Plan Review Details - Permit 09020137
Plan Review Stops For Permit 09020137
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-03-06 Cont ID  
Sent By mjacobs Date 2009-03-06 Time 15:00 Rev Time 0.00
Received By mjacobs Date 2009-03-06 Time 14:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-02-12 Cont ID  
Sent By mjacobs Date 2009-02-12 Time 11:02 Rev Time 0.00
Received By mjacobs Date 2009-02-12 Time 10:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-03-12 Cont ID  
Sent By btrobaug Date 2009-03-12 Time 15:58 Rev Time 0.00
Received By btrobaug Date 2009-03-12 Time 15:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-10 Cont ID  
Sent By btrobaug Date 2009-02-10 Time 11:10 Rev Time 0.00
Received By btrobaug Date 2009-02-10 Time 10:47 Sent To  
Notes
2009-02-10 11:09:38 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 13-415.1.ABC.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING***SOME
 SPACES INDICATE SWITCHES AS EXISTING WITH NO COMPLIANCE
 FOR SPACE CONTROL 30 MINUTE RESTRICTIONS.
  
 2} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 LIGHTING CIRCUITS, SHEET #2.
  
 3} PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. AN
 ELECTRICAL CONTRACTOR MUST REMOVE ALL WIRING IN
 AFFECTED AREAS FOR DEMOLITION AND MAKE SAFE SAME. ALL
 TEMPORARY WIRING FOR THIS DEMOLITION SHALL COMPLY WITH
 ARTICLE 590 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-03-17 Cont ID  
Sent By mwennerg Date 2009-03-17 Time 11:28 Rev Time 0.00
Received By mwennerg Date 2009-03-17 Time 11:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-02-17 Cont ID  
Sent By mwennerg Date 2009-02-17 Time 10:27 Rev Time 0.00
Received By mwennerg Date 2009-02-17 Time 10:26 Sent To  
Notes
2009-02-17 10:27:55LIFE SAFETY TO COMPLY WITH FLORIDA FIRE PREVENTION
 CODE, 2007 EDITION SINCE DECEMBER 31, 2008.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-02 Cont ID  
Sent By adarroug Date 2009-03-02 Time 09:22 Rev Time 0.00
Received By adarroug Date 2009-03-02 Time 09:22 Sent To  
Notes
2009-03-02 09:26:11TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-17 Cont ID  
Sent By kstevens Date 2009-02-17 Time 16:07 Rev Time 0.00
Received By kstevens Date 2009-02-06 Time 15:43 Sent To  
Notes
2009-02-06 15:43:51TO "BOB"#12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-03-25 Cont ID  
Sent By rregueir Date 2009-03-25 Time 08:56 Rev Time 0.00
Received By rregueir Date 2009-03-25 Time 08:40 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-02-15 Cont ID  
Sent By rregueir Date 2009-02-15 Time 12:27 Rev Time 0.00
Received By rregueir Date 2009-02-15 Time 12:01 Sent To  
Notes
2009-02-15 12:27:41REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THIS PROJECT CONSISTD OF A LEVEL 2 ALTERATION IN
 ACCORDANCE WITH FBC-EB 304.1. LEVEL 2 ALTERATIONS SHALL
 DEMONSTRATE COMPLIANCE WITH THE MECHANICAL VENTILATION
 REQUIREMENTS OF THE FBC-M IN ACCORDANCE WITH FBC-EB
 SECTION 609.1. PROVIDE OUTSIDE AIR CALCULATIONS FOR ALL
 RECOFIGURED SPACES WITH OCCUPANT LOADS, OCCUPANCY
 CLASSIFICATIONS AND OUTSIDE AIR QUANTITIES IN
 ACCORDANCE WITH FBC-M SECTION 403.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-03-16 Cont ID  
Sent By kstevens Date 2009-03-16 Time 12:04 Rev Time 0.00
Received By kstevens Date 2009-03-16 Time 12:01 Sent To  
Notes
2009-03-16 12:04:02 
  
  
 PASSED/PROVISO
 PER SECTION 802.1.6 AN AIR GAP OR AIR BREAK IS
 REQUIRED. PER THE ARCHITECT THE TRAP FOR THE
 DISHWASHWER WILL BE DELETED AND THE DISHWASHER WILL
 CONNECT TO THE TAIL PIECE FROM THE SINK. A REVISION IS
 REQUIRED SHOWING THIS CHANGE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-02-17 Cont ID  
Sent By kstevens Date 2009-02-17 Time 15:43 Rev Time 0.00
Received By kstevens Date 2009-02-17 Time 15:43 Sent To  
Notes
2009-02-17 16:07:06DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHT 1 WATER RISER DIAGRAM. A WATER HAMMER ARRESTOR
 IS REQUIRED ON THE HOT WATER SUPPLY TO THE DISHWASHER.
 SECTION 604.9.
  
 2. SHT 1 WATER RISER DIAGRAM. THE WATER HEATER REQUIRES
 THERMAL EXPANSION CONTROL. SECTION 607.3.2. PLEASE
 INDICATE METHOD.
  
 3. SHT 1 WATER RISER DIAGRAM. THE P&T VALVE FROM THE
 WATER HEATER. PLEASE INDICATE WHERE THE VALVE
 DISCHARGES. SECTION 504.6.1.
  
 4. SHT 1 WATER RISER DIAGRAM. THE WATER HEATER SHALL BE
 INSTALLED IN A GALVANIZED STEEL OR OTHER METAL PAN OF
 EQUAL CORROSION RESISTANCE OR IN A HIGH-IMPACT PLASTIC
 PAN. SECTION 504.7. ALSO SEE SECTIONS 504.7.1 PAN SIZE
 AND DRAIN AS WELL AS SECTION 504.7.2 PAN DRAIN
 TERMINATION.
  
 5. SHT 1 WASTE RISER DIAGRAM. THE DISHWASHER SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK
 INTO A STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH
 SECTION 802.2. -- EACH FIXTURE SHALL BE SEPARATELY
 TRAPPED BY A WATER SEAL TRAP, EXCEPT AS OTHERWISE
 PERMITTED BY THIS CODE. SECTION 1002.1. NO TRAP SHOWN
 AT THE DISHWASHER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-02-10 Cont ID  
Sent By jroach Date 2009-02-10 Time 15:04 Rev Time 0.00
Received By jroach Date 2009-02-10 Time 15:04 Sent To  
Notes
***NONE***