Plan Review Details - Permit 09020234
Plan Review Stops For Permit 09020234
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-03-09 Cont ID  
Sent By lmartine Date 2009-03-09 Time 14:32 Rev Time 0.00
Received By lmartine Date 2009-03-09 Time 14:32 Sent To  
Notes
2009-03-09 14:34:16JIM WITMER APPROVED, SEE SHEET C5-1

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-16 Cont ID  
Sent By dpalmer Date 2009-04-16 Time 16:36 Rev Time 0.00
Received By dpalmer Date 2009-04-16 Time 16:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-25 Cont ID  
Sent By dpalmer Date 2009-02-25 Time 11:20 Rev Time 0.00
Received By dpalmer Date 2009-02-25 Time 11:20 Sent To  
Notes
2009-02-25 11:20:25** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON THE PLANS. THE PLANS MUST LIST THE ACTUAL DESIGN
 DOCUMENTS.
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70
  
 ** PLEASE BE AWARE THAT THE PLANS ALSO STATE PALM BEACH
 COUNTY AMENDMENTS HOWEVER THE SCOPE OF WORK AS APPLIED
 IS LOCATED IN THE CITY OF WEST PALM BEACH. PLEASE
 ADJUST NOTES.
  
 2) NOTE: NOTES ON ELECTRICAL PLANS STATE TO SEE
 DIVISION 16 SPECIFICATIONS. WILL THESE BE PART OF THE
 RECORD DOCUMENTS? WILL ANY MINIMUM CODE COMPLIANCE
 ITEMS BE PART OF THE SPECS?
 FBC 106.1, NEC 2005.
 PLEASE KNOW THAT ANY NEW WIRING WOULD BE REQUIRED TO BE
 COLOR CODE PER AHJ FOR 277/480V SYSTEMS. BROWN, PURPLE,
 YELLOW.
 THE NEC DOES NOT PROVIDE COLOR CODING OF SYSTEMS. AS
 THE NEC DOES STATE ORANGE SHALL BE USED FOR HIGH-LEG
 DELTA SYSTEMS THIS IS NOT THE SAME FOR 277/480V.
 PLEASE CALL TO GO OVER FOR ANY QUESTIONS. IN KEEPING
 WITH EXISTING SYSTEMS IN THIS JURISDICTION BASED ON
 PREVIOUS TECHNICAL AMENDMENTS THESE COLORS WILL BE
 REQUIRED FOR NEW WIRING METHODS AS STATED. 90.4.
 PLEASE ADJUST NOTES TO INCLUDE COLOR CODING.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2009-04-23 Cont ID  
Sent By efabian Date 2009-04-23 Time 10:18 Rev Time 0.00
Received By efabian Date 2009-04-23 Time 10:18 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2009-03-05 Cont ID  
Sent By mgonzale Date 2009-03-05 Time 10:03 Rev Time 1.00
Received By mgonzale Date 2009-03-05 Time 10:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-08 Cont ID  
Sent By adarroug Date 2009-04-08 Time 15:29 Rev Time 0.00
Received By adarroug Date 2009-04-08 Time 15:29 Sent To  
Notes
2009-04-08 15:29:33TO "C15"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-09 Cont ID  
Sent By lmartine Date 2009-03-09 Time 14:34 Rev Time 0.00
Received By lmartine Date 2009-02-13 Time 08:49 Sent To  
Notes
2009-02-13 09:01:10TO "COMM" BD#3

Review Stop Z ZONING
Rev No 2 Status P Date 2009-04-15 Cont ID  
Sent By jroach Date 2009-04-15 Time 11:31 Rev Time 0.00
Received By jroach Date 2009-04-15 Time 11:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-24 Cont ID  
Sent By jroach Date 2009-02-24 Time 19:16 Rev Time 0.00
Received By jroach Date 2009-02-24 Time 11:30 Sent To  
Notes
2009-02-24 19:19:38ZONING PLAN REVIEW
  
 PERMIT NO.: 09020234
 ADDRESS: 4325 HAVERHILL ROAD
 CONTRACTOR/CONTACT: EDWARD MCCULLERS
 TELEPHONE NO.: (239) 489-4444
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) SCREENING (I.E. HEDGE) SHALL BE PROVIDED AROUND ALL
 MONITORING WELLS....ESPECIALLY THOSE WELLS THAT WILL
 NOT BE SCREENED BY THE LANDSCAPING INSTALLED AS PART OF
 THE OVERAL ECR PROJECT.
  
 2) PLEASE CLARIFY WHETHER OR NOT THESE ARE "REPLACEMENT
 WELLS." THE PLANS NOTE "REPLACEMENT" WHILE THE PERMIT
 APPLICATION NOTES "NEW." ARE THESE WELLS EXISTING ON
 SITE?
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  