Plan Review Details - Permit 09020294
Plan Review Stops For Permit 09020294
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-05-18 Cont ID  
Sent By jnguyen Date 2009-05-18 Time 10:41 Rev Time 0.00
Received By jnguyen Date 2009-05-15 Time 17:36 Sent To  
Notes
2009-05-18 10:25:30I HAVE TAKEN A LOOK AT THE SITE PLAN & NOTICED THAT THE
 PROSPECTIVE WORK AREA DOES NOT OCCUR WITHIN THE
 BOUNDARIES OF PCN# 74424311010190000 AT 4325 N
 HAVERHILL RD (WPB WASTEWATER TREATMENT PLANT). THERE IS
 AN ADDRESSING ISSUE FOR THE WPB WASTEWATER TREATMENT
 PLANT BECAUSE ACCESS DOES NOT OCCUR OFF N HAVERHILL RD,
 BUT INSTEAD EASLEY DR (THERE WILL BE AN ATTEMPT MADE BY
 ME TO EVENTUALLY TRY TO RESOLVE THIS ISSUE WITH OUR
 CITY'S WASTEWATER DEPARTMENT.). HOWEVER, THAT ISSUE
 WILL BE A WORK IN PROGRESS THAT DOES NOT PARTICULARLY
 APPLY TO THIS PERMIT. FROM MY OBSERVATION OF THE SITE
 PLANS, THE AREA OF ALTERATION ACTUALLY TAKES PLACE ON
 THE PARCEL TO THE SOUTH, PCN# 74424311010350000 WITH A
 GENERAL PRIMARY ADDRESS OF 4335 EASLEY DR (WHICH MY
 PREDECESSOR, LILI ISSUED BACK ON 8-25-2006). FOR THE
 RECORD, I NEVER ISSUED ANY ADDRESSES BACK IN EARLY
 APRIL, I SIMPLY "VERIFIED" EXISTING ADDRESSES & PARCELS
 THAT WE CURRENTLY HAD ON FILE IN OUR DATABASES FOR A
 CITIZEN, PETER GILSTAD. IT JUST TURNED OUT THAT 4335
 EASLEY DR ON 74424311010350000 WAS APPROPRIATELY VALID
 TO BE USED FOR THIS PARTICULAR PERMIT. IN
 COMMUNITYPLUS, PLEASE MOVE THIS PERMIT RECORD FROM PCN#
 74424311010190000 AT 4325 N HAVERHILL RD TO BE
 CORRECTLY APPLIED INSTEAD TO PCN# 4424311010350000 AT
 4335 EASLEY DR (AS I DO NOT HAVE AUTHORIZATION TO
 IMPLEMENT THIS PROCEDURE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-06-11 Cont ID  
Sent By jwitmer Date 2009-06-11 Time 1:55 Rev Time 1.11
Received By jwitmer Date 2009-06-11 Time 12:45 Sent To  
Notes
2009-06-11 12:56:50PLANS OK TO ISSUE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-05-14 Cont ID  
Sent By jwitmer Date 2009-05-14 Time 10:17 Rev Time 1.22
Received By jwitmer Date 2009-05-14 Time 10:17 Sent To  
Notes
2009-05-14 10:21:56BUILDING PLAN REVIEW
 PERMIT: 09020294
 ADD: 4325 N HAVERHILL RD.
 CONT: MAJOR WORKING DRAWING REVIEW
 TEL: (561)632-5317
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 MAY 14TH, 2009
 2ND REVIEW
 ACTION: DENIED
 1A) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
 NOTE: PLANS THAT ARE SUBMITTED FIRST TIME UNDER A
 PERMIT APPLICATION STARTING MARCH 1, 2009 WILL BE
 REVIEWED TO THE 2007 FBC, WITH THE 2009 SUPPLEMENTS
 THIS START DATE IS A MANDATED IMPLEMENTION DATE STATE
 WIDE.
 SINCE TO DATE NO CONTRACTOR HAS MADE APPLICATION TO
 CHANGE THIS MAJOR WORKING DRAWING REVIEW INTO A PERMIT
 APPLICATION THIS REVIEW WILL BE COMPLETED UNDER THE
 2007FBC WITH 2009 SUPPLEMENTS, PLEASE UPDATE ALL PLANS
 TO REFECT AS SUCH!. SHEET S0.1.
  
 CALLED RCT ENGINEERING TO SPEAK TO MR WILLIAM KIAHON P.
 E. ABOUT A NEW S0.1, 2007 FBC W/ 2009 SUPPLEMENTS. THE
 RECEPTIONIST INDICATED MR KIAHON IS OUT OF THE COUNTRY
 UNTIL NEXT WEEK.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-11 Cont ID  
Sent By jwitmer Date 2009-03-11 Time 09:43 Rev Time 7.55
Received By jwitmer Date 2009-03-11 Time 09:43 Sent To  
Notes
2009-03-11 10:06:12BUILDING PLAN REVIEW
 PERMIT: 09020294
 ADD: 4325 N HAVERHILL RD.
 CONT: MAJOR WORKING DRAWING REVIEW
 TEL: (561)632-5317
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOROR
 RESIDENT INSPECTOR, THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
 NOTE: PLANS THAT ARE SUBMITTED FIRST TIME UNDER A
 PERMIT APPLICATION STARTING MARCH 1, 2009 WILL BE
 REVIEWED TO THE 2007 FBC, WITH THE 2009 SUPPLEMENTS
 THIS START DATE IS A MANDATED IMPLEMENTION DATE STATE
 WIDE.
 SINCE TO DATE NO CONTRACTOR HAS MADE APPLICATION TO
 CHANGE THIS MAJOR WORKING DRAWING REVIEW INTO A PERMIT
 APPLICATION THIS REVIEW WILL BE COMPLETED UNDER THE
 2007FBC WITH 2009 SUPPLEMENTS, PLEASE UPDATE ALL PLANS
 TO REFECT AS SUCH!. SHEET A9.0 & S0.1.
  
 2) SHEET A9.0 INDICATES FIRE SPRINKLERS NOT REQUIRED
 AND NOTED PER THE REQUIREMENT OF PBC AMENDMENT TO THE
 FIRE PREVENTION CODE SECTION 13.3.2.1.1.4. THIS
 FACILITY IS LOCATED WITHIN THE
 CITY OF WEST PALM BEACH, NOT THE COUNTY. ALSO NOTE
 SINCE THE 2004 FBC THERE ARE NO LONGER LOCAL AMENDMENT
 TO THE FBC EXCEPT FOR CHAPTER 1.
  
 3) SHEET A9.0 WILL NEED TO PROVIDE THE TYPES OF
 MATERIALS TO BE STORED AND THE AMOUNTS TO DETERMINE THE
 TYPE OF OCCUPANCY. WITHOUT THIS INFORMATION WE CAN NOT
 CLASSIFY THIS BUILDING.THE PLANS INDICATE STORAGE OF
 SODIUM HYPOCHLORITE. SECTION 307.2 UNDER THE DEFINITION
 OF OXIDIZER THERE ARE FOUR CLASSIFICATIONS. PLEASE
 IDENTIFY WHICH OF THESE CATEGORIES WE WILL BE DEALING
 WITH AND THE AMOUNT TO BE STORED, STATE OF COMPOUND
 (GAS, LIQUID OR SOLID) AND WHAT TYPE OF STORAGE
 CONTAINER. ALSO PROVIDE THE MSDS SHEETS FOR THIS
 COMPOUND AND OTHER CHEMICALS TO BE STORED WITHIN THIS
 BUILDING.
  
 4) THE COVERSHEET C1.1 INDICATES THE USE OF A 3MG
 CHLORINE CONTACT STORAGE TANK, PLEASE PROVIDE
 ADDITIONAL INFORMATION, IS THIS 3 MILLION GALLONS OF
 CHLORINE, OR A MIXING TANK? IS THIS NEW CONSTRUCTION OR
 JUST A TIE IN ASA INDICATED ON SHEET S99.1.
  
 5) SHEET A9.0 INDICATES THIS BUILDING TO BE A TYPE II-B
 CONSTRUCTION. WEST PALM BEACH ADMINISTRATIVE CODE
 109.3.7 (1) FOR BUILDINGS OF TYPE I OR II CONSTRUCTION
 SHALL REQUIRE A RESIDENT INSPECTOR . A COPY OF THE
 PAPERWORK SHALL BE ATTACHED.
  
 6) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 7A) EXTERIOR METAL DOORS SINGLE & DOUBLE DOORS
 7B) WALL LOUVERS
 7C) ROOFING ASSEMBLIES INCLUDING INSULATION
 7D) ROLL UP DOOR
  
 8) NO ENERGY CALCULATIONS WERE SUBMITTED, SHALL COMPLY
 WITH 13-101.1.1. METHOD A,B OR C. PLEASE PROVIDE THE
 INPUT DATA REPORT WITH THE ENRGY CALCULATIONS, PLEASE
 NOTE THE 2007 BUILDING CODE HAS UPDATED CHAPTER 13 BUT
 THE 2009 SUPPLEMENTS ARE NOT AVAILABLE AS OF YET.
  
 9) NOTE THAT SHEET A9.7 DETAIL 04 ROOF INSULATION THIS
 AREA BY THE SCUPPER IS THE LOWEST LEVEL OF ROOF
 INSULATION AND THIS AREA WOULD NEED TO MEET AS THE
 MINIMUM R-VALUE LISSTED IN THE INPUT DATA REPORT.
 13-404.ABC.1.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-05-29 Cont ID  
Sent By dpalmer Date 2009-05-29 Time 09:56 Rev Time 0.00
Received By dpalmer Date 2009-05-29 Time 09:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-05-18 Cont ID  
Sent By dpalmer Date 2009-05-18 Time 10:47 Rev Time 0.00
Received By dpalmer Date 2009-05-15 Time 15:41 Sent To  
Notes
2009-05-18 10:47:34**DENIED REVIEW **
  
 1) NOTE: REVIEW SHALL REMAIN IN FAILED STATUS UNTIL
 SUCH TIME PERMIT APPLICATION HAS BEEN MADE WITH A
 LICENSED CONTRACTOR. THIS WAS NOTED ON PREVIOUS REVIEW.
  
 ** ELECTRICAL PLANS CONTAIN STAMPS; PLEASE DO NOT
 REVISE ANY PLANS UNTIL AFTER PERMIT ISSUANCE. IF SHEETS
 ARE REVISED THEN THIS WILL REQUIRE A RE-REVIEW OF SAID
 PROJECT.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-03 Cont ID  
Sent By dpalmer Date 2009-03-03 Time 08:56 Rev Time 0.00
Received By dpalmer Date 2009-03-03 Time 08:56 Sent To  
Notes
2009-03-03 08:56:57** DENIED REVIEW **
  
 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW
 UNDER THE 2004 CODE AND OTHER ADOPTED STANDARDS. THERE
 WILL BE A CODE CHANGE AS OF MARCH 1ST, 2009 WHICH WILL
 REQUIRE ALL PLANS TO BE REVISED TO THE NEW CODES.
 PLEASE BE AWARE THE SUBMISSION OF PLANS FOR PLAN REVIEW
 ONLY DOES NOT LOCK THE PROJECT IN UNDER THE CURRENT
 CODES IN EFFECT. ONLY PERMIT APPLICATIONS UNDER A
 LICENSED CONTRACTOR WITH REQUIRED MINIMUM FEES APPLIED
 FOR BEFORE THAT DATE WILL *LOCK* THE PROJECT UNDER THE
 CURRENT CODE EDITIONS. THIS WILL AFFECT THE DESIGNS ON
 THE PROJECT FOR MANY ASPECTS HOWEVER THE ELECTRICAL
 CODE IS NOT SCHEDULED TO BE CHANGED UNTIL JULY 1ST,
 2009.
  
 ** ANY REFERENCES BELOW TO FBC CHAPTER 1 IS BASED ON
 AMENDMENTS AS ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON THE PLANS. THE PLANS MUST LIST THE ACTUAL DESIGN
 DOCUMENTS.
 THERE ARE SEVERAL SHEETS WITH REFERENCES TO CODES WHICH
 ARE NO LONGER IN EFFECT.
 FOR EXAMPLE: THE STATE FAC RULE 69A-60.003 AND .004
 ADOPTED THE 2006 NFPA-1 AND 2006 NFPA-101 BEFORE THE
 ACTUAL ADOPTION OF THE NEW CODES. THE PLANS FOR EXAMPLE
 ON SHEET A9.0 DOES LIST THE PREVIOUS CODES AS WELL THE
 PREVIOUS ADOPTED RULE WHICH NO LONGER CONTAINS THESE
 CODES REFERENCES. IF THE FAC RULE IS GOING TO BE PLACED
 ON PLANS PLEASE REVISE TO THE SECTIONS AS NOTED ABOVE.
 PLEASE ALSO SEE OTHER EXAMPLES SUCH AS REFERENCE TO THE
 2002 NFPA-70 ( NATIONAL ELECTRICAL CODE). THE FOLLOWING
 CODES WILL BE STATED AND NEEDED ON BOTH THE
 ARCHITECTURAL COVER SHEET AND ELECTRICAL PLANS. IT IS
 NOTICED THAT SOME CODES ARE OK ON ELECTRICAL PLANS
 HOWEVER NOT ALL.
 PLEASE BE AWARE THAT SHEETS SUCH AS FIRE ALARM AND
 STRUCTURAL SHEETS MAY NEED TO BE REVISED FOR CURRENT
 CODES.
 *** KEEP IN MIND IF THIS PROJECT HAS NOT APPLIED FOR
 PERMIT BEFORE THE MARCH 1ST, 2009 DEADLINE ALL CODES
 STATED BELOW MAY NOT BE ACCURATE.
 *** MANY SHEETS IN THE SETS OF PLANS SUBMITTED ALSO
 STATE * PALM BEACH COUNTY* AS THE AMENDED LOCAL
 AUTHORITY. AS THIS PROJECT IS IN THE CITY OF WEST PALM
 BEACH PLEASE ADJUST NOTES ACCORDINGLY. THIS IS STATED
 ON NUMEROUS SHEETS AND PLANS.
 PLEASE LIST AS FOLLOWS BASED ON CURRENT CODES. IF
 APPLICATION IS NOT MADE SOME OTHER CODES WILL CHANGE.
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70
 2006 NFPA-101
 2006 NFPA-1
 2002 NFPA-72
  
 ** NOTES UPDATED: AS PERMIT HAS NOT BEEN APPLIED FOR
 BEFORE MARCH 1ST, THE NEW CODES SHALL BE BASED ON THE
 2007 FBC.
  
  
 3) NOTE: IN THE SET OF PLANS REVIEWED THERE ARE SEVERAL
 SHEETS WHICH WERE SIGNED AND DATED HOWEVER THEY ARE
 MISSING THE REQUIRED RAISED SEAL PER FS 471.025 AND FAC
 61G15-23.002.
 MANY OF THESE SHEETS ARE NOT ELECTRICAL IN NATURE
 HOWEVER THIS IS GIVEN AS A BENEFIT FOR INFORMATION.
 SHEETS: CU1.1,1.3,1.4,1.5 , CP 1.1,1.2, 1.4 AND 1.6
 THROUGH C9.18.
 THIS IS NOTED FOR DESIGN TEAM ONLY BY THIS REVIEWER. IF
 COMMENT IS NOT MADE BY OTHER TRADE(S) THIS IS STILL
 REQUIRED.
 FS 481.221, 471.025
  
 4) NOTE: ANY * LOCK OFF* TYPE OF BREAKERS ON THIS
 PROJECT SHALL HAVE THE LOCK OFF DEVICE BE AN INTEGRAL
 PART OF THE BREAKER. MOST OF THE CLIP ON OR SNAP ON
 TYPE DEVICES ARE NOT LISTED FOR PERMANENT INSTALLATION.
 PLEASE MAKE NOTE ON PLANS FOR THE TYPE OF BREAKERS
 REQUIRED. THE DIVISION SPECIFICATIONS WERE NOT CLEAR TO
 THE ACTUAL TYPE OF DEVICE INTENDED.
 110.3
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 5) NOTE: THE RISER CLEARLY INDICATES A CONNECTION OF A
 PORTABLE GENERATOR WITHOUT ANY FAIL SAFE OPERATION OF A
 TRANSFER SWITCH OF DEVICE OF SOME SORT. THIS
 INSTALLATION DOES NOT MEET 702.6. THE PROPOSED KIRK KEY
 INTERLOCK IS NOT A LISTED TRANSFER SWITCH OR DEVICE. IT
 ALSO DOES NOT PROVIDE FAIL SAFE OPERATION. PLEASE BE
 AWARE THAT INSTALLATION OF THIS TYPE OF DEVICE MAY ALSO
 VOID LISTING AND OR WARRANTY OF EQUIPMENT.
 110.3
 THIS COMMENT IS WITH RESPECT TO ALL PANELS AND ALL
 EQUIPMENT ON RISER WHICH INDICATE THIS SAME KIRK KEY
 INTERLOCK SYSTEM.
 THE INSTALLATION OF A PORTABLE GENERATOR WITH OUT THE
 USE OF TRANSFER EQUIPMENT MAY BE PART OF THE EXCEPTION.
 PLEASE PROVIDE AN ORIGINAL NOTARIZED LETTER FROM THE
 RESPONSIBLE AUTHORITY WHICH STATES THIS ENTIRE SCOPE OF
 WORK WILL ONLY BE DONE BY *QUALIFIED PERSONNEL* PER THE
 DEFINITIONS IN THE NATIONAL ELECTRICAL CODE ARTICLE
 100. THIS DOES NOT NEGATE THE FIRST PART OF THIS NOTE
 WITH RESPECT TO THE KIRK KEY BEING LISTED OR VOID
 LISTING OF EQUIPMENT.
 SEE OTHER NOTES BELOW WITH RESPECT TO ARC FLASH AND
 OTHER HAZARDS.
  
 6) NOTE: PLEASE PROVIDE INFORMATION ON THE REQUIRED
 GROUND FAULT PROTECTION OF MAINS PER 240.13 AND 230.95.
  
 7) NOTE: PLEASE ALSO PROVIDE NOTES OR INFORMATION ON
 ALL MAINS. THE RISER LENDS TO THE FACT BOTH OF THESE
 ARE SHUNT TRIP HOWEVER DO BOTH OF THESE STILL CONTAIN
 THE REQUIRED MANUAL MEANS OF DISCONNECT RATED FOR THE
 LOAD SERVED PER 230.76 AND 230.79?
 IF ACTUAL LISTING IS PROVIDED THIS MAY ALSO HELP ANSWER
 QUESTION.
  
 8) NOTE: PLEASE PROVIDE INFORMATION ON TRANSFORMERS AS
 THE OVER CURRENT PROTECTION IS EXCEEDING THE MAXIMUM
 125% BASED ON 450.3.
 IF MEETING NOTES IN TABLES, TYPE OF UNIT NEEDS TO BE
 VERIFIED AND STATED ON PLANS. IF NOT MEETING NOTES ON
 TABLE 450.3 THE MAXIMUM OVER CURRENT PROTECTION SHALL
 BE 125%.
  
 9) NOTE: PLEASE VERIFY ALL TRANSFORMER LOCATIONS FOR
 LENGTH OF TAPPED CONDUCTORS PER 240.21. THE TAP RULES
 ARE BASED ON THE LENGTH OF CONDUCTORS AND AS SOME SEEM
 TO PERHAPS BE LOCATED SO THE LENGTHS ARE OVER THE
 ALLOWANCES IN THE SECTION NOTED, THIS NEEDS TO BE
 VERIFIED AT THIS TIME.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
2009-02-25 16:54:43REVIEW HAS COMMENCED. ONCE REVIEW IS COMPLETED REVIEW
 WILL PROCEED INTO A FAILED STATUS.
 REVIEW WILL CONTINUE ON 3/2

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2009-06-03 Cont ID  
Sent By efabian Date 2009-05-13 Time 11:39 Rev Time 0.00
Received By efabian Date 2009-05-12 Time 11:39 Sent To  
Notes
2009-06-03 11:41:24PASSED
  
 PLAN REVIEW FEE RECEIVED

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2009-03-17 Cont ID  
Sent By dlauderm Date 2009-03-17 Time 11:42 Rev Time 0.00
Received By dlauderm Date 2009-03-17 Time 11:42 Sent To  
Notes
***NONE***

Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status P Date 2009-06-03 Cont ID  
Sent By efabian Date 2009-04-08 Time 11:13 Rev Time 0.00
Received By efabian Date 2009-04-02 Time 11:12 Sent To  
Notes
2009-06-03 11:16:10PASSED WITH PROVISO
  
 ALL DOCUMENTS/PLANS ARE RECIEVED AND ARE SATISFACTORY
  
 APPROVAL IS PENDING PAYMENT OF PLAN REVIEW FEE

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 2 Status P Date 2009-06-03 Cont ID  
Sent By efabian Date 2009-05-29 Time 11:47 Rev Time 0.00
Received By efabian Date 2009-05-29 Time 11:56 Sent To  
Notes
2009-06-03 11:45:14INFRASTUCTURE REPORTS PART I AND II
 RECEIVED

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status P Date 2009-05-29 Cont ID  
Sent By efabian Date 2009-05-28 Time 11:33 Rev Time 0.00
Received By efabian Date 2009-05-28 Time 11:57 Sent To  
Notes
2009-06-03 11:36:50PASSED
  
 CONSTRUCTION ADMINISTRTION FEE RECIEVED
  
 REQUESTED APPROVED PRODUCTS LIST
 BE SUBMITTED PRIOR TO A PRE-CONSTRUCTION MEETING

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status P Date 2009-06-02 Cont ID  
Sent By efabian Date 2009-03-30 Time 15:00 Rev Time 0.00
Received By efabian Date 2009-03-24 Time 15:00 Sent To  
Notes
2009-06-02 15:10:07STATUS - PASSED WITH PROVISOS
  
 NOTE: LAST (THIS PAST MARCH 2009) PLANS ARE PASSED WITH
 A FEW MINOR PROVISOS
 WHICH INCLUDED
  
 LIFT STATION PLAN/DETAILS AND SOME ADDITIONAL REVISIONS
 NOTED ON PLANS.
  
 CERTIFIED COST ESTIMATE & PLAN REVIEW FEE
  
  
 PRIOR TO THE MARCH 2009 PLANS SUBMITTALS, BOTH 60% AND
 90% PLANS WERE REVIEWED AND REVISED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-06-12 Cont ID  
Sent By rbrown Date 2009-06-12 Time 09:42 Rev Time 0.00
Received By rbrown Date 2009-06-12 Time 09:41 Sent To  
Notes
2009-06-12 09:49:35DISCUSSED WITH CAPT. MIKE WENNERGREN ON 6/11/09. PLANS
 ALREADY STAMPED BY CAPT. MIKE WILLIAMS (SEE FIRE REVIEW
 COMMENTS ON 5/18/09 REVIEW). CONTRACTOR PERMIT
 APPLICATION FORM HAS SINCE BEEN SUBMITTED AND FEES
 PAID, SO CAPT. WILLIAMS REQUIREMENTS HAVE BEEN MET.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-05-18 Cont ID  
Sent By mawillia Date 2009-05-18 Time 13:13 Rev Time 0.00
Received By mawillia Date 2009-05-18 Time 11:55 Sent To  
Notes
2009-05-18 12:29:39*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS C91.6, A9.0, A9.1, A9.2,
 A9.4, F0.1,F0.2, F0.3, F9.1, AND E9.2 WERE STAMPED,
 INITIALED, AND DATED. PLEASE BE ADVISED, HOWEVER THE
 REVIEW SHALL REMAIN IN FAILED STATUS UNTIL SUCH TIME
 PERMIT APPLICATION HAS BEEN MADE WITH A LICENSED
 CONTRACTOR.
  
  
  
 CAPT. MICHAEL A.WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-03-31 Cont ID  
Sent By mawillia Date 2009-03-31 Time 21:48 Rev Time 0.00
Received By mawillia Date 2009-03-31 Time 20:02 Sent To B
Notes
2009-04-01 10:30:23*****DENIED*****
  
  
 01. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 02. FIRE DEPARTMENT ACCESS ROADS SHALL BE DESIGNED AND
 MAINTAINED TO SUPPORT THE IMPOSED LOADS OF FIRE
 APPARATUS AND SHALL BE PROVIDED WITH AN ALL-WEATHER
 DRIVING SURFACE.
  
 03. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 04. ON SHEET C91.6 INCLUDE IN NOTES AND/OR SHOW ON
 DIAGRAM THAT IN ADDITION TO THE ELECTRONIC SWITCH, THE
 OS&Y VALVE SHALL BE REQUIRED TO BE CHAINED AND LOCKED.
  
 05. THE 2007 EDITION FLORIDA FIRE PREVENTION CODE
 (BASED ON NFPA 1- UNIFORM FIRE CODE - 2006 EDITION AND
 NFPA 101 - LIFE SAFETY CODE - 2006 EDITION) SHALL BE
 REFERENCED.
  
 06. ON SHEET A9.0, THE DEAD END CORRIDOR IN A
 NON-SPRINKLERED BUILDING SHALL BE 20' INSTEAD OF 50' AS
 LISTED IN THE CODE REQUIREMENT SECTION.
  
 07. ON SHEET A9.0, THE COMMON PATH REQUIREMENT FOR A
 NON-SPRINKLERED BUILDING SHALL BE 50' INSTEAD 100' AS
 LISTED IN THE CODE REQUIREMNT SECTION.
  
 08. ON SHEET A9.0, REFERENCE IS MADE TO AUTOMATIC FIRE
 SPRINKLER SYSTEM - NOT REQUIRED - PER THE REQUIREMENT
 OF PBC AMENDMENT TO THE FLORIDA FIRE PREVENTION CODE
 13.3.2.1.1.4; HAS THIS AMENDMENT BEEN ADOPTED BY THE
 JURISDICTION OF THE CITY OF WEST PALM BEACH?
  
 09. ON SHEET A9.0, ELIMINATE/AMEND NOTE #9 UNDER
 APPLICABLE CODES.
  
 10. IF ANY, WHAT TYPE OF CHEMICALS WILL BE STORED AT
 THE FACILITY AND IN WHAT QUANTITIES?
  
 11. WILL THERE BE ANY MARKING, IDENTIFICATION,
 PLACARDING, ETC TO BE UTILIZED AT THE FACILITY? AND IF
 SO, PLEASE SHOW ON THE APPROPIATE PLAN SHEET.
  
 12. SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION FRONTING OR FACING THE
 STREET OR PRINCIPAL VEHICULAR ACCESS TO THE PREMISES.
 AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH/STROKE.
  
 13. ON SHEET F0.1 UPDATE REFERENCES TO NFPA 101 TO THE
 2006 EDITION AND ELIMINATE REFERERENCE(S) TO PALM BEACH
 COUNTY CODES.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCEESS, INCLUDE A
 RESPONSE LETTER INDICATING HOW/WHERE ON THE APPROPIATE
 PLAN SHEET EACH COMMENT WERE ADDRESSED
  
  
  
 CAPT. MICHAEL A.WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2011-02-24 Time 09:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-06-11 Cont ID  
Sent By dpalmer Date 2009-06-11 Time 09:43 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2009-06-11 09:44:28IN C34

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-30 Cont ID  
Sent By rregueir Date 2009-04-30 Time 16:21 Rev Time 0.00
Received By rregueir Date 2009-04-30 Time 16:18 Sent To  
Notes
2009-04-30 16:21:52C4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-31 Cont ID  
Sent By mawillia Date 2009-03-31 Time 20:02 Rev Time 0.00
Received By mawillia Date 2009-02-13 Time 15:33 Sent To  
Notes
2009-02-13 15:35:26TO "COMM" BD#23/PLANS ON RACK--2 ROLLS AND PAPERWORK

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-05-22 Cont ID  
Sent By rkussner Date 2009-05-22 Time 11:45 Rev Time 0.00
Received By rkussner Date 2009-05-22 Time 11:45 Sent To  
Notes
2009-05-22 11:47:08***LANDSCAPE REVIEW PASSED WITH PROVISO***
  
 SUBMIT NEW TREE ALTERATION APPLICATION AND TWO (2)
 COPIES OF THE MOST CURRENT APPROVED LANDSCAPE PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-06-12 Cont ID  
Sent By rregueir Date 2009-06-12 Time 10:06 Rev Time 0.00
Received By rregueir Date 2009-06-12 Time 10:06 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-05-14 Cont ID  
Sent By rregueir Date 2009-05-14 Time 15:32 Rev Time 0.00
Received By rregueir Date 2009-05-14 Time 15:03 Sent To  
Notes
2009-05-14 15:34:21**PLAN CHECK ONLY**
  
 PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 PASSED. HOWEVER, REVIEW WILL REMAIN IN FAIL STATUS
 PENDING RECEIPT OF AN APPLICATION FOR PERMIT. ONCE
 PERMIT IS READY TO ISSUE, A PROVISO WILL BE ADDED TO
 PLANS REQUIRING ADEQUATE SUPPORTING DOCUMENTATION
 REGARDING THE WIND RESISTANCE CAPABILITIES OF THE
 OUTDOOR MECHANICAL APPLIANCES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-02-21 Cont ID  
Sent By rregueir Date 2009-02-21 Time 14:27 Rev Time 0.00
Received By rregueir Date 2009-02-21 Time 14:08 Sent To  
Notes
2009-02-21 14:27:41REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. F-901 AND F-903 ARE SHOWN AS SUPPLY FANS WITH A
 DESIGN CAPACITY EXCEEDING 2000 CFM. SMOKE DETECTORS
 SHALL BE INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN
 CAPACITY GREATER THAN 2,000 CFM IN THE SUPPLY AIR DUCT
 IN ACCORDANCE WITH FBC-M 606.2.1. DUCT SMOKE DETECTORS
 SHALL BE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IN
 ACCORDANCE WITH BFC-M 606.4.
  
 2. THE MOTORIZED DAMPER SCHEDULE CALLS FOR MOTORIZED
 DAMPER MD-902 RO BE INTERCONNECTED WITH AHU-901. IT IS
 NOT CLEAR WHY IT WOULD BE INTERCONNECTED WITH SHU-901
 WHEN IT SERVES AHU-902. PLEASE CLARIFY THE DESIGN
 INTENT IN ACCORDANCE WITH FBC-M 603.1 AND FBC-B
 106.1.1.
  
 3. THEFAN SCHEDULE CALLS FOR F-901 AND F-902 TO BE
 EQUIPPED WITH EXPLOSION-PROOF MOTORS. DOES THIS
 REQUIREMENT APPLY TO ALL MOTORS AT THIS LOCATION? IS
 THIS A CLASS LOCATION PER NEC REQUIREMENTS? PLEASE
 CLARIFY WHETHER THE MOTORIZED DAMPER MOTORS ARE
 REQUIRED TO BE DESIGNED FOR A CLASS LOCATION IN
 CONJUNCTION WITH THE FANS THEMSELVES.
  
 4. NO STRUCTURAL DETAIL COULD BE FOUND FOR ANCHORING OF
 THE OUTDOOR CONDENSING UNITS FOR WIND RESISTANCE. ALSO,
 NO SUPPORTING DOCUMENTATION WAS PROVIDED SHOWING THESE
 OUTDOOR APPLIANCES ARE DESIGNED FOR WIND RESISTANCE.
 MECHANICAL APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES AS DETERMINED IN ACCORDANCE WITH FBCM 301.13.
 PROVIDE STRUCTURAL DETAIL FOR ATTACHMENT OF THE
 APPLIANCES FOR WIND RESISTANCE AS WELL AS SUPPORTING
 DOCUMENTATION SHOWING THE APPLIANCES THEMSELVES ARE
 DESIGNED TO RESIST THE ANTICIPATED WIND PRESSURES IN
 ACCORDANCE WITH THIS SECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-06-12 Cont ID  
Sent By kstevens Date 2009-05-08 Time 13:33 Rev Time 0.00
Received By kstevens Date 2009-05-08 Time 13:33 Sent To  
Notes
2009-05-08 14:19:56ATTACHMENT "J" FRESH AIR INLET COVER NOT APPROVED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-02-26 Cont ID  
Sent By kstevens Date 2009-02-26 Time 10:31 Rev Time 0.00
Received By kstevens Date 2009-02-26 Time 10:31 Sent To  
Notes
2009-02-26 11:03:00DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS IR1.3, IR1.4 & IR99.1 THE FOLLOWING INFORMATION
 IS MISSING FROM THE TITLE BLOCKS OF EACH SHEET. THE
 FIRM LICENSE NUMBER, (CERTIFICATE OF AUTHROIZATION),
 AND THE PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT. FAC 61G1-16.004(2)(6) & FS 481.306.
  
 2. SHTS A9.1 THRU A9.8 THE FOLLOWING INFORMATION IS
 MISSING FROM THE TITLE BLOCKS OF EACH SHEET. THE
 PRINTED NAME OF THE PERSON SEALING THE DOCUMENT. FAC
 61G1-16.004(6) & FS 481.2055.
  
 3. SHT A9.1 PER TABLE 403.1 A DRINKING FOUNTAIN AND A
 SERVICE SINK ARE REQUIRED FOR THE "F" OCCUPANCY. PLEASE
 INDICATE THE LOCATION OF EACH REQUIRED FIXTURE.
  
 4. SHTS A9.1 & A9.2 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ___LAV:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
 ___FOR TOILET ROOM:
 A. 11-4.22.3 TURNING AREA
  
 5. SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 6. SHTS M0.1 THRU M9.3 THE FOLLOWING INFORMATION IS
 MISSING FROM THE TITLE BLOCKS OF EACH SHEET. THE
 PRINTED NAME AND LICENSE NUMBER OF THE PERSON SEALING
 THE DOCUMENT. FAC 61G15-23.002(2) & FS 471.025.
  
 7. SHTS M9.2 & M9.3 INDICATES THE VENT FOR THE SANITARY
 PIPING AS A FRESH AIR INTAKE. THIS IS NOT CORRECT AS IT
 IS NOT A FRESH AIR INTAKE. PLEASE CLARIFY. SECTIONS
 106.1.1
  
 8. SHTS M9.2 PLUMBING PLAN & M9.3 SANITARY RISER
 DIAGRAM. THE VENT OFFSET BELOW THE FLOOR IS NOT
 APPROVED AT THE WATER CLOSET, NOR AT THE FLOOR DRAIN IN
 THE GENERATOR ROOM. SECTION 905.4. EVERY DRY VENT SHALL
 RISE VERTICALLY TO A MINIMUM OF 6 INCHES ABOVE THE
 FLOOD LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE
 SERVED.
  
 9. SUBMIT A SANITARY RISER DIAGRAM FOR THE FLOOR DRAINS
 IN THE GENERATOR ROOM AND THE PUMP ROOM. SHOW ALL PIPE
 SIZES, TRAPS AND VENTS. SECTION 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-05-21 Cont ID  
Sent By jroach Date 2009-05-21 Time 18:52 Rev Time 0.00
Received By jroach Date 2009-05-21 Time 18:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-24 Cont ID  
Sent By jroach Date 2009-02-24 Time 19:07 Rev Time 0.00
Received By jroach Date 2009-02-24 Time 19:07 Sent To  
Notes
2009-02-24 19:15:37ZONING PLAN REVIEW
  
 PERMIT NO.: 09020294
 ADDRESS: 4325 HAVERHILL ROAD
 CONTRACTOR/CONTACT: GREG SHAW
 TELEPHONE NO.: (561) 632-8715
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) AS SUBMITTED AND APPROVED AS PART OF THE CLASS A
 SPECIAL USE PERMIT, PLEASE PROVIDE A DETAILED SITE PLAN
 IDENTIFYING ALL IMPROVEMENTS, DIMENSIONS, SETBACKS, AS
 WELL AS TABULAR DATA INDICATING LANDSCAPE AREA,
 STRUCTURE HEIGHT, ETC. PLEASE REFER TO THE ATTACHED
 COPY OF THE APPROVED SITE PLAN.
  
 2) THE PAVING/GRADING/DRAINAGE PLANS, AS WELL AS THE
 LANDSCAPE PLANS, DO NOT MATCH WHAT WAS APPROVED BY THE
 CITY COMMISSION AS PART OF THE CLASS A SPECIAL USE
 PERMIT. PLEASE CONTACT ME REGARDING THIS COMMENT IF
 MODIFICATIONS ARE BEING MADE FROM WHAT WAS APPROVED.
  
 3) PLEASE PROVIDE A COPY OF THE APPROVED TREE
 ALTERATION PERMIT. CONTACT ROBERT KUSSNER, LANDSCAPE
 PLANNER, AT (561) 822-1462 TO OBTAIN A COPY.
  
 4) PLEASE IDENTIFY ALL IMPROVEMENTS ON THE SITE PLAN
 (I.E. WHAT ARE THE "INDIVIDUAL BLACK DOTS" SHOWN ON THE
 PAVING/GRADING/DRAINAGE PLANS SURROUNDING THE RECLAIMED
 WATER PUMP STATION?...ARE THESE BOLLARDS?).
  
 5) PLEASE PROVIDE THE OVERALL HEIGHT OF ALL
 FACILITIES/STRUCTURES, AS WELL AS LABEL AND NOTE THE
 HEIGHT OF ALL APPURTENANCES ON TOP OF ALL OF THE
 FACILITIES.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  