Plan Review Details - Permit 09020194
Plan Review Stops For Permit 09020194
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-07-28 Cont ID  
Sent By jwitmer Date 2009-07-28 Time 13:55 Rev Time 0.80
Received By jwitmer Date 2009-07-28 Time 13:02 Sent To  
Notes
2009-07-28 13:34:44BUILDING PLAN REVIEW
 PERMIT: 09020194
 ADD: 309 CLEMATIS ST.
 CONT: PLAN REVIEW / VON ESSELBORN
 TEL: (561)951-6729
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 2) MISSING ARCHITECTURAL SHEETS, THERE IS NO
 INFORMATION ON THE KITCHEN AS TO FLOOR, WALL NOR
 CEILING FINISHES, THICKNESS OF FINSIHES NOR FIRE RAING
 OF FINISHES.
 106.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS:
 (5) FIRE SUPRESSION SYSTEMS
 (9) ROOF/ WALL & FLOOR INSULATION
 (11) INTERIOR REQUIREMENTS SHALL INCLUDE FLAME SPREAD
 AND SMOKE DEVELOPMENT
 LIGHT AND VENTILATION
 (12) SPECIAL SYSTEMS: POSIBLE LIFTS
  
 3) MASTER PLAN 08060519 SHEET A-8.1 INDICATES FUTURE
 ROOF EXHAUST FAN, NO INFORMATION WAS SUBMITTED FOR THE
 ROOF CURB, FAN EXHAUST ASSEMBLY, FOR WIND. PLEASE
 SSUBMIT STRUCTURAL INFORMATION HOW THE FAN WILL BE
 ATTACHED TO THE STRUCTURAL COMPONENTS OF THE BUILDING.
 COMPONENTS AND CLADDING. 106.3.5.1.1(8) STRUCTURAL
 REQUIREMENTS.
  
 4) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 4A) EXHAUST FANS
 4B) PRE-MANUFACTURED A/C STANDS
  
 301.13 FBC MECHANICAL. WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 5) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-06 Cont ID  
Sent By shill Date 2009-03-06 Time 09:01 Rev Time 0.00
Received By shill Date 2009-03-06 Time 09:01 Sent To  
Notes
2009-03-06 09:12:49****CORRECTIONS****
 ****PLAN CHECK ONLY****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. NO BUILDING PLANS SUBMITTED. HOWEVER, COVER SHEET
 PROVIDES BUILDING INFORMATION AND STATES THAT THIS AREA
 IS "PROPOSED" BUT CALLS THE OPEN AIR DINING AREA AND
 GAZEBO DINING AREA "EXISTING." ISN'T THIS KITCHEN AREA
 UNDER THE SAME STATUS AS THE OPEN AIR DINING AND GAZEBO
 DINING; STRUCTURE PERMITTED AND THE BUILDOUT IN PLAN
 REVIEW? AS STATED, THIS APPEARS TO BE AN ADDITION.
  
 2. GOVERNING CODE EFFECTIVE MARCH 1, 2009 IS FBC2007
 WITH 2009 SUPPLEMENTS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-12 Cont ID  
Sent By btrobaug Date 2009-03-12 Time 10:03 Rev Time 0.00
Received By btrobaug Date 2009-03-10 Time 15:34 Sent To  
Notes
2009-03-12 10:03:42 
  
 THE ELECTRICAL PLANS APPEAR TO BE IN COMPLIANCE WITH
 THE 2005 NEC. THE REVIEW WILL BE CHANGED FROM FAIL TO
 PASS PENDING A CONTRACTOR APPLYING FOR A PERMIT WITH
 THE SAME PLANS. NOTE THE 2007 FBC BECAME EFFECTIVE
 3/1/09. THE 2005 NEC IS STILL IN EFFECT..
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-07 Cont ID  
Sent By mcarsill Date 2009-04-07 Time 15:47 Rev Time 0.00
Received By mcarsill Date 2009-04-07 Time 15:37 Sent To  
Notes
2009-04-07 15:47:11ROXY'S KITCHEN
 309 CLEMATIS STREET
 PERMIT NUMBER 09020194
  
 1. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF FIRE ALARM EQUIPMENT SHOWN ON PAGE E-2.
 SOME SMOKE DETECTORS SHOWN SHOULD BE REPLACED WITH HEAT
 DETECTORS DUE TO THEIR CLOSE PROXIMITY TO COOKING
 EQUIPMENT OR TO ITEMS THAT MAY PRODUCE STEAM.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE HOOD, DUCT, AND FIRE SUPPRESSION
 SYSTEM.
  
 3. PLEASE PROVIDE DETAILS ON THE GAS FIRE BOWLS SHOWN
 ON PAGE P-1. CUT SHEETS NEED TO BE PROVIDED ON THE
 DEVICES. WHAT SAFETY DEVICES ARE INSTALLED ON THESE
 BOWLS. ON APRIL 7, 2009, SPOKE TO WHITNEY OFFIELD
 REGARDING THESE FIRE BOWLS. SHE WILL ATTEMPT TO OBTAIN
 INFORMATION ON THESE.
  
 4. ON PAGE M-1 TWO DIFFERENT DUCT SIZES ARE SHOWN.
 PLEASE COORDINATE THE EXHAUST DUCT HOOD ELEVATION AND
 THE MECHANICAL PLAN DIAGRAM.
  
 5. THE EXHAUST FAN DISPLAYED ON PAGE M-1 SHALL BE
 PROPERLY SEPARATED FROM ANY DOORS, WINDOWS, AND
 PROPERTY LINES BY A MINIMUM OF AT LEAST 10 FEET.
  
 6. THE FIRE SUPPRESSION SYSTEM SHALL BE A WET CHEMICAL
 SYSTEM THAT COMPLIES WITH THE UL 300 STANDARD AND
 APPROPRIATE NFPA STANDARDS.
  
 7. THE MANUAL PULL STATION SHALL BE INSTALLED IN A
 MEANS OF EGRESS.
  
 8. NO HORIZONTAL OR VERTICAL PIPE PENETRATIONS ARE
 ALLOWED TO BE INSTALLED WITHIN STAIR # 2.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-03-12 Cont ID  
Sent By kstevens Date 2009-03-12 Time 11:55 Rev Time 0.00
Received By kstevens Date 2009-03-12 Time 11:55 Sent To  
Notes
2009-03-12 12:32:16DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 1. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A LISTED SHUT
 OFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH
 MP REGULATOR. SECTION 409.4. A UNION IS REQUIRED
 DOWNSTREAM OF THE SHUT OFF VALVE NEAR THE REGULATOR FOR
 SERVICING & REPLACEMENT.
  
 2. SHT P-2 GAS DISTRIBUTION ISOMETRIC. INDICATE THE
 TOTAL BTU'S FOR THE EXISTING KITCHEN & DISTANCE TO THE
 MOST REMOTE OUTLET IN THE KITCHEN ON THE RISER DIAGRAM.
 SECTION 106.1.2 MORE INFORMATION REQUIRED AND SECTION
 402 PIPE SIZING.
  
 3. SHT P-2 GAS DISTRIBUTION ISOMETRIC. NOTE REFERENCES
 GAS PIPE SIZE PER TABLE 402.4(20) P.E. PIPE. PLEASE
 INDICATE WHERE THE P.E. PIPE WILL BE INSTALLED. (P.E.
 FOR OUTDOOR UNDERGROUND ONLY). SECTION 404.14.1.
  
 4. SHT P-2 GAS DISTRIBUTION ISOMETRIC. PLEASE INDICATE
 GAS TYPE. (IF LP GAS MORE COMMENTS WILL BE
 FORTHCOMING).
  
 5. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A MANUAL SHUT
 OFF VALVE IS REQUIRED UPSTREAM OF THE EMERGENCY HOOD
 SHUT DOWN SHUT OFF VALVE.
  
 6. SHT P-2 GAS DISTRIBUTION ISOMETRIC. SUBMIT MANUF.
 SPECIFICATION SHEETS FOR THE UNIONS. INDICATE MODEL
 NUMBER AND SHOW BTU CAPACITY FOR TOTAL LOAD OF ALL
 APPLIANCES COMBINED. SECTION 410.2(1)(2)(3).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-04-07 Time   Rev Time 0.00
Received By adarroug Date 2009-02-12 Time 09:01 Sent To  
Notes
2009-02-12 09:02:17TO "COMM" BD#6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-03-26 Cont ID  
Sent By rregueir Date 2009-03-26 Time 09:04 Rev Time 0.00
Received By rregueir Date 2009-03-25 Time 20:40 Sent To  
Notes
2009-03-26 09:04:08REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THIS PLAN HAS BEEN REVIEWED FOR COMPLIANCE WITH THE
 ABOVE LISTED CODES. PLEASE MAKE THE FOLLOWING
 CORRECTIONS PRIOR TO RESUMITTING PLANS:
  
 1. WHAT IS THE DISTANCE OF THE KITCHEN EXHAUST FAN FROM
 ADJACENT BUILDING AND PROPERTY LINE? EXHAUST OUTLETS
 SHALL BE LOCATED NOT LESS THAN 10 FEET HORIZONTALLY
 FROM PARTS OF THE SAME OR CONTIGUOUS BUILDINGS,
 ADJACENT BUILDINGS, ADJACENT PROPERTY LINES AND AIR
 INTAKE OPENINGS INTO ANY BUILDING IN ACCORDANCE WITH
 FBC-M 506.3.12.3.
  
 2. TYPE I HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED
 TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER
 COOKING OPERATIONS OCCUR IN ACCORDANCE WITH FBC-M
 507.2.1.1. THE ACTIVATION OF THE EXHAUST FAN SHALL
 OCCUR THROUGH AN INTERLOCK WITH THE COOKING APPLIANCES,
 BY MEANS OF HEAT SENSORS OR BY MEANS OF OTHER APPROVED
 METHODS IN ACCORDANCE WITH THIS SECTION.
  
 3. FAN APPEARS TO BE NEXT TO THE ROOF EDGE. GUARDS
 SHALL BE PROVIDED WHERE FANS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET OF A ROOF
 EDGE IN ACCORDANCE WITH FBC-M 304.10. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES BEYOND EACH END OF THE
 FAN AND THE TOP OF THE GUARD SHALL BE LOCATED NOT LESS
 THAN 42 INCHES ABOVE THE ELEVATED SURFACE ADJACENT TO
 THE GUARD. THE GUARD SHALL BE CONSTRUCTED IN ACCORDANCE
 WITH THE REQUIREMENTS FOR GUARDS SPECIFIED IN THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4. THE PLAN SHOWS THE MANUAL PULL STATION (ACTUATION
 DEVICE) NEXT TO THE HOOD. THE MANUAL ACTUATION DEVICE
 SHALL BE LOCATED AT OR NEAR A MEANS OF EGRESS FROM THE
 COOKING AREA A MINIMUM OF 10 FEET AND A MAXIMUM OF 20
 FEET FROM THE KITCHEN EXHAUST SYSTEM IN ACCORDANCE WITH
 FBC-B 904.11.1. THE MANUAL ACTUATION DEVICE SHALL BE
 INSTALLED NOT MORE THAN 48 INCHES OR LESS THAN 42
 INCHES ABOVE THE FLOOR AND SHALL CLEARLY IDENTIFY THE
 HAZARD PROTECTED.
  
 5. EXHAUST FAN AND CURB SHALL BE DESIGNED AND INSTALLED
 FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12.
 PROVIDE MANUFACTURER???S DATA FOR FAN WIND RESISTANCE
 AND ATTACHMENT DETAIL FOR CURB-TO-BUILDING AND
 FAN-TO-CURB.
  
 6. PLAN SHOWS MAKE-UP AIR DUCTS FOR KITCHEN EXHAUST BUT
 THE SOURCE OF THE MAKE-UP AIR AND THE MAKE-UP AIR FAN
 ARE NOT SHOWN ON PLANS. THE EXHAUST AND MAKEUP AIR
 SYSTEMS SHALL BE ELECTRICALLY INTERLOCKED TO INSURE
 THAT MAKEUP AIR IS PROVIDED WHENEVER THE EXHAUST SYSTEM
 IS IN OPERATION. MAKEUP AIR INTAKE OPENING LOCATIONS
 SHALL COMPLY WITH SECTIONS 401.4 AND 401.4.1 IN
 ACCORDANCE WITH FBC-M 508.1.
  
 7. FLOOR PLAN SHOWS THE KITCHEN EXHAUST DUCT AS 12X12
 WHILE THE ELEVATION PLAN SHOWS THE EXHAUST DUCT AS
 10X12. WHICH IS CORRECT? PLEASE CLARIFY.
  
 8. THE ELEVATION PLAN CALLS FOR A 24X14 FIRE RATED
 CHASE FOR A 10X12 DUCT. THE ELEVATION PLAN REFERENCES
 ARCHITECTURAL PLAN FOR CHASE DETAIL. NO ARCHITECTURAL
 PLANS WERE PROVIDED FOR THIS REVIEW. WHILE THIS
 ENCLOSURE MAY OR MAY NOT BE REQUIRED BY CODE (SEE
 SECTION 506.3.6 FOR CLEARANCE REQUIREMENTS AND 506.3.10
 FOR DUCT ENCLOSURE REQUIREMENTS), THE SIZES SHOWN ON
 PLANS WOULD NOT PROVIDE THE REQUIRED MINIMUM CLEARANCES
 FOR A DUCT ENCLOSURE. THE ENCLOSURE SHALL BE SEPARATED
 FROM THE DUCT BY A MINIMUM OF 6 INCHES AND A MAXIMUM OF
 12 INCHES IN ACCORDANCE WITH FBC-M 506.3.10. THIS
 ENCLOSURE SHALL ALSO BE VENTED TO THE OUTSIDE OF THE
 BUILDING THROUGH THE USE OF WEATHER-PROTECTED OPENINGS.
  
 9. NO INFORMATION WAS PROVIDED REGARDING THE PROPOSED
 WALK-IN COOLER. PROVIDE MANUFACTURER???S SUBMITTAL DATA
 AND SHOW THE LOCATION OF ALL RELATED EQUIPMENT
 (INCLUDING REMOTE CONDENSER), PIPING AND CONDENSATE
 DISPOSAL IN ACCORDANCE WITH FBC-M 304.1 AND FBC-B
 106.1.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-03-12 Cont ID  
Sent By kstevens Date 2009-03-12 Time 11:55 Rev Time 0.00
Received By kstevens Date 2009-03-12 Time 11:55 Sent To  
Notes
2009-03-12 12:30:52DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. SHT P-2 SANITARY, (GREASE), RISER DIAGRAM. THE DISH
 WASHER SHALL DISCHARGE VIA A SEPARATE LINE, (SANITARY).
 ARTICLE III SECTION 90-124(7)(B).
  
 2. SHT P-2 SANITARY, (GREASE), RISER DIAGRAM. THE
 COMBINATION DRAIN & VENT SYSTEM SHALL BE PROVIDED WITH
 A DRY VENT CONNECTED AT ANY POINT WITHIN THE SYSTEM.
 SECTION 912.2.2. SYSTEM NOT VENTED.
  
 3. SHT P-2 POTABLE WATER RISER DIAGRAM. A WATER HAMMER
 ARRESTOR IS REQUIRED AT THE DISH WASHER. SECTION 604.9.
  
 4. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A LISTED SHUT
 OFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH
 MP REGULATOR. SECTION 409.4. A UNION IS REQUIRED
 DOWNSTREAM OF THE SHUT OFF VALVE NEAR THE REGULATOR FOR
 SERVICING & REPLACEMENT.
  
 5. SHT P-2 GAS DISTRIBUTION ISOMETRIC. INDICATE THE
 TOTAL BTU'S FOR THE EXISTING KITCHEN & DISTANCE TO THE
 MOST REMOTE OUTLET IN THE KITCHEN ON THE RISER DIAGRAM.
 SECTION 106.1.2 MORE INFORMATION REQUIRED AND SECTION
 402 PIPE SIZING.
  
 6. SHT P-2 GAS DISTRIBUTION ISOMETRIC. NOTE REFERENCES
 GAS PIPE SIZE PER TABLE 402.4(20) P.E. PIPE. PLEASE
 INDICATE WHERE THE P.E. PIPE WILL BE INSTALLED. (P.E.
 FOR OUTDOOR UNDERGROUND ONLY). SECTION 404.14.1.
  
 7. SHT P-2 GAS DISTRIBUTION ISOMETRIC. PLEASE INDICATE
 GAS TYPE. (IF LP GAS MORE COMMENTS WILL BE
 FORTHCOMING).
  
 8. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A MANUAL SHUT
 OFF VALVE IS REQUIRED UPSTREAM OF THE EMERGENCY HOOD
 SHUT DOWN SHUT OFF VALVE.
  
 9. SHT P-2 GAS DISTRIBUTION ISOMETRIC. SUBMIT MANUF.
 SPECIFICATION SHEETS FOR THE UNIONS. INDICATE MODEL
 NUMBER AND SHOW BTU CAPACITY FOR TOTAL LOAD OF ALL
 APPLIANCES COMBINED. SECTION 410.2(1)(2)(3).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-03-12 Cont ID  
Sent By mflis Date 2009-03-12 Time 10:30 Rev Time 0.00
Received By mflis Date 2009-03-12 Time 10:30 Sent To  
Notes
2009-03-12 10:33:02ZONING REVIEW: NOT REQUIRED
  
 ** THIS SUBMITTAL INCLUDES MEP ONLY
 ** SEE ALTERNATE ARCHITECTURAL PROJECT SUBMITTAL FOR
 ZONING COMMENTS RELATED TO THIS PROJECT
  
 MATT FLIS - 822-1445


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved