Plan Review Details - Permit 09020136
Plan Review Stops For Permit 09020136
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-07-16 Cont ID  
Sent By jwitmer Date 2009-07-16 Time 11:44 Rev Time 0.77
Received By jwitmer Date 2009-07-16 Time 11:44 Sent To  
Notes
2009-07-16 11:45:48REVISION:
 A-0.00
 A-1.01

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-03-31 Cont ID  
Sent By jwitmer Date 2009-03-31 Time 12:49 Rev Time 2.22
Received By jwitmer Date 2009-03-31 Time 12:48 Sent To  
Notes
2009-03-31 12:50:12PASSED PER MEETING WITH ROBERT BROWN AND REG ARCHITECTS
 3/19/09

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-03-19 Cont ID  
Sent By jwitmer Date 2009-02-27 Time 08:03 Rev Time 3.33
Received By jwitmer Date 2009-02-26 Time 14:56 Sent To  
Notes
2009-02-27 10:59:06BUILDING PLAN REVIEW
 PERMIT: 09020136
 ADD: 315 S FLAGLER DR
 CONT: J. JAY ROTHE, INC.
 TEL: (561) 389-4137
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) LS-1 INDICATES APPLICABLE CODES, UNDER THIS HEADING
 THE WORDING OF FAMILY OF 2004 FLORIDA BUILDING CODE,
 WHICH WOULD INCLUDE THE EXISTING BUILDING CODE,
 UNDERTHE EXISTING BUILDING CODE THE DESIGNER OF RECORD
 IS TO INDICATE AS TO WHAT LEVEL OF ALTERATION THE
 PROJECT WILL CONFORM TO? EXISTING BUILDING CODE 301.5.
 WITH THIS INFORMATION LACKING A THROUGH REVIEW MAY NOT
 BE POSSIBLE. FOR THIS REVIEW IT WILL BE ASSUMED THE
 LEVEL OF ALTERATION SHALL BE CONSIDERED A LEVEL TWO
 ALTERATION WITH THE RECONFIGURATION OR EXTENSION OF ANY
 SYSTEM, OR THE INSTALLATION OF ANY ADDED EQUIPMENT.
 304.1. EXISTING BUILDING CODE.
  
 3) PLEASE REVIEW SHEET A-1.01 AND SECTION 603.3 OF THE
 EXISTING BUILDING CODE . SMOKE BARRIERS. SMOKE BARRIERS
 IN GROUP I-2 OCCUPANCIES SHALL BE INSTALLED WHERE
 REQUIRED BY SECTIONS 603.3.1 & 603.3.2.
 603.3.1 COMPARTMENTATION. SEE SECTION 407 OF THE
 FLORIDA BUILDING CODE, BUILDING.
 603.3.2 FIRE-RESISTANCE RATING. THE SMOKE BARRIERS
 SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, OR THE FLORIDA FIRE PREVENTION CODE.
  
  
 3A) UNDER THE HEADING SECTIOIN 407.2.1 SPACES OF
 UNLIMITED AREA SPLEASE REVIEW 407.2.1(1-4). (1) THE
 SPACES ( WAITING ROOMS AND SIMILAR SPACES) ARE NOT
 OCCUPIED FOR PATIENT SLEEPING UNITS, TREATMENT ROOMS,
 HAZARDOUS OR INCIDENTIAL USE AREAS AS DEFINED IN
 SECTION 302.1.1. THIS AREA CLEALY IS IN DIRECT CONTACT
 WITH SLEEPING UNITS, MECANICAL ROOMS, JANITORS CLOSETS
 AND LINEN ROOMS. PLEASE REVIEW SECTIONS FROM THE CODE
 COMMENTARY AND FIGURE 407.2.1.
  
 3B) THE SECOND CRITERIA IS AUTOMATIC FIRE DETECTION
 SYSTEM INSTALLED IN ACCORDANCE WITH SECTIOIN 907. THIS
 BUILDING IS A HIGHRISE AND WILL NEED TO MEET THE
 REQUIREMENTS OF 907.2.12..2.
 907.2.12.2 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM.
 THE OPERATION OF ANY AUTOMATIC FIRE DETECTOR, SPRINKLER
 WATER-FLOW DEVICE OR MANUAL FIRE ALARM BOX SHALL
 AUTOMATICALLY SOUND AN ALERT TONE FOLLOWED BY VOICE
 INSTRUCTIONS GIVING APPROVED INFORMATION AND DIRECTIONS
 ON A GENERAL OR SELECTIVE BASIS TO THE FOLLOWING
 TERMINAL AREAS ON A MINIMUM OF THE ALARMING FLOOR, THE
 FLOOR ABOVE AND THE FLOOR BELOW IN ACCORDANCE WITH THE
 FLORIDA FIRE PREVENTION CODE.
 1. ELEVATOR LOBBIES.
 2. CORRIDORS.
 3. ROOMS AND TENANT SPACES EXCEEDING 1,000 SQUARE FEET
 (93 M2) IN AREA.
 4. DWELLING UNITS OR SLEEPING UNITS IN GROUP R-2
 OCCUPANCIES.
 5. SLEEPING UNITS IN GROUP R-1 OCCUPANCIES.
 6. AREAS OF REFUGE AS DEFINED IN SECTION 1002.
 EXCEPTION: IN GROUP I-1 AND I-2 OCCUPANCIES, THE ALARM
 SHALL SOUND IN A CONSTANTLY ATTENDED AREA AND A GENERAL
 OCCUPANT NOTIFICATION SHALL BE BROADCAST OVER THE
 OVERHEAD PAGE.
  
 EXISTING BUILDING CODE 604.2.1 HIGH RISE SEE SECTION
 403 FBC, BUILDING. 403.15 SMOKE CONTROL EXCEPTION FOR
 I-2 SHALL COMPLY WITH 407, 419.3.12 AND 420.3.16.
  
 3C) THE THIRD CRITERIA IS THE OPEN CORRIDOR ONTO WHICH
 THE OPEN SPACE ADJOINS THIS SPACE IS TO BE OUTFITTED
 WITH QUICK RESPONCE SPRINKLER HEADS, SHEET FS.02 DOES
 INDICATE THE USE OF QUICK RESPONCE HEADS BUT FS.01 DOES
 INDICATE THE USE OF A R13 SYSTEM THIS AREA IS WITHIN A
 HIGH-RISE BUILDING REQUIRING A FULL NFPA 13 SYSTEM
 PLEASE CORRECT.
  
 3D) AS TO THE FOURTH REQUIREMENT WAITING AREAS AND
 SIMILAR SPACES OPEN TO THE CORRIDORS MUST BE ARRANGED
 SO AS TO NOT OBSTRUCT ACCESS TO THE EXITS, THIS
 CRITERIA HAS BEEN MET.
  
 4) . EXISTING BUILDING CODE 606.1. A BUILDING FACILITY,
 OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH CHAPTER 11
 OF THE FLORIDA BUILDING CODE, BUILDING, ACCESSIBILITY.
 SHEET A-1.01 DETAIL 2 A HI-LOW DRINKING FOUNTAIN, THE
 LOW SECTION OF THE FOUNTAIN INDICATES A MINIMUM CLEAR
 SPACE OF 2'-3" OR 27". THIS WILL BECOME A ABSOLUTE
 HEIGHT IN MOST CASES SINCE WE ALSO HAVE TO REVIEW FOR
 11-4.4.1 PROTRUDING OBJECT WHICH REQUIRES A HEIGTH OF
 NOT MORE THAN 27" FROM THE FINISH FLOOR FOR OBJECTS
 THAT PROTRUDE MORE THAN 4". THE SECOND ISSUE IS WITH
 THE HIGH SIDE OF THE DRINKING FOUNTAIN, HOW WILL THIS
 AREA OF THE DRINKING FOUNTAIN COMPLY WITH THIS SAME
 CODE SECTION. WE HAVE SEEN IN SOME INSTANCES EXTENSION
 OR APRONS DROPPING FROM THE DRINKING FOUNTAIN THAT
 BRINGS THE DRINKING FOUNTAIN INTO COMPLIANCE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
 PASSED PER MEETING WITH ROBERT BROWN 3-19-09

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-05-06 Cont ID  
Sent By dpalmer Date 2009-05-06 Time 14:19 Rev Time 0.00
Received By dpalmer Date 2009-05-06 Time 14:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-03-24 Cont ID  
Sent By dpalmer Date 2009-03-24 Time 20:14 Rev Time 0.00
Received By dpalmer Date 2009-03-24 Time 20:14 Sent To  
Notes
2009-03-24 20:14:54** PROVISO **
  
 1) NOTE: SOME CODE EDITIONS WERE CORRECTED HOWEVER THE
 SHEET M0.1 STILL INDICATES THE 2002 NFPA-70
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1 AND .1.2.
 ROOMS/AREAS 242, 243 AND 247 STILL INDICATE STANDARD
 SINGLE POLE SWITCHES. PLEASE ADDRESS MINIMUM CODE AND
 RESPOND ACCORDINGLY.
  
 3) NOTE: PLEASE SEE FURNITURE/DESK/COUNTER SHOWN ON
 E4.1 AND ON POWER PLANS WHICH IS SHOWN DIRECTLY IN
 FRONT OF THE ELECTRICAL PANELS 4CR1 AND 4CR2. THIS DOES
 NOT MINIMUM CODE COMPLIANCE FOR WORKING CLEARANCES.
 PLEASE SEE 110.26. PLEASE RELOCATE EITHER THE PANELS OR
 THE FURNITURE/DESK/COUNTER.
  
 ** PLANS NEED TO BE REVISED BEFORE ROUGH ELECTRICAL
 INSPECTION. ANY INSTALLATION NOT DONE PER PROVISO
 ISSUED ON PLANS MAY RESULT IN A DELAY OF PROJECT.
 PLEASE CALL IF THERE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-06 Cont ID  
Sent By dpalmer Date 2009-03-06 Time 12:01 Rev Time 0.00
Received By dpalmer Date 2009-03-06 Time 12:02 Sent To  
Notes
2009-03-06 12:02:00** DENIED REVIEW **
  
 1) NOTE: PLANS SHALL STATE THE FOLLOWING CODES.
 NFPA-101 2006. ADOPTED BY FAC 69A-60.004 DECEMBER 31ST,
 2008
 NFPA-1 2006 FAC 69A-60.003 SAME.
  
 SOME SHEETS SUCH AS MECHANICAL STILL STATE THE 2002
 NEC, SOME OTHERS STATE 2003 NFPA-101.
  
 ** PLEASE ADJUST AND REVISE.
 BASED ON THE TIME OF PERMIT APPLICATION THE BUILDING
 CODE SHOW SHOULD BE 2004 W/ 2007 REVISIONS.
  
 2) NOTE: PLEASE INCLUDE COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2.
  
 3) NOTE: PLEASE INCLUDE REQUIRED LIGHTING CONTROLS FOR
 NEW AREAS PER FBC 13-415.1.ABC.1.1, .1.2. SOME AREAS
 SUCH AS ROOMS 250, 249 ETC WHICH ARE NOT 24HR USE AND
 NOT PATIENT CARE SHOW STANDARD SINGLE POLE DEVICES.
 PLEASE ADJUST AND REVISE.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-05-06 Cont ID  
Sent By mawillia Date 2009-05-06 Time 15:28 Rev Time 0.00
Received By mawillia Date 2009-05-06 Time 14:59 Sent To  
Notes
2009-05-06 15:12:35*****REVISION #2, DATED 3/31/2009, APPROVED*****
  
  
 OF THE SUBMITTED REVISED SHEETS, PLAN SHEETS E2.1 WAS
 STAMPOED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-03-30 Cont ID  
Sent By mawillia Date 2009-03-30 Time 16:47 Rev Time 0.00
Received By mawillia Date 2009-03-30 Time 13:16 Sent To  
Notes
2009-03-30 16:47:30*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS LS-3 THRU LS-9, A-1.05,
 A-2.01, E2.1, FA0.1 & FA2.1, AND FS0.1 & FS2.1 WERE
 STAMPOED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-03-12 Cont ID  
Sent By mwennerg Date 2009-03-12 Time 11:27 Rev Time 0.00
Received By mwennerg Date 2009-03-12 Time 11:27 Sent To  
Notes
2009-03-12 11:37:09***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE, 2007 WHICH INCLUDES NFPA 101, 2006 AND
 NFPA 1, 2006 EFFECTIVE ON DECEMBER 31, 2008. SHT LS-1
  
 2) LIFE SAFETY SHEETS INDICATE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING TO BE CLASS B BUT
 SHOW A FLAME SPREAD INDEX OF 0-25 WHICH WOULD SUGGEST
 CLASS A.
  
 3) PLEASE NOTE THAT THE USE OF THE LIFE SAFETY ANNEX
 SECTION DOES NOT SUPPORT PRESCRIPTIVE CODE
 REQUIREMENTS.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 5) WORK SHALL NOT INTERFERE WITH THE BUILDING FIRE
 PROTECTION SYSTEMS. ALL REQUIRED MEANS OF EGRESS TO BE
 MAINTAINED.
  
 6) WHERE PROVIDED, DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
 7) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODAL.
  
 8) FIRE SPRINKLER SYSTEM REMODEL TO COMPLY WITH NFPA
 13, 2002.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2009-06-25 Time   Rev Time 0.00
Received By jwitmer Date 2009-06-25 Time 09:30 Sent To  
Notes
2009-06-25 09:32:38INCOMING TO C-43

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-17 Cont ID  
Sent By swurafti Date 2009-04-17 Time 12:05 Rev Time 0.00
Received By swurafti Date 2009-04-17 Time 12:05 Sent To  
Notes
2009-04-17 12:09:01TO "C13"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-26 Cont ID  
Sent By dpalmer Date 2009-03-24 Time 16:20 Rev Time 0.00
Received By dpalmer Date 2009-03-24 Time 16:20 Sent To  
Notes
2009-03-27 15:27:123/27/09--TO IN-BOX "C20"
2009-03-26 16:21:54PLANS WERE REMOVED FROM INCOMING TO DO THE EXPITED
 ELECTRICLA REVIEW. PLANS WERE ROUTED BACK TO INCOMING
 WITH NOTIFICATION TO ROBERT BROWN.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-12 Cont ID  
Sent By rregueir Date 2009-03-12 Time 14:01 Rev Time 0.00
Received By rregueir Date 2009-02-09 Time 08:41 Sent To PC
Notes
2009-02-09 08:54:56TO "COMM" BD#18

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-07-16 Cont ID  
Sent By rregueir Date 2009-07-16 Time 10:54 Rev Time 0.00
Received By rregueir Date 2009-07-16 Time 10:47 Sent To B
Notes
2009-07-16 10:54:44REVISED M1.0, M2.1, M6.1 DELTA 4 **PROVISO**
  
 PAGE M6.1: IN ORDER TO USE THE SUB-DUCT SYSTEM IN LIEU
 OF FIRE/SMOKE DAMPERS AT SHAFT PENETRATIONS FOR EF-18,
 THE FAN MUST BE SUPPLIED WITH BUILDING EMERGENCY POWER
 IN ACCORDANCE WITH FBC-M 607.5.5.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-04-30 Cont ID  
Sent By rregueir Date 2009-04-30 Time 11:28 Rev Time 0.00
Received By rregueir Date 2009-04-30 Time 11:27 Sent To  
Notes
2009-04-30 11:27:58REVISED M0.1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-03-31 Cont ID  
Sent By rregueir Date 2009-03-31 Time 08:18 Rev Time 0.00
Received By rregueir Date 2009-03-31 Time 07:49 Sent To B
Notes
2009-03-31 07:50:37PLANS PREVIOUSLY PASSED AND STAMPED. ONE PAGE OF ONE
 SET AND ALL PAGES OF THE OTHER SET HAVE BEEN STAMPED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-03-12 Cont ID  
Sent By rregueir Date 2009-03-12 Time 14:01 Rev Time 0.00
Received By rregueir Date 2009-03-12 Time 14:00 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-03-12 Cont ID  
Sent By kstevens Date 2009-03-12 Time 10:54 Rev Time 0.00
Received By kstevens Date 2009-03-12 Time 10:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-02-19 Cont ID  
Sent By aaponte Date 2009-02-19 Time 12:53 Rev Time 0.00
Received By aaponte Date 2009-02-19 Time 12:53 Sent To  
Notes
***NONE***