Plan Review Details - Permit 09020181
Plan Review Stops For Permit 09020181
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-06-29 Cont ID  
Sent By jgomez Date 2009-06-29 Time 15:35 Rev Time 0.00
Received By jgomez Date 2009-06-17 Time 09:50 Sent To  
Notes
2009-06-29 15:36:47TALKED TO MIKE MERRITT TO GO OVER CONTRACT COMMENTS.
 JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-05-04 Cont ID  
Sent By jgomez Date 2009-05-04 Time 14:25 Rev Time 0.00
Received By jgomez Date 2009-05-04 Time 14:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-17 Cont ID  
Sent By jgomez Date 2009-03-17 Time 15:33 Rev Time 0.00
Received By jgomez Date 2009-03-17 Time 14:24 Sent To P
Notes
2009-03-17 15:43:35RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 3- OWES $70.74 FOR UPDATED PERMIT VALUATION AS REQUIRED
 BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 C) ROOF SHINGLES.
  
 D) SHUTTERS IF SINGLE HUNG WINDOWS DON'T HAVE IMPACT
 GLAZING.
 ALSO, PROVIDE COMPLETE SHUTTERS INSTALLATION SCHEDULE.
 SEE ATTACHED COPY. AND, CLEARLY MARK ON SHUTTERS
 DRAWINGS SPECIFIC MOUNTING CONDITIONS AND ANCHOR TYPE
 AND SPACING TO BE USED.
  
 5- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 6- SHEET A-2:
 A) SPECIFY SAFETY GLAZING FOR WINDOW IN MASTER
 BATHROOM. SEC. R308.4 2004 FLORIDA RESIDENTIAL CODE.
  
 B) WINDOW ON EXISTING BEDROOM IS BLOCKED TO ALLOW FOR
 NEW CLOSET. SPECIFY SIZE OF OPENING TO BE BLOCKED AND
 SIZE OF EXISTING WINDOW TO REMAIN TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS. SEC. R310 OF 2004 FLORIDA
 RESIDENTIAL CODE AND SEC. 501.2 OF 2004 FLORIDA
 EXISTING BUILDING CODE.
  
 C) REVISE DOOR AND WINDOW NOTE #7. REVISE ITEMS A, B
 AND C AS REQUIRED. CHECK SIZE OF SHIMMING. SEE WINDOW
 PRODUCT APPROVAL AND SEC. R613.6 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 7- SHEET S-1:
 A) REVISE INFORMATION SHOWN ON FOUNDATION NOTES,
 FOUNDATION DETAIL, TYPICAL WALL SECTION AND FOUNDATION
 PLAN TO MATCH. REVISE STRENGTH OF CONCRETE AND SIZE OF
 WIRE MESH TO MATCH. SEE COMMENTS ON PLANS.
  
 B) REVISE ROOF SHEATHING SPECIFICATIONS SHOWN ON TYP.
 WALL SECTION. SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR MIN. TYPE OF NAIL AND SPACING TO
 BE USED.
 NOTE: ALSO, COORDINATE THIS INFORMATION WITH DIAPHRAGM
 SCHEDULE ON SHEET S-2.
  
 C) CLARIFY INSTALLATION OF 30# FELT SHOWN ON TYP. WALL
 SECTION. WHAT'S "30# BASE FELT TIN-TAGGED (@ 24" O.C.
 ON BOTH SIDES OF SHEET)".
  
 D) SPECIFY FIREBLOCKING MATERIAL AND LOCATION ON TYP.
 WALL SECTION AS REQUIRED BY SEC. R602.1.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 E) SPECIFY SIZE OF ATTIC VENT TO VERIFY COMPLIANCE WITH
 SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 F) CLARIFY IF TYPICAL WALL SECTION IS FOR THE NEW
 ADDITION OR FOR EXISTING WALL SECTION. WALL SECTION FOR
 EXISTING WALL IS NOT REQUIRED. ONLY FOR NEW WALL IS
 REQUIRED. REVISE TITLE AS REQUIRED.
  
 8- SHEET S-2:
 A) ENGINEERING CRITERIA:
 * CLARIFY IF BUILDING CATEGORY IIIB IS REFERRING TO THE
 CONSTRUCTION TYPE. CONSTRUCTION TYPE IIIB REQUIRES TWO
 HOUR FIRE RATING. IS THIS ADDITION A 2 HOUR FIRE RATED
 CONSTRUCTION?. CLARIFY REVISE AS REQUIRED.
  
 ** DOOR AND WINDOWS DESIGN PRESSURES DON'T MATCH THOSE
 SHOWN ON SHEET A-2. REVISE AS REQUIRED TO MATCH.
  
 *** REFER TO 2004 FBC WITH 2007 REVISIONS, NOT 2006.
  
 B) REVISE ROOF ZONE DIAGRAM: REVISE DIMENSION "A"..
 IT'S 4'-0" MIN. SEE FIGURE R301.2(8) NOTE A OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 C) DESIGN PARAMETERS NOTE #5 AND INFORMATION SHOWN ON
 TYPICAL WALL SECTION DON'T MATCH. REVISE AS REQUIRED.
  
 D) UPDATE DESIGN PARAMETERS NOTE #6. REVISE CODE YEAR
 AND SPECIFIC SECTIONS AND TABLES TO BE USED.
  
 E) UPDATE INFORMATION FOR CAST-CRETE UPLIFT
 CALCULATIONS. REFER TO CORRECT BUILDING CODE EDITION.
  
 F) ATTIC SIZE SHOWN ON FRAMING PLAN DOESN'T COMPLY WITH
 SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 G) COORDINATE DIAPHRAGM SCHEDULE WITH ITEM # 7B ABOVE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-06-22 Cont ID  
Sent By btrobaug Date 2009-06-22 Time 16:05 Rev Time 0.00
Received By btrobaug Date 2009-06-22 Time 15:50 Sent To B
Notes
2009-06-22 16:06:40TO JULIO'S DESK./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-04-21 Cont ID  
Sent By btrobaug Date 2009-04-21 Time 15:46 Rev Time 0.00
Received By btrobaug Date 2009-04-21 Time 12:20 Sent To  
Notes
2009-04-21 12:46:08 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET MEP-1 UNLESS OTHERWISE
 NOTED.
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW***INDICATES
 FURTHER EXPLANATION OF PREVIOUS COMMENT
  
 3} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANELS PER
 250.118, SIZED PER 250.122***} THE EQUIPMENT GROUND
 BETWEEN THE METER AND DISCONNECT A ON THE RISER DIAGRAM
 CREATES A PARALLEL PATH TO GROUND WITH THE NEUTRAL AND
 MUST BE REMOVED. AN ISOLATED NEUTRAL AND EQUIPMENT
 GROUND ARE TO BE RAN FROM THE FIRST MEANS OF
 DISCONNECT. 250.6. THERE IS BO EQIPMENT GROUND RAN TO
 PANEL B..
  
 4} PER 240.24(E) NOT LOCATED IN BATHROOMS IN DWELLING
 UNITS AND GUEST ROOMS OR GUEST SUITES OF HOTELS AND
 MOTELS, OVERCURRENT DEVICES, OTHER THAN SUPPLEMENTARY
 OVERCURRENT PROTECTION, SHALL NOT BE LOCATED IN
 BATHROOMS.***PANEL "B" MUST BE MOVED TO COMPLY WITH
 THIS ARTICLE***IT IS NOW IN THE CLOSET IN VIOLATION OF
 240.24(D).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-26 Cont ID  
Sent By btrobaug Date 2009-02-26 Time 10:07 Rev Time 0.00
Received By btrobaug Date 2009-02-25 Time 16:39 Sent To M
Notes
2009-02-25 16:56:02 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET MEP-1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN
 INCLUDING THE DISCONNECTS SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} THE GROUNDING ELECTRODE SYSTEM IS INSTALLED AT THE
 METER AND SHOULD GO TO FOOTER STEEL AT THAT POINT. THE
 GROUND RODS AT THE PANELS WOULD VIOLATE 250.24(A)(5)
 LOAD-SIDE GROUNDING CONNECTIONS A GROUNDING CONNECTION
 SHALL NOT BE MADE TO ANY GROUNDED CONDUCTOR ON THE LOAD
 SIDE OF THE SERVICE DISCONNECTING MEANS-.
  
 3} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANELS PER
 250.118, SIZED PER 250.122.
  
 4} PER 240.24(E) NOT LOCATED IN BATHROOMS IN DWELLING
 UNITS AND GUEST ROOMS OR GUEST SUITES OF HOTELS AND
 MOTELS, OVERCURRENT DEVICES, OTHER THAN SUPPLEMENTARY
 OVERCURRENT PROTECTION, SHALL NOT BE LOCATED IN
 BATHROOMS.***PANEL "B" MUST BE MOVED TO COMPLY WITH
 THIS ARTICLE.
  
 5} THERE IS A RECEPTACLE SHOWN IN THE DOORWAY TO THE
 BEDROOM, SHOW CORRECT LOCATION PER 210.52.
  
 6} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT OUTLET
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET
 SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS.*** LOCATE ON THE PLANS.
  
 7} SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14 FOR THE CONDENSING UNIT.
  
 8} PER 220.52(B) LAUNDRY CIRCUIT LOAD A LOAD OF NOT
 LESS THAN 1500 VOLT-AMPERES SHALL BE INCLUDED FOR EACH
 2-WIRE LAUNDRY BRANCH CIRCUIT INSTALLED AS REQUIRED BY
 210.11(C)(2). THIS LOAD SHALL BE PERMITTED TO BE
 INCLUDED WITH THE GENERAL LIGHTING LOAD AND SUBJECTED
 TO THE DEMAND FACTORS PROVIDED IN TABLE 220.42.*** THE
 LOAD CALCULATION INDICATES 800 VA.
  
 9} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN. ALSO
 SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-07-05 Cont ID  
Sent By mcruz Date 2009-07-05 Time 09:40 Rev Time 0.00
Received By mcruz Date 2009-06-16 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-17 Cont ID  
Sent By swurafti Date 2009-04-17 Time 15:01 Rev Time 0.00
Received By swurafti Date 2009-04-17 Time 15:01 Sent To  
Notes
2009-04-17 15:13:45TO "R10"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-24 Cont ID  
Sent By adarroug Date 2009-02-24 Time 13:02 Rev Time 0.00
Received By adarroug Date 2009-02-24 Time 13:02 Sent To  
Notes
2009-02-24 13:02:43TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-18 Cont ID  
Sent By kstevens Date 2009-03-18 Time 15:22 Rev Time 0.00
Received By kstevens Date 2009-02-09 Time 15:27 Sent To  
Notes
2009-02-09 16:21:13TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-07-01 Cont ID  
Sent By rkussner Date 2009-07-01 Time 12:19 Rev Time 0.00
Received By rkussner Date 2009-07-01 Time 12:18 Sent To  
Notes
2009-07-01 12:23:07***LANDSCAPE REVIEW PASSED WITH 'PROVISO'**
  
 A COMPLETE LANDSCAPE PLAN AND IRRIGATION PLAN SHALL BE
 SUBMITTED AND APPROVED PRIOR TO C/O.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-05-07 Cont ID  
Sent By rkussner Date 2009-05-07 Time 14:30 Rev Time 0.00
Received By rkussner Date 2009-05-07 Time 14:30 Sent To  
Notes
2009-05-07 15:04:56***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. SUBMIT A LANDSCAPE PLAN THAT CONTAINS ALL ITEMS
 LISTED IN SECTION 94-448 (D)(2).
  
 2. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND CEVELOPMENT REGULATIONS, INCLUDING THE DESIGN
 OPTIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-03-19 Cont ID  
Sent By hmoser Date 2009-03-16 Time 13:49 Rev Time 0.00
Received By hmoser Date 2009-03-18 Time 15:22 Sent To P
Notes
2009-03-16 13:58:27PROVISO
  
 PLEASE SUBMIT MANUFACTURERS INSTALLATIONS INSTRUCTIONS
 FOR EQUIPMENT AT TIME OF FIRST INSPECTION TO CHECK
 REFRIGERANT LINE SIZE .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-04-30 Cont ID  
Sent By kstevens Date 2009-04-30 Time 11:06 Rev Time 0.00
Received By kstevens Date 2009-04-30 Time 11:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-03-18 Cont ID  
Sent By hmoser Date 2009-03-19 Time 07:09 Rev Time 0.00
Received By kstevens Date 2009-03-18 Time 15:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2009-07-05 Cont ID  
Sent By mcruz Date 2009-07-05 Time 09:38 Rev Time 0.00
Received By mcruz Date 2009-07-05 Time 09:34 Sent To  
Notes
2009-07-05 09:36:30PASSED WITH PROVISO:
 THE LANDSCAPE/IRRIGATION PLANS SHALL BE APPROVED PRIOR
 TO FINAL C.O.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2009-05-14 Cont ID  
Sent By mcruz Date 2009-05-14 Time 09:00 Rev Time 0.00
Received By mcruz Date 2009-05-07 Time 11:26 Sent To  
Notes
2009-05-14 09:00:22PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE ADDRESS COMMENTS BY ROBERT KUSSNER, LANDSCAPE
 PLANNER.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-20 Cont ID  
Sent By mcruz Date 2009-02-20 Time 11:41 Rev Time 0.00
Received By mcruz Date 2009-02-20 Time 11:33 Sent To I
Notes
2009-02-20 11:41:53PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. THE SIDE SETBACK DIMENSION SHOWN ON THE SURVEY
 DIFFERS FROM THAT ONE SHOWN ON THE SITE PLAN. PLEASE
 CORRELATE ALL SETBACK DIMENSIONS.
  
 3. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK
 EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 4. THE SIDE SETBACK EXCEEDS THE MAXIMUM ALLOWABLE BY
 CODE. PURSUANT TO THE ZLDR, SECTION 94-72(A)(2):
 SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT -
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET;
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 5. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR,
 SECTION 94-305(B)(4): WINDOW AIR-CONDITIONING UNITS MAY
 NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED SIDE
 SETBACK.
  
 6. INDICATE OVERHANG DIMENSIONS OF THE PROPOSED
 ADDITION. PURSUANT TO THE ZLDR, SECTION 94-305(B):
 OVERHANGS SHALL NOT PROJECT MORE THAN THREE (3) FEET
 INTO A REQUIRED SETBACK.
  
 7. INDICATE IF ANY TREES WILL BE REMOVED AS A RESULT OF
 THE PROPOSED PROJECT. IF YES, A TREE ALTERATION/REMOVAL
 PERMIT WILL BE REQUIRED. CONTACT ROBERT KUSSNER, CITY
 LANDSCAPE PLANNER, AT (561) 822-1462 FOR THE
 APPLICATION.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved