| 2009-02-25 11:20:25 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON THE PLANS. THE PLANS MUST LIST THE ACTUAL DESIGN |
| | DOCUMENTS. |
| | 2004 FBC W/2007 REVISIONS |
| | 2005 NFPA-70 |
| | |
| | ** PLEASE BE AWARE THAT THE PLANS ALSO STATE PALM BEACH |
| | COUNTY AMENDMENTS HOWEVER THE SCOPE OF WORK AS APPLIED |
| | IS LOCATED IN THE CITY OF WEST PALM BEACH. PLEASE |
| | ADJUST NOTES. |
| | |
| | 2) NOTE: NOTES ON ELECTRICAL PLANS STATE TO SEE |
| | DIVISION 16 SPECIFICATIONS. WILL THESE BE PART OF THE |
| | RECORD DOCUMENTS? WILL ANY MINIMUM CODE COMPLIANCE |
| | ITEMS BE PART OF THE SPECS? |
| | FBC 106.1, NEC 2005. |
| | PLEASE KNOW THAT ANY NEW WIRING WOULD BE REQUIRED TO BE |
| | COLOR CODE PER AHJ FOR 277/480V SYSTEMS. BROWN, PURPLE, |
| | YELLOW. |
| | THE NEC DOES NOT PROVIDE COLOR CODING OF SYSTEMS. AS |
| | THE NEC DOES STATE ORANGE SHALL BE USED FOR HIGH-LEG |
| | DELTA SYSTEMS THIS IS NOT THE SAME FOR 277/480V. |
| | PLEASE CALL TO GO OVER FOR ANY QUESTIONS. IN KEEPING |
| | WITH EXISTING SYSTEMS IN THIS JURISDICTION BASED ON |
| | PREVIOUS TECHNICAL AMENDMENTS THESE COLORS WILL BE |
| | REQUIRED FOR NEW WIRING METHODS AS STATED. 90.4. |
| | PLEASE ADJUST NOTES TO INCLUDE COLOR CODING. |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |