| Plan Review Stops For Permit 09020254 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-07-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-07-29 |
Time |
14:02 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2009-07-28 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2009-07-28 11:31:32 | PERMIT# 09070020 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-02-23 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-02-23 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-02-23 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2009-02-23 09:49:17 | BUILDING PLAN REVIEW | | | PERMIT: 09020254 | | | ADD: 6246 45TH STREET | | | CONT:? | | | TEL: (813)843-1605 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER | | | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 SUPPLEMENTS. | | | | | | 4) (2004 FBC) 106.1 2004 FBC 1609.1.3 PLEASE PROVIDE | | | INFORMATION ON THE ANCHORAGE THE GENERATOR TO RESIST | | | THE MOMENT OF OVERTURNING, UPLIFT AND SLIDING. THE | | | ANCHORAGE DESIGN SHALL BE PER ASCE 7-02 1603.1.4. | | | | | | 5) GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE | | | SIZE OF GENERATOR(WXL), PLUS PROVIDE PLANS WITH THE | | | INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF | | | FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE | | | REQUIRES WITHOUT LOAD REDUCTION. | | | | | | 6) PROVIDE PLANS ENOUGH TO VERIFY LOCATION OF GENERATOR | | | VERSES BUILDING OPENINGS WINDOWS, DOORS OR SOFFIT TYPE | | | VENTS, ETC. | | | | | | 7) THE WIND SPEED INFORMATION INDICATED ON THE PLANS | | | STATES 130MPH. WEST PALM BEACH IS LOCATED IN THE 140MPH | | | REGION PER FIGURE1609. CORRECT THE WIND LOAD | | | INFORMATION TO SHOW THE CORRECT INFORMATION. | | | | | | 8) INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION | | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | | THE LOCATION, NATURE & EXTENT OF THE WORK PROPOSED & | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS | | | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, AND RULES | | | AND REGULATIONS AS DETERMINED BY THE BUILDING OFFICIAL. | | | | | | NOTE: A PERMIT WILL NOT BE ISSUED UNTIL A CERTIFIED | | | CONTRACTOR IS SIGNED ON THE APPLICATION. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | PHONE (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-07-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-07-17 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-07-17 |
Time |
09:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-03-06 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-03-06 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-03-06 |
Time |
10:57 |
Sent To |
I |
|
| Notes |
| 2009-03-06 13:18:49 | | | | | | | APPLICATION #09020254 ELECTRICAL PLAN REVIEW | | | 6246 45TH STREET 3/6/09 | | | WEST PALM BEACH, FL. | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} REGARDING NOTE #2 SHEET E-1 THE FOLLOWING IS | | | REQUIRED- 700.8 (A) EMERGENCY SOURCES A SIGN SHALL BE | | | PLACED AT THE SERVICE ENTRANCE EQUIPMENT, INDICATING | | | TYPE AND LOCATION OF ON-SITE EMERGENCY POWER SOURCES. | | | NOTE THE SAME ON THE PLAN. | | | | | | 2} THE EXISTING BONDING CONDUCTOR BETWEEN THE METER AND | | | THE SERVICE DISCONNECT SHOWN ON THE ONE LINE DIAGRAM, | | | SHEET E-1, PARALLELS THE GROUNDED CONDUCTOR (NEUTRAL) | | | AND CREATES A PARALLEL PATH IN VIOLATION OF 250.6 (B). | | | THE BOND WOULD BE ALLOWED IF THE NEUTRAL IS ISOLATED | | | FROM THE METER ENCLOSURE. VERIFY CONNECTIONS. ALTHOUGH | | | THE SERVICE IS SHOWN AS EXISTING, THIS VIOLATION MUST | | | BE CORRECTED AS IT IS A LIFE SAFETY ISSUE. THERE IS A | | | POTENTIAL OF ENERGIZING ALL METAL PARTS AND EQUIPMENT | | | THE EQUIPMENT GROUNDS ARE CONNECTED TO. | | | | | | | | | 3} THE ELECTRICAL CONSTRUCTION SPECIFICATIONS ON E-1 | | | REFERENCE THE 2006 REVISIONS TO THE FBC, THE 2007 ARE | | | IN EFFECT AS OF 7/1/07. ALSO THE 2006 VERSION OF | | | NFPA-101 HAS BEEN ADOPTED BY THE STATE FIRE MARSHAL AS | | | OF 1/1/09, CORRECT REFERENCES. | | | | | | 4} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE | | | GENERATOR AND ATS. 106.1 FBC AS AMENDED. | | | | | | 5} SHEET E-2 GROUNDING PLAN DETAIL STATES THAT THE | | | PROPOSED GENERATOR IS 60 KW. CORRELATE WITH SHEET E-1. | | | | | | 6} THE GENERAL GROUNDING NOTES, SHEET E-2, NOTE #5, | | | INDICATES THE SYSTEM MUST BE INSPECTED BY THE | | | CONSTRUCTION MANAGER PRIOR TO BACKFILL. IT SHOULD ALSO | | | BE NOTED THAT AN INSPECTION BY THE CITY OF WEST PALM | | | BEACH ELECTRICAL INSPECTOR IS ALSO REQUIRED PRIOR TO | | | BACKFILL. | | | | | | 7} PROVIDE A PANEL SCHEDULES FOR ALL PANELS BEING FED | | | FROM THE GENERATOR SO A DETERMINATION CAN BE MADE IF | | | THIS IS AN OPTIONAL OR LEGALLY REQUIRED SYSTEM. 215.5 | | | NEC | | | | | | PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE | | | SCOPE OF WORK PURPOSED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-07-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-07-29 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-07-29 |
Time |
13:51 |
Sent To |
B |
|
| Notes |
| 2009-07-29 14:02:02 | *****APPOROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED; PLAN SHEET E-1 (OF THE PLAN SET) WAS | | | STAMPED, INITIALED, OR DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-03-04 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-03-04 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-03-04 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2009-03-04 14:37:12 | ***DENIED*** | | | | | | 1) WORK TO COMPLY WITH THE FLORIDA FIRE PREVENTION | | | CODE, 2007 COMPRISING OF NFPA 101, 2006 AND NFPA 1, | | | 2006. THIS CURRENT EDITION WAS ADOPTED ON DECEMBER 31, | | | 2008. | | | | | | 2) ILLUSTRATE THE LOCATION OF THE GENERATOR AND | | | ASSOCIATED EQUIPMENT AND EXHAUST TERMINUS AS IT RELATES | | | TO MEANS OF EGRESS AND BUILDING OPENINGS. | | | | | | 3) PROVIDE INFORMATION INDICATING WHAT LIFE SAFETY | | | EQUIPMENT WILL BE CONNECTED TO THE GENERATOR. | | | | | | 4) IN ADDITION TO OTHER APPLICABLE LISTED CODES, WORK | | | TO COMPLY WITH NFPA 30, 2003. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-07-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-07-17 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-07-06 |
Time |
10:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-03-06 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-03-06 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-02-13 |
Time |
10:47 |
Sent To |
PC |
|
| Notes |
| 2009-02-13 10:53:36 | TO "BOB"#5 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-07-28 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-28 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-28 |
Time |
16:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-03-04 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-03-04 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-03-04 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2009-03-04 13:21:34 | REVIEW #: 1ST **PLAN CHECK ONLY** | | | ACTION: DENIED | | | | | | REVIEWED FOR COMPLIANCE WITH THE FOLLOWING: | | | FBC 2007 CODE FAMILY W/ 2009 REVISIONS | | | | | | | | | 1. THE SCOPE OF WORK AS STATED ON THE PLANS IS UNCLEAR. | | | IN SOME LOCATIONS THE PLANS REFERENCE THE INSTALLATION | | | OF A 30KW GENERATOR WHILE OTHERS REFERENCE A 60 KW | | | GENERATOR. WHICH IS CORRECT? PLEASE CLARIFY AND | | | COORDINATE PLANS IN ACCORDANCE WITH FBC-B 106.1.1 AND | | | FBC-M 304.1. | | | | | | 2. NO SUBMITTAL DATA WAS PROVIDED FOR THE PROPOSED | | | GENERATOR OR FUEL STORAGE SYSTEM. PROVIDE SUBMITTAL | | | DATA FOR THE PROPOSED GENERATOR AND FUEL STORAGE. | | | GENERATOR AND FUEL STORAGE SHALL BE IN COMPLIANCE WITH | | | FBC-M SECTION 915. | | | | | | 3. PLEASE UPDATE ALL REFERENCED CODES ON THE PLANS. | | | THERE HAS BEEN NO APPLICATION FOR PERMIT SUBMITTED AT | | | THIS TIME. ANY APPLICATION FOR PERMIT SUBMITTED AFTER | | | MARCH 1, 2009 IS SUBJECT TO THE REQUIREMENTS OF THE | | | 2007 FLORIDA BUILDING CODE WITH 2009 REVISIONS. IN | | | ADDITION, THE 2007 FLORIDA FIRE PREVENTION CODE IS IN | | | EFFECT AS OF DECEMBER 31, 2008. PLEASE CORRECT THESE | | | AND ALL OTHER REFERENCED CODES AND STANDARDS ON THE | | | PLANS. | | | | | | NOTE: THE SIZE OF THE FUEL TANK FOR THE PROPOSED | | | GENERATOR IS NOT KNOWN AT THIS TIME. ANY ABOVE GROUND | | | FUEL TANK INSTALLATION >550 GALLONS MUST BE APPROVED BY | | | THE PALM BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL | | | RESOURCE MANAGEMENT (DERM). IF THE PROPSED FUEL TANK | | | EXCEEDS 550 GALLONS, PLANS SHALL BE APPROVED BY PBC | | | DERM PRIOR TO SUBMISSION TO THE CITY FOR PERMIT. FOR | | | MORE INFORMATION PLEASE VISIT | | | HTTP://WWW.PBCGOV.COM/ERM/ | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2009-02-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-02-27 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-02-27 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2009-02-27 16:20:42 | NO PLUMBING/GAS SHOWN ON PLANS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2009-07-15 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2009-07-15 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2009-07-15 |
Time |
11:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-02-18 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2009-02-18 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2009-02-18 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2009-02-18 10:30:12 | ***FAILED*** | | | | | | 1. VICNINITY MAP DOES NOT DEPICT THE ACTUAL PROJECT | | | LOCATION, PLEASE CORRECT IT. | | | | | | 2. THE PARCEL CONTROL NUMBER (PCN) INCLUDED WITH THE | | | APPLICATION IS FOR 515 NORTH FLAGLER DRIVE. THE PCN FOR | | | THIS PROPERTY IS 74-42-43-03-00-000-3010. | | | | | | 3. THE ADDRESS ON FILE FOR THIS PROPERTY IS 6650 45TH | | | STREET, NOT 6246 AS SHOWN ON THE APPLICATION. | | | | | | 4. PROVIDE TWO (2) COPIES OF THE SURVEY REFERENCED IN | | | THE DESCRIPTION OF THE LEASE AREA (ADVANCED LAND | | | SURVEYING AND MAPPING DATED 10-18-06). IF A MORE RECENT | | | SURVEY EXISTS, PLEASE INCLUDE THAT SURVEY INSTEAD. | | | | | | 5. PURSUANT TO SEC. 94-444(B) OF THE ZONING CODE, THE | | | GENERATOR SHALL BE SCREENED WITH AN OPAQUE WALL/FENCE | | | AND HEDGE. | | | | | | 6. SEC. 94-441(C)(2) OF THE ZONING CODE REQUIRES THAT | | | PROPERTIES WHICH ARE IMPROVED BEYOND 50 PERCENT OF THE | | | VALUE OF THE STRUCTURE ON THE PROPERTY ARE REQUIRED TO | | | COMPLY WITH THE LANDSCAPE CODE. THE PBC PROPERTY | | | APPRAISER PLACES AN IMPROVEMENT VALUE OF APPROXIMATELY | | | $101,000 ON THE PROPERTY. WITHIN THE LAST MONTH AT&T | | | HAS CONSTRUCTED A GENERATOR TO POWER THEIR FACILITIES | | | AT THIS LOCATION. THE COMBINED PERMIT VALUES OF BOTH | | | PROJECTS EXCEEDS 50 PERCENT OF THE IMPROVEMENT VALUE ON | | | THE PROPERTY AND, AS SUCH, THE PROPERTY NEEDS TO BE | | | BROUGHT UP TO COMPLIANCE WITH THE CITY'S LANDSCAPE | | | REQUIREMENTS. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1458 | | | OR [email protected] WITH QUESTIONS OR TO SCHEDULE A | | | MEETING TO DISCUSS POSSIBLE SOLUTIONS. |
|
|