Plan Review Details - Permit 09020115
Plan Review Stops For Permit 09020115
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-07-17 Cont ID  
Sent By jgomez Date 2009-07-17 Time 17:20 Rev Time 0.00
Received By jgomez Date 2009-07-17 Time 17:20 Sent To PC
Notes
2009-07-17 17:21:22BUILDING REVISIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-03-04 Cont ID  
Sent By jgomez Date 2009-03-04 Time 13:42 Rev Time 0.00
Received By jgomez Date 2009-03-04 Time 13:42 Sent To PC
Notes
2009-03-04 13:53:29BUILDING REVIEW APPROVED WITH PROVISO (PROVIDE
 INFORMATION PRIOR TO INSPECTION TO AVOID ANY CONFLICTS
 OR DELAYS):
  
 1- REVISE CONSTRUCTION TYPE SPECIFIED ON SHEET TS-1.
 SPECIFY CONSTRUCTION TYPE OF EXISTING OVERALL BUILDING,
 NOT JUST THE PHARMACY AREA.
  
 2- CLARIFY WHY PROVIDING 2 DIFFERENT WIND LOAD
 CALCULATIONS. ONE FROM THE ARCHITECT AND THE OTHER ONE
 FROM THE ENGINEER. CALCULATIONS DON'T MATCH EACH OTHER.
 ENGINEER TO SIGN AND SEAL AND PROVIDE HIS INFORMATION
 IN ALL SHEETS WITH ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE. ARCHITECT TO SIGN AND SEAL
 AND PROVIDE HIS INFORMATION IN ALL SHEETS AS REQUIRED
 BY CHAPTER 481 FLORIDA STATUTE.
 ***NOTE: ONLY NEED TO PROVIDE CALCULATIONS DONE BY ONE
 DESIGN PROFESSIONAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date 2009-02-22 Cont ID  
Sent By jgomez Date 2009-02-22 Time 18:20 Rev Time 0.00
Received By jgomez Date 2009-02-22 Time 17:11 Sent To  
Notes
2009-02-22 18:25:42COMMERCIAL BUILDING (MERCANTILE), BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE FOR
 CHANGE OF USE. BRING BACK STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. (REPEAT COMMENT).
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW TO COVER ALL WORK SHOWN ON PLANS. SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004. REVISE VALUATION TO INCLUDE
 DEMOLITION FEES, PROFESSIONAL DESIGN FEES AND COMPLETE
 SCOPE OF WORK TO BE PERFORMED. (REPEAT COMMENT).
  
 4- SHEET TS-1:
 A) REVISE CONSTRUCTION TYPE. THIS BUILDING CAN'T BE
 TYPE VB UNPROTECTED. AREA OF WORK IS ONLY FOR ONE
 TENANT. THERE ARE MORE TENANTS ON THIS BUILDING. THIS
 CONSTRUCTION TYPE DOESN'T APPLY TO THE SIZE OF
 BUILDING. REVISE CONSTRUCTION TYPE AS REQUIRED. (NEED
 TO VERIFY CONSTRUCTION TYPE).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-06 Cont ID  
Sent By jgomez Date 2009-02-07 Time 19:29 Rev Time 0.00
Received By jgomez Date 2009-02-07 Time 14:48 Sent To  
Notes
2009-02-06 19:31:12COMMERCIAL BUILDING (MERCANTILE), BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE FOR
 CHANGE OF USE. BRING BACK STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW TO COVER ALL WORK SHOWN ON PLANS. SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004. REVISE VALUATION TO INCLUDE
 DEMOLITION FEES, PROFESSIONAL DESIGN FEES AND COMPLETE
 SCOPE OF WORK TO BE PERFORMED.
  
 4- SHEET TS-1:
 A) REVISE CONSTRUCTION TYPE. THIS BUILDING CAN'T BE
 TYPE VB UNPROTECTED. AREA OF WORK IS ONLY FOR ONE
 TENANT. THERE ARE MORE TENANTS ON THIS BUILDING. THIS
 CONSTRUCTION TYPE DOESN'T APPLY TO THE SIZE OF
 BUILDING. REVISE CONSTRUCTION TYPE AS REQUIRED.
  
 B) SPECIFY IF BUILDING IS SPRINKLERED OR NOT.
  
 C) PROVIDE ONLY ONE TS-1 SHEET. THERE WERE TWO
 SUBMITTED.
  
 D) UPDATE CODE INFORMATION. REFER TO 2007 REVISIONS,
 NOT 2006.
  
 E) SPECIFY IF STRUCTURAL COLUMNS ARE REQUIRED TO BE
 FIRE RATED. COORDINATE WITH ITEM #4A ABOVE AND TABLE
 601 FBC 2004.
  
 5- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 13-4
 OF FBC 2004.
  
 6- WIND RESISTANCE CALCULATIONS FOR ROOF TOP A/C
 EQUIPMENT:
 A) UPDATE HVAC EQUIPMENT ROOF CURB DETAIL. REVISE
 FLORIDA BUILDING CODE EDITION AND SECTION REFERENCED.
 SEE FBC 2004.
  
 B) UPDATE AMENDMENTS REFERENCED ON COVER PAGE. REFER TO
 2007 REVISIONS, NOT 2006.
  
 7- SHEET A-1.2: UPDATE GENERAL DESIGN CRITERIA:
 * REFER TO 2007 REVISIONS, NOT 2006.
 ** REVISE TABLES REFERENCED FOR LIVE LOADS. SEE FBC
 2004 FOR CORRECT TABLES AND REVISE AS REQUIRED.
  
 8- SHEET A-2.2:
 A) DOOR SCHEDULE IS MISSING SPECIFICATIONS FOR DOOR
 "D".
  
 B) PROVIDE LAYOUTS, DETAILS AND SPECIFICATIONS FOR
 GENERAL SALES AREA, FITTING ROOM AND LOUNGE AREA TO
 SHOW COMPLIANCE WITH CHAPTER 11 REQUIREMENTS SEC. 11-7.
  
 C) CLEAN ROOM: PROVIDE COMPLETE WRITTEN DIMENSIONS AND
 SIZES OF DOORS TO VERIFY COMPLIANCE WITH CHAPTER 11 FBC
 2004.
  
 D) PROVIDE COMPLETE SHOP DRAWINGS FOR CLEAN ROOM. SHOP
 DRAWINGS TO BE REVIEWED AND APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 E) SPECIFY WHAT'S THE PROPOSED USE OF SPACE BETWEEN
 FRONT STOREFRONT AND CLEAN ROOM?
  
 9- SHEET A-2.3: TENANT SEPARATION WT-5 IS ONLY FOR ONE
 HOUR FIRE SEPARATION. NEED TO PROVIDE TENANT SEPARATION
 AS REQUIRED BY TABLE 302.3.2 OF FBC 2004. REVISE AS
 REQUIRED. ALSO, IDENTIFY OCCUPANCY USE OF TENANTS ON
 BOTH SIDES OF STORE TO PROPERLY USE TABLE 302.3.2
  
 10- SHEET A-4.0 :
 A) WAS NOT SIGNED, SEALED AND DATED AS REQUIRED BY
 CHAPTER 481 FLORIDA STATUTE.
  
 B) UPDATE BUILDING CODE YEAR AND CODE SECTION CITED ON
 HVAC EQUIPMENT ROOF CURB DETAIL. SEE FBC 2004 AND
 REVISE AS REQUIRED.
  
 11- SHEET A-4.1:
 A) NAILING SCHEDULE DOESN'T APPLY TO THIS JOB.
  
 B) PROVIDE COMPLETE DETAILS AND DIMENSIONS FOR DETAILS
 "C" AND "D" TO SHOW THE 16" HIGH VOID ON LEXAN WINDOWS
 AND SHOWING COMPLIANCE WITH CHAPTER 11 FBC 2004 SEC.
 11-7.
  
 C) DETAIL "E" TO BE COORDINATED WITH ITEM #9 ABOVE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-07-07 Cont ID  
Sent By btrobaug Date 2009-07-07 Time 14:42 Rev Time 0.00
Received By btrobaug Date 2009-07-07 Time 14:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-05-26 Cont ID  
Sent By btrobaug Date 2009-05-26 Time 13:22 Rev Time 0.00
Received By btrobaug Date 2009-05-26 Time 13:22 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-02-20 Cont ID  
Sent By btrobaug Date 2009-02-20 Time 16:58 Rev Time 0.00
Received By btrobaug Date 2009-02-20 Time 16:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-09 Cont ID  
Sent By btrobaug Date 2009-02-09 Time 07:19 Rev Time 0.00
Received By btrobaug Date 2009-02-09 Time 07:02 Sent To  
Notes
2009-02-09 07:19:19 
  
  
 APPLICATION #009020115 ELECTRICAL PLAN REVIEW
 2100 45TH STREET 2/6/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE COMPLIANCE WITH 13-415.2ABC.1, PERFORMANCE
 CALCULATION PROCEDURES. THIS CAN BE DEMONSTRATED ON THE
 PLANS INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN
 FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
 INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE
 WITH THE ONES IN THE CALCULATIONS. SEE TABLE 13-415.2.B
  
 2} SUBMIT A LEGEND OF FIXTURE TYPES AND WATTAGES ON THE
 PLAN TO CORRELATE WITH THE ONES IN THE CALCULATIONS.
  
 3} LOCATE SPACE CONTROL DEVICE TYPES AND LOCATIONS ON
 THE PLAN PER 13-415.1.ABC.1.2 SPACE CONTROL.
  
 4} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED. SEE ABOVE REFERENCES. SHEET TS-1 INCORRECTLY
 REFERENCES THE 2001 & 2006 NEC .
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-02-23 Cont ID  
Sent By mawillia Date 2009-02-23 Time 11:07 Rev Time 0.00
Received By mawillia Date 2009-02-23 Time 10:14 Sent To  
Notes
2009-02-23 10:43:46*****APPROVED W/PROVISO*****
  
  
 PLAN SHEETS L-S.1, A-4.0, AND E-2.0 WERE STAMPED,
 INITIALED, AND STAMPED; HOWEVER THE FOLLOWING COMMENT
 WAS ADDED TO SHEET E-2.0: COORDINATE THE DISCREPANCY IN
 THE LOCATION OF THE EMERGENCY LIGHT AS SHOWN ON BOTTOM
 RIGHT HAND SECTION OF THE FLOOR LAYOUT ON L-S.1 AND
 A-4.0, BUT IS NOT DISPLAYED ON E-2.0 SHEET.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-02-09 Cont ID  
Sent By mawillia Date 2009-02-09 Time 13:00 Rev Time 0.00
Received By mawillia Date 2009-02-09 Time 12:23 Sent To  
Notes
2009-02-09 13:00:11*****DENIED*****
  
  
 1. ON SHEET THE COVER SHEET (TS-1), AMEND EDITION OF
 THE FLORIDA FIRE PREVENTION CODE FROM 2004 TO 2007
 WHICH SHALL BE REFERENCED. THE 2007 EDITION IS BASED
 UPON NFPA 101, LIFE SAFETY CODE, 2006 EDITION AND NFPA
 1, UNIFORM FIRE CODE, 2006 EDITION.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3. EXPLAIN AND/OR COORDINATE THE DISCREPANCY WITH THE
 NUMBER AND LOCATION OF EXIT AND EMERGENCY LIGHTS AS
 SHOWN ON L-S.1, A-4.0, AND E-2.0 SHEETS.
  
 4. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR
 THIS TENANT SPACE IF SO EQUIPPED. SPRINKLER HEADS MAY
 BE SHOWN ON THE REFLECTED CEILING SHEET (A-4.0).
  
 5. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THIS
 TENANT SPACE IF SO EQUIPPED. FIRE ALARM DEVICES MAY BE
 SHOWN ON THE LIFE SAFETY SHEET (L-S.1).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-07-07 Cont ID  
Sent By btrobaug Date 2009-07-07 Time 14:43 Rev Time 0.00
Received By btrobaug Date 2009-07-06 Time 09:03 Sent To  
Notes
2009-07-06 09:10:39TO C-4

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-05-26 Cont ID  
Sent By btrobaug Date 2009-05-26 Time 13:22 Rev Time 0.00
Received By btrobaug Date 2009-05-15 Time 15:47 Sent To  
Notes
2009-05-15 15:47:55ELECT REV TO B TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-03 Cont ID  
Sent By adarroug Date 2009-03-03 Time 11:12 Rev Time 0.00
Received By adarroug Date 2009-03-03 Time 11:12 Sent To B
Notes
2009-03-03 11:13:18TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-20 Cont ID  
Sent By adarroug Date 2009-02-20 Time 15:56 Rev Time 0.00
Received By adarroug Date 2009-02-20 Time 15:56 Sent To  
Notes
2009-02-20 15:58:27TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-10 Cont ID  
Sent By jgomez Date 2009-02-09 Time 14:21 Rev Time 0.00
Received By jgomez Date 2009-02-07 Time 14:49 Sent To  
Notes
2009-02-07 14:50:302-9-09 ALL TRADES COMPLETED REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-07-10 Cont ID  
Sent By rregueir Date 2009-07-10 Time 15:27 Rev Time 0.00
Received By rregueir Date 2009-07-10 Time 15:27 Sent To PC
Notes
2009-07-10 15:27:52REVISED M-1.0 DELTA 3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-02-21 Cont ID  
Sent By rregueir Date 2009-02-21 Time 10:09 Rev Time 0.00
Received By rregueir Date 2009-02-21 Time 10:07 Sent To  
Notes
2009-02-21 10:09:07******PROVISO******
 PROVIDE MANUFACTURER'S SUBMITTAL DATA OR STRUCTURAL
 ANALYSIS SHOWING NEW RTU AND VENT CAPS ARE DESIGNED FOR
 WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.13.
 SUPPORTING DOCUMENTATION SHALL BE SUBMITTED FOR PLAN
 REVIEW PRIOR TO FINAL INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-02-09 Cont ID  
Sent By rregueir Date 2009-02-06 Time 07:48 Rev Time 0.00
Received By rregueir Date 2009-02-06 Time 07:28 Sent To  
Notes
2009-02-09 07:48:05REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG A-4.0: THE CRUB/RTU ATTACHMENT DETAIL REFERENCES
 THE 2001 FBC AND SECTION 1511.7. THIS PROJECT WAS
 SUBMITTED UNDER THE 2004 FBC WITH 2007 SUPPLEMENTS.
 ALSO, THE CORRECT CODE SECTION FOR CURB HEIGHTS IS
 1509.7. PLEASE REFERENCE THE CORRECT CODE EDITION AND
 SECTIONS ON ALL AREAS OF PLANS.
  
 2. PG A-4.0 & M-2.0: THE CURB AND RTU INSTALLATION
 DETAILS SHOWN ON THESE PAGES (AND ATTACHED
 CALCULATIONS) ARE IN CONFLICT. WHICH IS CORRECT? PLEASE
 CLARIFY AND DEMONSTRATE COMPLIANCE WITH FBCM 301.13.
  
 3. PG M-2.0: DIFFUSER DETAIL ON THIS PAGE CALLS FOR 1"
 WIDE STRAP AS SUPPORT FOR THE FLEX DUCT. N NO CASE
 SHALL THE MATERIAL SUPPORTING FLEXIBLE DUCT THAT IS IN
 DIRECT CONTACT WITH IT BE LESS THAN 1 1/2 INCHES WIDE
 IN ACCORDANCE WITH FBCM 603.5.6.6(6).
  
 4. PG M-2.0: DUCT DETECTOR DETAIL CALLS FOR AUDIBLE -
 VISIBLE NOTIFICATION TO BE IN A "NORMALLY OCCUPIED"
 LOCATION. THE SIGNALS ARE ACTUALLY REQUIRED TO BE IN AN
 APPROVED LOCATION IN ACCORDANCE WITH FBCM 606.4.1.
 CONSULT FIELD INSPECTOR TO DISCUSS AN APPROVED
 LOCATION.
  
 5. PG M-2.0: RTU DETAIL SAYS "SEE MECHANICAL PLAN" FOR
 CONTINUATION OF CONDENSATE DRAIN LINE. NO CONTINUATION
 COULD BE FOUND ON PLANS. CONDENSATE SHALL BE CONVEYED
 FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE OF
 DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO A STREET,
 ALLEY OR OTHER AREAS SO AS TO CAUSE A NUISANCE IN
 ACCORDANCE WITH FBCM 307.2.1. SHOW ON PLANS THE MEANS
 AND LOCATION OF CONDENSATE DISPOSAL FOR NEW RTU.
  
 6. WIND RESISTANCE: DETAILS AND CALCULATIONS FOR RTU
 CAND RTU CURB ATTACHMENT WERE PROVIDED (SEE COMMENT #2
 ABOVE), BUT NO DETAIL WAS PROVIDED FOR VENT CAPS OR
 VENT CAP CURBS. ALSO, NO INFORMATION WAS PROVIDED
 REGARDING THE WIND RESISTANCE CAPABILITIES OF THE RTU
 AND VENT CAPS THEMSELVES. EQUIPMENT AND APPLIANCES THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST WIND PRESSURES AS DETERMINED IN ACCORDANCE WITH
 FBCM 301.13.
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH
 AN EXPLANATION OF HOW EACH COMMENT WAS ADDRESSED AND A
 DESCRIPTION OF WHERE THE RELEVANT INFORMATION CAN BE
 FOUND.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-07-10 Cont ID  
Sent By kstevens Date 2009-07-10 Time 13:56 Rev Time 0.00
Received By kstevens Date 2009-07-10 Time 13:56 Sent To  
Notes
2009-07-10 13:58:49REVISION OK -- SHT P-1.0. -- THERMAL EXPANSION CONTROL
 IS REQUIRED PER SECTION 607.3.2 & A PAN DRAIN IS
 REQUIRED PER SECTION 507.4. -- A REVISION IS REQUIRED
 FOR SHT A-2.2 TO REFLECT THE CHANGE TO THE SINK FROM
 ACCESSIBLE TO NON-ACCESSIBLE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-02-20 Cont ID  
Sent By kstevens Date 2009-02-20 Time 18:10 Rev Time 0.00
Received By kstevens Date 2009-02-20 Time 18:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-02-07 Cont ID  
Sent By kstevens Date 2009-02-07 Time 18:23 Rev Time 0.00
Received By kstevens Date 2009-02-07 Time 18:23 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved