| Plan Review Stops For Permit 09020137 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-03-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-03-06 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-03-06 |
Time |
14:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2009-02-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-02-12 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-02-12 |
Time |
10:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-03-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-03-12 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-03-12 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-02-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-02-10 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-02-10 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2009-02-10 11:09:38 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} 13-415.1.ABC.1.2 SPACE CONTROL. | | | EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL | | | HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY | | | CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH | | | MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED | | | SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING***SOME | | | SPACES INDICATE SWITCHES AS EXISTING WITH NO COMPLIANCE | | | FOR SPACE CONTROL 30 MINUTE RESTRICTIONS. | | | | | | 2} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR | | | LIGHTING CIRCUITS, SHEET #2. | | | | | | 3} PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE | | | SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. AN | | | ELECTRICAL CONTRACTOR MUST REMOVE ALL WIRING IN | | | AFFECTED AREAS FOR DEMOLITION AND MAKE SAFE SAME. ALL | | | TEMPORARY WIRING FOR THIS DEMOLITION SHALL COMPLY WITH | | | ARTICLE 590 NEC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-03-17 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-03-17 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-03-17 |
Time |
11:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2009-02-17 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-02-17 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-02-17 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2009-02-17 10:27:55 | LIFE SAFETY TO COMPLY WITH FLORIDA FIRE PREVENTION | | | CODE, 2007 EDITION SINCE DECEMBER 31, 2008. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-03-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-03-02 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-03-02 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2009-03-02 09:26:11 | TO "BOB"#12 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-02-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-02-17 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-02-06 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2009-02-06 15:43:51 | TO "BOB"#12 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-03-25 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-03-25 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-03-25 |
Time |
08:40 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-02-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-02-15 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-02-15 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2009-02-15 12:27:41 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THIS PROJECT CONSISTD OF A LEVEL 2 ALTERATION IN | | | ACCORDANCE WITH FBC-EB 304.1. LEVEL 2 ALTERATIONS SHALL | | | DEMONSTRATE COMPLIANCE WITH THE MECHANICAL VENTILATION | | | REQUIREMENTS OF THE FBC-M IN ACCORDANCE WITH FBC-EB | | | SECTION 609.1. PROVIDE OUTSIDE AIR CALCULATIONS FOR ALL | | | RECOFIGURED SPACES WITH OCCUPANT LOADS, OCCUPANCY | | | CLASSIFICATIONS AND OUTSIDE AIR QUANTITIES IN | | | ACCORDANCE WITH FBC-M SECTION 403. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2009-03-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-16 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-16 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2009-03-16 12:04:02 | | | | | | | | | | PASSED/PROVISO | | | PER SECTION 802.1.6 AN AIR GAP OR AIR BREAK IS | | | REQUIRED. PER THE ARCHITECT THE TRAP FOR THE | | | DISHWASHWER WILL BE DELETED AND THE DISHWASHER WILL | | | CONNECT TO THE TAIL PIECE FROM THE SINK. A REVISION IS | | | REQUIRED SHOWING THIS CHANGE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-02-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-02-17 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-02-17 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2009-02-17 16:07:06 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | | | | 1. SHT 1 WATER RISER DIAGRAM. A WATER HAMMER ARRESTOR | | | IS REQUIRED ON THE HOT WATER SUPPLY TO THE DISHWASHER. | | | SECTION 604.9. | | | | | | 2. SHT 1 WATER RISER DIAGRAM. THE WATER HEATER REQUIRES | | | THERMAL EXPANSION CONTROL. SECTION 607.3.2. PLEASE | | | INDICATE METHOD. | | | | | | 3. SHT 1 WATER RISER DIAGRAM. THE P&T VALVE FROM THE | | | WATER HEATER. PLEASE INDICATE WHERE THE VALVE | | | DISCHARGES. SECTION 504.6.1. | | | | | | 4. SHT 1 WATER RISER DIAGRAM. THE WATER HEATER SHALL BE | | | INSTALLED IN A GALVANIZED STEEL OR OTHER METAL PAN OF | | | EQUAL CORROSION RESISTANCE OR IN A HIGH-IMPACT PLASTIC | | | PAN. SECTION 504.7. ALSO SEE SECTIONS 504.7.1 PAN SIZE | | | AND DRAIN AS WELL AS SECTION 504.7.2 PAN DRAIN | | | TERMINATION. | | | | | | 5. SHT 1 WASTE RISER DIAGRAM. THE DISHWASHER SHALL | | | DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK | | | INTO A STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH | | | SECTION 802.2. -- EACH FIXTURE SHALL BE SEPARATELY | | | TRAPPED BY A WATER SEAL TRAP, EXCEPT AS OTHERWISE | | | PERMITTED BY THIS CODE. SECTION 1002.1. NO TRAP SHOWN | | | AT THE DISHWASHER. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2009-02-10 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2009-02-10 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2009-02-10 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|