| 2009-02-24 08:48:14 | ** DENIED ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED |
| | ON THE PLANS. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | THE 2006 LIFE SAFETY CODE CHANGED DECEMBER 31ST, 2008 |
| | FAC69A-60.004 |
| | 2002 NFPA-72 (WHEN APPLICABLE). |
| | |
| | 2) NOTE: PLEASE SUBMIT WORST CASE VOLTAGE DROP |
| | CALCULATIONS. |
| | 13-413.1ABC.1 |
| | |
| | 3) NOTE: PLEASE SUBMIT AND MEET PRESCRIPTIVE |
| | REQUIREMENTS FOR LIGHTING PER CURRENT CODE 13-415.2, |
| | 13-415.2.ABC.1.3. |
| | THE LIGHTING BEING PROPOSED GOES BEYOND THE PARKING |
| | STRUCTURE PERMIT APPLIED FOR IN 2007. |
| | |
| | 4) NOTE: LIGHTING CONTROLS NEED TO MEET |
| | 13-415.1.ABC.1.4. NOT ALL SHOWN DETAILS PHOTO-SENSOR OR |
| | ASTRONOMICAL TIME CLOCK WITH PROGRAMMING BACK UP. SEE |
| | CONTACTOR RISER ON E0.1. |
| | |
| | 5) NOTE: PLANS DO NOT INDICATE ANY LIGHT POLES AND |
| | FIXTURE DETAILS. PLEASE BE SURE TO SEE COMMENTS FROM |
| | OTHER TRADES SUCH AS BUILDING WITH RESPECT TO MINIMUM |
| | WIND LOADS MEETING 1609 OF THE FBC WITH EFFECTIVE |
| | PROJECTED AREAS ETC. |
| | |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |