONS.
 2006 NFPA-101
 2006 NFPA-1
 2005 NFPA-70 (ALREADY ON COVER)
 2002 NFPA-72 (ALREADY ON BOTH)
 2002 NFPA-110 ( ALREADY ON BOTH)
  
 2) NOTE: PLEASE SEE FAC 61G1-16.004 AND FLORIDA
 STATUTES 481.219 AS THE ARCHITECTURAL TITLE BLOCKS ARE
 MISSING REQUIRED INFORMATION AS WELL AS STATE REQUIRED
 LICENSING.
 MISSING PRINTED NAME OF ARCHITECT
 MISSING PRINTED LICENSE NUMBER OF ARCHITECT
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
  
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13 2007 EDITION WITH
 2009 GLITCH AMENDMENTS. THIS CHAPTER WAS COMPLETELY
 REVISED FROM THE FIRST PRINTING OF THE 2007 FBC. THERE
 ARE SUBSTANTIAL CHANGES WHICH WILL AFFECT THIS PROJECT.
  
 ** THERE ARE LOCATIONS WHICH REQUIRE AUTOMATED LIGHTING
 CONTROLS HOWEVER NOT SHOWN ON PLANS PER FBC
 13-415.AB.1,.1.1,.1.2, .1.3.
 ONE EXAMPLE ONLY IS 1-125. THIS IS ONE LOCATION ONLY
 GIVEN AS A BENEFIT. PLEASE BE AWARE THERE ARE MANY
 OTHERS.
  
 ** PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2, 13-415.AB.5, 13-415.AB.5.1, 13-415.B
  
 4) NOTE: PLEASE KNOW THAT THE LIGHTNING PROTECTION
 SYSTEM/ADDITION/REWORK WILL BE UNDER SEPARATE PERMIT
 AND PLANS.
  
 5) NOTE: ALL WORKING CLEARANCE SHALL MEET 110.26. BASED
 ON THE NURSE STATION ELEVATION ALONE THERE ARE SEVERAL
 ITEMS WHICH REQUIRE CLEARANCE HOWEVER DO NOT MEET THE
 SECTIONS.
  
 6) NOTE: PLEASE SEE 240.12,700.27, 701.18. PLEASE
 PROVIDE COMPLETE SELECTIVE COORDINATION FOR SYSTEMS
 INCLUDING NEW EQUIPMENT BEING INSTALLED. THIS STUDY
 NEEDS TO INCLUDE TIME CURVES. SOME INFORMATION SHOWN
 AND SUBMITTED HOWEVER BASED ON E7.01 NOT MATCHING RISER
 COMPLETELY AND NOT TIME CURVES SUBMITTED IT IS NOT
 KNOWN IF MINIMUM CODE COMPLIANCE IS MET. SEE COMMENT #8
 ALSO.
  
 7) NOTE: PLEASE SEE 517.17. PLEASE PROVIDE COMPLIANCE
 BY SHOWING THE PROTECTION OF SYSTEM.
  
 8) NOTE: PLEASE GO THROUGH RISER, CONDUCTORS AND ALL
 OVER CURRENT PROTECTION DEVICES. THERE ARE ITEMS WHICH
 DO NOT COORDINATE.
 215.5, 110.9, 240.4, 310.16, 240.12 ETC THESE CODE
 SECTIONS ARE GIVEN IN GENERAL AS COORDINATION OF
 CONDUCTORS, OVER CURRENT PROTECTION, PANELS ETC EFFECT
 ALL SECTIONS.
  
 FOR EXAMPLE: PLEASE SEE RISER LINE DIAGRAM, MAIN NDB
 INDICATES A NEW BREAKER TO FEED EDNH. THIS IS SHOWN
 WITH A 125AMP OCP ON THE LINE DIAGRAM YET THE
 COORDINATION STUDY RISER SHOWS THIS BEING A 300AMP
 BREAKER TO THE NEW 300AMP MLO.
  
 FOR EXAMPLE: THE RISER INDICATES THE PANEL BEING FED AS
 NOTED ABOVE AS EDNH, HOWEVER BASED ON THE PANEL
 DESIGNATION ON E7.03 THE PANEL IS MARKED AS EDHN. ONE
 COULD ASSUME THIS IS ONLY A MISPRINT HOWEVER ALL OF
 THESE ITEMS NEED TO COORDINATE.
  
 FOR EXAMPLE: THE LOAD IN EDHN/EDNH EXCEEDS THE 125AMP
 BREAKER FEEDING THIS PANEL BASED ON RISER.
  
 ** THESE ARE TWO EXAMPLES ONLY GIVEN AS A BENEFIT.
 THERE ARE OTHERS.
  
 9) NOTE: PLEASE SHOW THE TRANSFORMER GROUNDING
 LOCATIONS. PLEASE INCLUDE ON RISER THE SIZE OF THE GEC
 AND CONNECTION POINT.
 250.66,250.20,250.30.
  
 10) NOTE: PLEASE SEE 408.4. THE PANEL SCHEDULES NEED TO
 BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED.
 STATING, RECEPTACLES, OR CONSOLE OR OTHER GENERIC TERMS
 IS NOT PERMITTED. THESE NEED TO BE CLEAR TO THE ROOMS
 AND AREAS. FOR EXAMPLE: * RECEPTACLES RM 101, ETC.
 THESE MAY BE ALPHA OR NUMERIC DESIGNATIONS BASED ON
 PLANS.
  
 ** IMPORTANT: AS NOTED ABOVE THE PROJECT WAS NOT
 SUBMITTED FOR PERMIT UNDER THE 2004 FBC. PLEASE REVISE
 ALL DESIGNS
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-08-27 Cont ID  
Sent By mawillia Date 2009-08-27 Time 15:38 Rev Time 0.00
Received By mawillia Date 2009-08-27 Time 15:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-06-11 Cont ID  
Sent By mwennerg Date 2009-06-11 Time 12:51 Rev Time 0.00
Received By mwennerg Date 2009-06-11 Time 12:51 Sent To  
Notes
2009-06-11 12:56:36COMMENTS FROM THE FIRST REVIEW APPEAR TO HAVE BEEN
 ADDRESSED AND THE PLANS HAVE BEEN APPROVED AND STAMPED.
 PLEASE SEE THE FOLLOWING:
  
 1) FIRE AND SMOKE DAMPERS TO BE TESTED FOR CLOSURE IN
 ACCORDANCE WITH UL 555 PRIOR TO FINAL INSPECTION.
  
 2) FIRE DEPARTMENT VALVES TO BE 2 1/2" CONNECTIONS TO 1
 1/2" REDUCER WITH CHAIN AND CAP.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-02 Cont ID  
Sent By mawillia Date 2009-04-02 Time 13:55 Rev Time 0.00
Received By mawillia Date 2009-04-02 Time 13:06 Sent To  
Notes
2009-04-02 13:55:18*****DENIED*****
  
  
 1. THE ACTUAL PROJECT SITE ADDRESS SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 3. THE 2007 EDITION OF FLORIDA FIRE PREVENTION CODE
 BASED ON NFPA 101 - LIFE SAFETY CODE - 2006 EDITION AND
 NFPA 1 - UNIFORM FIRE CODE 2006 EDITION) SHALL BE
 REFERENCED.
  
 4. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS
 AND CEILINGS IN THE PROJECT AREAS IN TERMS OF CLASS A,
 CLASS B, OR CLASS C.
  
 5. WILL THE SCOPE WORK HAVE CAUSE FOR THE FIRE ALARM
 SYSTEM AND/OR DEVICES TO BE REMODELED? IF SO, SEPARATE
 FIRE ALARM PERMIT AND SHOP DRAWINGS SHALL BE REQUIRED.
  
 6. SEPARATE PLANS AND SHOP DRAWINGS SHALL BE REQUIRED
 FOR ANY SPRINKLER INSTALLATION AND/OR REMADEL.
  
 7. FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80.
  
 8. BUILDINGS, OR PORTIONS OF THEREOF SHALL BE PERMITTED
 TO BE OCCUPIED DURING THE PROJECTED SCOPE OF WORK ONLY
 WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 PROTECTION FEATURES ARE IN PLACE AND CONTINUOUSLY
 MAINTAINED FOR THE PORTION OCCUPIED OR WHERE
 ALTERNATIVE LIFE SAFETY MEASURES ARE ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION ARE IN PLACE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-08-20 Cont ID  
Sent By lmartine Date 2009-08-20 Time 16:56 Rev Time 0.00
Received By lmartine Date 2009-08-20 Time 16:56 Sent To  
Notes
2009-08-20 16:56:40C-27

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-05-22 Cont ID  
Sent By dpalmer Date 2009-05-22 Time 14:52 Rev Time 0.00
Received By dpalmer Date 2009-05-22 Time 14:52 Sent To  
Notes
2009-05-22 14:52:34PLANS REMOVED FROM BOXES TO DW OFFICE FOR EXPEDITED
 REVIEWS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2009-05-19 Time   Rev Time 0.00
Received By jgomez Date 2009-05-19 Time 10:12 Sent To  
Notes
2009-05-19 10:12:41TO COMMERCIAL BOX #29.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2009-04-02 Cont ID  
Sent By mawillia Date 2009-04-02 Time 13:06 Rev Time 0.00
Received By mawillia Date 2009-02-18 Time 11:12 Sent To  
Notes
2009-02-18 11:27:21TO "COMM" BD#59

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-08-26 Cont ID  
Sent By rregueir Date 2009-08-26 Time 18:30 Rev Time 0.00
Received By rregueir Date 2009-08-26 Time 18:29 Sent To  
Notes
2009-08-26 18:30:35REVISED M0.11 THRU M0.17 AND M1.50 DELTA 3

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-07-09 Cont ID  
Sent By rregueir Date 2009-07-09 Time 14:26 Rev Time 0.00
Received By rregueir Date 2009-07-09 Time 13:45 Sent To  
Notes
2009-07-09 13:46:50PROVISO:
 PROVIDE ENGINEERING ANALYSIS OF MUNTERS RTU FOR WIND
 RESISTANCE FOR PLAN REVIEW PRIOR TO INSPECTION OF RTU.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-06-12 Cont ID  
Sent By rregueir Date 2009-06-12 Time 14:21 Rev Time 0.00
Received By rregueir Date 2009-06-12 Time 14:11 Sent To P
Notes
2009-06-12 14:21:15REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. PLANS HAVE BEEN CHANGED TO SHOW THE CONDENSATE
 DISCHARGING INTO A FUNNEL INTO STORM WATER RISER. THIS
 IS NOT ACCEPTABLE AS THIS CREATES AN OPENING OF THE
 STORMWATER SYSTEM INTO THE BUILDING. IF THE STORMWATER
 DRAIN WERE TO BECOME OBSTRUCTED IT WOULD LEAD TO A
 BACKUP OF RAIN WATER INTO THE BUILDING. CONDENSATE
 SHALL DISCHARGE OUTDOORS AT AN APPROVED LOCATION OR TIE
 INTO STORMWATER OUTSIDE THE BUILDING. PLEASE CONTACT
 PLUMBING OR MECHANICAL REVIEWER TO DISCUSS OPTIONS.
 FBC-M 307.2.1.
  
 2. PRODUCT APPROVAL SUBMITTED FOR FANS AND AHU. NO DATA
 PROVIDED FOR RTU. MAY BE A PROVISO ITEM ONCE ALL OTHER
 ISSUES ARE ADDRESSED. FBC-M 301.12.
  
 3. PLAN SHOWS AUXILIARY DRAIN DISCHARGING ONTO ROOF.
 ROOFTOP UNITS NOT LIKELY DESIGNED WITH AUX. DRAIN
 OUTLET. ALSO, WOULD NOT BE DISCHARGING TO A CONSPICUOUS
 LOCATION AS REQUIRED BY FBC-M 307.2.3. ON DOWN-FLOW
 UNITS AND ALL OTHER COILS THAT DO NOT HAVE A SECONDARY
 DRAIN AND DO NOT HAVE A MEANS TO INSTALL AN AUXILIARY
 DRAIN PAN, A WATER-LEVEL MONITORING DEVICE SHALL BE
 INSTALLED INSIDE THE PRIMARY DRAIN PAN. THIS DEVICE
 SHALL SHUT OFF THE EQUIPMENT SERVED IN THE EVENT THAT
 THE PRIMARY DRAIN BECOMES RESTRICTED. EXTERNALLY
 INSTALLED DEVICES AND DEVICES INSTALLED IN THE DRAIN
 LINE SHALL NOT BE PERMITTED IN ACCORDANCE WITH FBC-M
 307.2.3.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-03-26 Cont ID  
Sent By rregueir Date 2009-03-26 Time 20:45 Rev Time 0.00
Received By rregueir Date 2009-03-26 Time 19:00 Sent To  
Notes
2009-03-26 20:45:13REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING NOTES HAVE BEEN ADDED TO ONE SET OF
 SUBMITTED PLANS TO ASSIST IN MAKING CORRECTIONS.
  
 1. PAGE M2.01 AND M4.03: PLANS SHOW CONDENSATE FROM FCU
 DISCHARGING INTO SANITARY SEWER VIA HUB DRAIN ABOVE
 CEILING. CONDENSATE SHALL NOT DISCHARGE INTO SANITARY
 SEWER SYSTEM IN ACCORDANCE WITH CITY ORDINANCE.
 CONDENSATE SHALL DISCHARGE INTO STORMWATER SYSTEM OR
 DIRECTLY TO THE OUTDOORS. SHOW CONDENSATE DISCHARGE
 LOCATION IN ACCORDANCE WITH FBC-M 307.2.1.
  
 2. PAGES M4.02, M4.03 AND M4.04: ALL APPLIANCES,
 EQUIPMENT AND SUPPORTS WHICH ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12. PROVIDE MANUFACTURER'S
 DATA FOR FANS AND ROOFTOP UNITS SHOWING THESE
 APPLIANCES ARE DESIGNED FOR WIND RESISTANCE. ALSO, SHOW
 HOW FANS, DUCTWORK AND SUPPORTS ARE TO BE SECURED TO
 STRUCTURE FOR WIND RESISTANCE.
  
 3. PAGE M4.03: SHOW HOW FAN-COIL AND ROOFTOP UNITS ARE
 TO BE PROVIDED WITH AUXILIARY DRAIN PROTECTION IN
 ACCORDANCE WITH FBC-M 307.2.3.
  
 NOTE: THIS PLAN WAS SUBMITTED WITHOUT APPLICATION FOR
 PERMIT. THE 2007 FBC IS IN EFFECT AS OF MARCH 1, 2009.
 PLANS WILL REMAIN IN FAIL STAUS PENDING APPLICATION FOR
 PERMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop MEDGAS MEDICAL GAS
Rev No 3 Status P Date 2009-08-26 Cont ID  
Sent By kstevens Date 2009-08-26 Time 17:30 Rev Time 0.00
Received By kstevens Date 2009-08-25 Time 17:52 Sent To  
Notes
2009-08-26 17:31:47REVISIONS OK -- SHT P2.01, P2.02, P2.03, P2.04, P2.05,
 P2.06 (NEW SHEET), P2.07 (NEW SHEET).

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2009-06-12 Cont ID  
Sent By kstevens Date 2009-06-12 Time 15:58 Rev Time 0.00
Received By kstevens Date 2009-06-12 Time 15:58 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2009-06-12 Cont ID  
Sent By kstevens Date 2009-03-27 Time 11:41 Rev Time 0.00
Received By kstevens Date 2009-03-26 Time 17:13 Sent To  
Notes
2009-03-27 11:48:31PLANS ARE CODE COMPLIANT - REFERENCE NFPA 99C 2002 TO
 BE ADDED ON SHT AO.OO

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-08-26 Cont ID  
Sent By kstevens Date 2009-08-26 Time 17:31 Rev Time 0.00
Received By kstevens Date 2009-08-25 Time 17:51 Sent To  
Notes
2009-08-26 17:33:38REVISIONS OK -- SHTS P1.00, P1.01, P1.02, P1.03, P1.04,
 P1.05, P1.06 (NEW SHEET).

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-07-09 Cont ID  
Sent By kstevens Date 2009-07-09 Time 14:19 Rev Time 0.00
Received By kstevens Date 2009-07-09 Time 14:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-06-12 Cont ID  
Sent By kstevens Date 2009-06-12 Time 15:59 Rev Time 0.00
Received By kstevens Date 2009-06-12 Time 15:59 Sent To  
Notes
2009-06-12 16:03:07DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 NFPA 99C 2002
 CITY OF WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHTS P1.01 & P3.01 WASTE & VENT PIPING. THE 2 INCH
 HUB DRAIN FOR THE FCU IS NOT APPROVED. CONDENSATE SHALL
 NO DRAIN INTO THE SANITARY DRAINAGE SYSTEM PER ARTICLE
 III SECTION 90-125(5). CONDENSATE SHALL BE CONNECTED TO
 A DEDICATED CONDENSATE LINE, TO THE STORM SYSTEM
 OUTSIDE THE BUILDING, TO A DRYWELL OR TO A PLANTED AREA
 MINIMUM 1 FOOT AWAY FROM THE STRUCTURAL WALL.
 ****RESPONSE NOTED, BUT THE 2" HUB DRAIN CONNECTING TO
 THE STORM ABOVE THE CEILINGON SHT P1.01 IS NOT AN
 APPROVED PLACE OF DISPOSAL. CONDENSATE SHALL BE DRAINED
 SEPARATELY FROM THE BUILDING AS INDICATED IN COMMENT. A
 RELIEF VENT, (GOOSENECK) IS REQUIRED ON THE CONDENSATE
 PIPING AS IT EXITS THE BUILDING IF THE CONDENSATE WILL
 BE CONNECTED TO THE STORM LINE OUTSIDE THE BUILDING.
 SECTION 314.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-03-27 Cont ID  
Sent By kstevens Date 2009-03-27 Time 11:48 Rev Time 0.00
Received By kstevens Date 2009-03-26 Time 17:13 Sent To  
Notes
2009-03-27 11:56:07DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 NFPA 99C 2002
 CITY OF WPB MUNICIPAL CODE
  
 1. SHT A0.00 CODE CRITERIA SHALL BE UPDATED TO FBC-2007
 W/2009 SUPPLEMENTS AS THE PERMIT WILL BE APPLIED FOR
 AFTER MARCH 1 2009. ALSO ADD NFPA 99C 2002 FOR THE
 MED-GAS CODE CRITERIA.
  
 2. SHTS P1.01 & P3.01 WASTE & VENT PIPING. THE 2 INCH
 HUB DRAIN FOR THE FCU IS NOT APPROVED. CONDENSATE SHALL
 NO DRAIN INTO THE SANITARY DRAINAGE SYSTEM PER ARTICLE
 III SECTION 90-125(5). CONDENSATE SHALL BE CONNECTED TO
 A DEDICATED CONDENSATE LINE, TO THE STORM SYSTEM
 OUTSIDE THE BUILDING, TO A DRYWELL OR TO A PLANTED AREA
 MINIMUM 1 FOOT AWAY FROM THE STRUCTURAL WALL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-06-02 Cont ID  
Sent By eschneid Date 2009-06-02 Time 09:48 Rev Time 0.50
Received By eschneid Date 2009-06-02 Time 09:48 Sent To  
Notes
2009-06-02 10:31:38PASSED
  
 NOTE: IF PERMITS WITHIN A ONE YEAR PERIOD ON THE
 BUILDING AT 2201 45TH STREET EXCEED 50% OF THE VALUE OF
 THE BUILDING, THEN A LANDSCAPE PLAN SHOWING COMPLIANCE
 WITH THE CITY'S LANDSCAPE CODE IS REQUIRED.
  
 PERMIT NO. 09020635 $495,000
 PERMIT NO. 09020319 $2,150,000
  
 TOTAL $2,645,000
  
 BUILDING VALUE $12,685,641 = CURRENTLY LESS THAN 50%.
  
 ANY EXTERIOR SIGNAGE REQUIRES A SEPARATE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-03-02 Cont ID  
Sent By eschneid Date 2009-03-02 Time 14:57 Rev Time 1.25
Received By eschneid Date 2009-03-02 Time 14:57 Sent To  
Notes
2009-03-02 14:59:28FAILED PLAN REVIEW
  
 1) PLEASE NOTE THAT THE ADDRESS AND PCN ARE INCORRECT.
 THE LIMITS OF WORK ARE IN THE BUILDING LOCATED AT 4631
 N. CONGRESS WITH PCN 74434306000001030.
  
 2) NOTE THAT IF THE VALUE OF THIS PERMIT, WHEN ADDED TO
 OTHER PERMITS WITHIN THE LAST YEAR TOTAL 50% OF THE
 VALUE OF THE BUILDING, THEN A LANDSCAPE PLAN VERIFYING
 THAT THE SITE CONFORMS TO THE LANDSCAPE CODE IS
 REQUIRED.
  
 3) IT APPEARS THAT THE DECONTAMINATION AREA IS ADDED
 SQUARE FOOTAGE/STRUCTURE OUTSIDE OF THE EXISTING WALL.
 PLEASE CLARIFY. IF THIS IS AN ADDITION, THEN IT
 REQUIRES THE APPROVAL OF A MINOR PLANNED DEVELOPMENT
 AMENDMENT PRIOR TO THE ISSUANCE OF THE BUILDING PERMIT.
  
 4) IF DECONTAMINATION AREA HAS NO ADDITIONAL SQUARE
 FOOTAGE, THEN WORK SHOWN COMPLIES WITH ZONING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved