Plan Review Details - Permit 09020254
Plan Review Stops For Permit 09020254
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-28 Cont ID  
Sent By mawillia Date 2009-07-29 Time 14:02 Rev Time 0.50
Received By jwitmer Date 2009-07-28 Time 11:00 Sent To  
Notes
2009-07-28 11:31:32PERMIT# 09070020

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-23 Cont ID  
Sent By mjacobs Date 2009-02-23 Time 09:49 Rev Time 0.00
Received By mjacobs Date 2009-02-23 Time 09:49 Sent To  
Notes
2009-02-23 09:49:17BUILDING PLAN REVIEW
 PERMIT: 09020254
 ADD: 6246 45TH STREET
 CONT:?
 TEL: (813)843-1605
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4) (2004 FBC) 106.1 2004 FBC 1609.1.3 PLEASE PROVIDE
 INFORMATION ON THE ANCHORAGE THE GENERATOR TO RESIST
 THE MOMENT OF OVERTURNING, UPLIFT AND SLIDING. THE
 ANCHORAGE DESIGN SHALL BE PER ASCE 7-02 1603.1.4.
  
 5) GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE
 SIZE OF GENERATOR(WXL), PLUS PROVIDE PLANS WITH THE
 INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.
  
 6) PROVIDE PLANS ENOUGH TO VERIFY LOCATION OF GENERATOR
 VERSES BUILDING OPENINGS WINDOWS, DOORS OR SOFFIT TYPE
 VENTS, ETC.
  
 7) THE WIND SPEED INFORMATION INDICATED ON THE PLANS
 STATES 130MPH. WEST PALM BEACH IS LOCATED IN THE 140MPH
 REGION PER FIGURE1609. CORRECT THE WIND LOAD
 INFORMATION TO SHOW THE CORRECT INFORMATION.
  
 8) INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE & EXTENT OF THE WORK PROPOSED &
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, AND RULES
 AND REGULATIONS AS DETERMINED BY THE BUILDING OFFICIAL.
  
 NOTE: A PERMIT WILL NOT BE ISSUED UNTIL A CERTIFIED
 CONTRACTOR IS SIGNED ON THE APPLICATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-17 Cont ID  
Sent By btrobaug Date 2009-07-17 Time 10:12 Rev Time 0.00
Received By btrobaug Date 2009-07-17 Time 09:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-06 Cont ID  
Sent By btrobaug Date 2009-03-06 Time 13:38 Rev Time 0.00
Received By btrobaug Date 2009-03-06 Time 10:57 Sent To I
Notes
2009-03-06 13:18:49 
  
 APPLICATION #09020254 ELECTRICAL PLAN REVIEW
 6246 45TH STREET 3/6/09
 WEST PALM BEACH, FL.
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} REGARDING NOTE #2 SHEET E-1 THE FOLLOWING IS
 REQUIRED- 700.8 (A) EMERGENCY SOURCES A SIGN SHALL BE
 PLACED AT THE SERVICE ENTRANCE EQUIPMENT, INDICATING
 TYPE AND LOCATION OF ON-SITE EMERGENCY POWER SOURCES.
 NOTE THE SAME ON THE PLAN.
  
 2} THE EXISTING BONDING CONDUCTOR BETWEEN THE METER AND
 THE SERVICE DISCONNECT SHOWN ON THE ONE LINE DIAGRAM,
 SHEET E-1, PARALLELS THE GROUNDED CONDUCTOR (NEUTRAL)
 AND CREATES A PARALLEL PATH IN VIOLATION OF 250.6 (B).
 THE BOND WOULD BE ALLOWED IF THE NEUTRAL IS ISOLATED
 FROM THE METER ENCLOSURE. VERIFY CONNECTIONS. ALTHOUGH
 THE SERVICE IS SHOWN AS EXISTING, THIS VIOLATION MUST
 BE CORRECTED AS IT IS A LIFE SAFETY ISSUE. THERE IS A
 POTENTIAL OF ENERGIZING ALL METAL PARTS AND EQUIPMENT
 THE EQUIPMENT GROUNDS ARE CONNECTED TO.
  
  
 3} THE ELECTRICAL CONSTRUCTION SPECIFICATIONS ON E-1
 REFERENCE THE 2006 REVISIONS TO THE FBC, THE 2007 ARE
 IN EFFECT AS OF 7/1/07. ALSO THE 2006 VERSION OF
 NFPA-101 HAS BEEN ADOPTED BY THE STATE FIRE MARSHAL AS
 OF 1/1/09, CORRECT REFERENCES.
  
 4} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR AND ATS. 106.1 FBC AS AMENDED.
  
 5} SHEET E-2 GROUNDING PLAN DETAIL STATES THAT THE
 PROPOSED GENERATOR IS 60 KW. CORRELATE WITH SHEET E-1.
  
 6} THE GENERAL GROUNDING NOTES, SHEET E-2, NOTE #5,
 INDICATES THE SYSTEM MUST BE INSPECTED BY THE
 CONSTRUCTION MANAGER PRIOR TO BACKFILL. IT SHOULD ALSO
 BE NOTED THAT AN INSPECTION BY THE CITY OF WEST PALM
 BEACH ELECTRICAL INSPECTOR IS ALSO REQUIRED PRIOR TO
 BACKFILL.
  
 7} PROVIDE A PANEL SCHEDULES FOR ALL PANELS BEING FED
 FROM THE GENERATOR SO A DETERMINATION CAN BE MADE IF
 THIS IS AN OPTIONAL OR LEGALLY REQUIRED SYSTEM. 215.5
 NEC
  
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-29 Cont ID  
Sent By mawillia Date 2009-07-29 Time 14:02 Rev Time 0.00
Received By mawillia Date 2009-07-29 Time 13:51 Sent To B
Notes
2009-07-29 14:02:02*****APPOROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEET E-1 (OF THE PLAN SET) WAS
 STAMPED, INITIALED, OR DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-03-04 Cont ID  
Sent By mwennerg Date 2009-03-04 Time 14:31 Rev Time 0.00
Received By mwennerg Date 2009-03-04 Time 14:31 Sent To  
Notes
2009-03-04 14:37:12***DENIED***
  
 1) WORK TO COMPLY WITH THE FLORIDA FIRE PREVENTION
 CODE, 2007 COMPRISING OF NFPA 101, 2006 AND NFPA 1,
 2006. THIS CURRENT EDITION WAS ADOPTED ON DECEMBER 31,
 2008.
  
 2) ILLUSTRATE THE LOCATION OF THE GENERATOR AND
 ASSOCIATED EQUIPMENT AND EXHAUST TERMINUS AS IT RELATES
 TO MEANS OF EGRESS AND BUILDING OPENINGS.
  
 3) PROVIDE INFORMATION INDICATING WHAT LIFE SAFETY
 EQUIPMENT WILL BE CONNECTED TO THE GENERATOR.
  
 4) IN ADDITION TO OTHER APPLICABLE LISTED CODES, WORK
 TO COMPLY WITH NFPA 30, 2003.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-29 Cont ID  
Sent By btrobaug Date 2009-07-17 Time 09:10 Rev Time 0.00
Received By lmartine Date 2009-07-06 Time 10:06 Sent To  
Notes
2009-07-06 10:06:53C-27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-06 Cont ID  
Sent By btrobaug Date 2009-03-06 Time 13:38 Rev Time 0.00
Received By btrobaug Date 2009-02-13 Time 10:47 Sent To PC
Notes
2009-02-13 10:53:36TO "BOB"#5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-28 Cont ID  
Sent By rregueir Date 2009-07-28 Time 16:36 Rev Time 0.00
Received By rregueir Date 2009-07-28 Time 16:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-03-04 Cont ID  
Sent By rregueir Date 2009-03-04 Time 13:23 Rev Time 0.00
Received By rregueir Date 2009-03-04 Time 13:05 Sent To  
Notes
2009-03-04 13:21:34REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2007 CODE FAMILY W/ 2009 REVISIONS
  
  
 1. THE SCOPE OF WORK AS STATED ON THE PLANS IS UNCLEAR.
 IN SOME LOCATIONS THE PLANS REFERENCE THE INSTALLATION
 OF A 30KW GENERATOR WHILE OTHERS REFERENCE A 60 KW
 GENERATOR. WHICH IS CORRECT? PLEASE CLARIFY AND
 COORDINATE PLANS IN ACCORDANCE WITH FBC-B 106.1.1 AND
 FBC-M 304.1.
  
 2. NO SUBMITTAL DATA WAS PROVIDED FOR THE PROPOSED
 GENERATOR OR FUEL STORAGE SYSTEM. PROVIDE SUBMITTAL
 DATA FOR THE PROPOSED GENERATOR AND FUEL STORAGE.
 GENERATOR AND FUEL STORAGE SHALL BE IN COMPLIANCE WITH
 FBC-M SECTION 915.
  
 3. PLEASE UPDATE ALL REFERENCED CODES ON THE PLANS.
 THERE HAS BEEN NO APPLICATION FOR PERMIT SUBMITTED AT
 THIS TIME. ANY APPLICATION FOR PERMIT SUBMITTED AFTER
 MARCH 1, 2009 IS SUBJECT TO THE REQUIREMENTS OF THE
 2007 FLORIDA BUILDING CODE WITH 2009 REVISIONS. IN
 ADDITION, THE 2007 FLORIDA FIRE PREVENTION CODE IS IN
 EFFECT AS OF DECEMBER 31, 2008. PLEASE CORRECT THESE
 AND ALL OTHER REFERENCED CODES AND STANDARDS ON THE
 PLANS.
  
 NOTE: THE SIZE OF THE FUEL TANK FOR THE PROPOSED
 GENERATOR IS NOT KNOWN AT THIS TIME. ANY ABOVE GROUND
 FUEL TANK INSTALLATION >550 GALLONS MUST BE APPROVED BY
 THE PALM BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL
 RESOURCE MANAGEMENT (DERM). IF THE PROPSED FUEL TANK
 EXCEEDS 550 GALLONS, PLANS SHALL BE APPROVED BY PBC
 DERM PRIOR TO SUBMISSION TO THE CITY FOR PERMIT. FOR
 MORE INFORMATION PLEASE VISIT
 HTTP://WWW.PBCGOV.COM/ERM/
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-02-27 Cont ID  
Sent By kstevens Date 2009-02-27 Time 16:20 Rev Time 0.00
Received By kstevens Date 2009-02-27 Time 16:20 Sent To  
Notes
2009-02-27 16:20:42NO PLUMBING/GAS SHOWN ON PLANS.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-07-15 Cont ID  
Sent By kdfreema Date 2009-07-15 Time 11:00 Rev Time 0.00
Received By kdfreema Date 2009-07-15 Time 11:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-18 Cont ID  
Sent By kdfreema Date 2009-02-18 Time 09:43 Rev Time 0.00
Received By kdfreema Date 2009-02-18 Time 09:43 Sent To  
Notes
2009-02-18 10:30:12***FAILED***
  
 1. VICNINITY MAP DOES NOT DEPICT THE ACTUAL PROJECT
 LOCATION, PLEASE CORRECT IT.
  
 2. THE PARCEL CONTROL NUMBER (PCN) INCLUDED WITH THE
 APPLICATION IS FOR 515 NORTH FLAGLER DRIVE. THE PCN FOR
 THIS PROPERTY IS 74-42-43-03-00-000-3010.
  
 3. THE ADDRESS ON FILE FOR THIS PROPERTY IS 6650 45TH
 STREET, NOT 6246 AS SHOWN ON THE APPLICATION.
  
 4. PROVIDE TWO (2) COPIES OF THE SURVEY REFERENCED IN
 THE DESCRIPTION OF THE LEASE AREA (ADVANCED LAND
 SURVEYING AND MAPPING DATED 10-18-06). IF A MORE RECENT
 SURVEY EXISTS, PLEASE INCLUDE THAT SURVEY INSTEAD.
  
 5. PURSUANT TO SEC. 94-444(B) OF THE ZONING CODE, THE
 GENERATOR SHALL BE SCREENED WITH AN OPAQUE WALL/FENCE
 AND HEDGE.
  
 6. SEC. 94-441(C)(2) OF THE ZONING CODE REQUIRES THAT
 PROPERTIES WHICH ARE IMPROVED BEYOND 50 PERCENT OF THE
 VALUE OF THE STRUCTURE ON THE PROPERTY ARE REQUIRED TO
 COMPLY WITH THE LANDSCAPE CODE. THE PBC PROPERTY
 APPRAISER PLACES AN IMPROVEMENT VALUE OF APPROXIMATELY
 $101,000 ON THE PROPERTY. WITHIN THE LAST MONTH AT&T
 HAS CONSTRUCTED A GENERATOR TO POWER THEIR FACILITIES
 AT THIS LOCATION. THE COMBINED PERMIT VALUES OF BOTH
 PROJECTS EXCEEDS 50 PERCENT OF THE IMPROVEMENT VALUE ON
 THE PROPERTY AND, AS SUCH, THE PROPERTY NEEDS TO BE
 BROUGHT UP TO COMPLIANCE WITH THE CITY'S LANDSCAPE
 REQUIREMENTS.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1458
 OR [email protected] WITH QUESTIONS OR TO SCHEDULE A
 MEETING TO DISCUSS POSSIBLE SOLUTIONS.