Plan Review Details - Permit 09020107
Plan Review Stops For Permit 09020107
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-05-20 Cont ID  
Sent By dwise Date 2009-05-20 Time 19:30 Rev Time 0.00
Received By dwise Date 2009-05-20 Time 19:28 Sent To PC
Notes
2009-05-20 19:34:42APPROVED WITH PROVISOS AS NOTED BY JULIO GOMEZ IN PRIOR
 REVIEW, EXCEPT:
 1. MUST PROVIDE ELEVATION CERTIFICATES A. PRIOR TO THE
 CONSTRUCTION OF THE LOWEST FLOOR LEVEL. B.AFTER THE
 FIRST FLOOR LEVEL IS CONSTRUCTED, AND C. AT THE TIME OF
 THE FINAL INSPECTION. ALL ELEVATION CERTIFICATES ARE TO
 SIGNED AND SEALED AS APPROPRIATE BY A PROFESSIONAL LAND
 SURVEYOR AND ARE TO BE PROVIDED TO THE FIELD INSPECTOR
 FOR RETURN TO THE CITY FILE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-05-20 Cont ID  
Sent By jgomez Date 2009-04-30 Time 16:40 Rev Time 0.00
Received By dwise Date 2009-04-30 Time 16:40 Sent To  
Notes
2009-04-30 17:10:28BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE COMPLETE DETAILS/SPECS FOR STAIRWAY
 HANDRAILS. SEC. R311.5.6.
 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS (DCA RULE
 9B-72) FOR: A) LOUVERED DOOR IN GENERATOR ROOM. B) NEW
 FOLDING DOORS IN CABANA ROOM. C) PRECAST LINTELS (ONE
 SUBMITTED IS MISSING THE DRAWINGS). D) GENERATOR
 LOUVERS (INFORMATION SUBMITTED IS NOT THE APPROVED
 PRODUCT APPROVAL FL 10088). E) FLAT ROOF (CIRCLE
 SELECTED APPROVED ASSEMBLY AND RE-SUBMIT PACKAGE).
 ***REMAINDER: DESIGNER OF RECORD TO REVIEW AND APPROVE
 ALL PRODUCT APPROVALS.
 3- PROVIDE SIZES FOR CABANA ROOF SCUPPERS (SEC. R903.4)
 AND OVERFLOW SCUPPERS TO COMPLY WITH SEC. R903.4.1.
 4- RE-SUBMIT SOIL TEST REPORT WITH ENGINEER'S ORIGINAL
 SIGNATURE (NOT COLOR COPY) AND PROVIDE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER (SEC.
 61G15-23.001).
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE REVISED
 PRODUCT APPROVAL FOR ROLL UP SHUTTERS AND RE-SUBMIT
 PACKAGE.
 6- RE-SUBMIT SITE SPECIFIC ENGINEERING FOR BALCONY
 GUARDRAIL SYSTEM. SEE COMMENTS ON PACKAGE SUBMITTED.
 7- ENERGY CALCULATIONS ARE TAKING THE WHITE ROOF
 CREDIT. PROVIDE WHITE ROOF TEST RESULTS AS REQUIRED BY
 SEC. 13-607.1.A.5 FBC 2004.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-24 Cont ID  
Sent By jgomez Date 2009-02-24 Time 11:03 Rev Time 0.00
Received By jgomez Date 2009-02-24 Time 11:01 Sent To E
Notes
2009-02-24 11:15:10NEW RESIDENTIAL CONSTRUCTION (R3) , BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- PROPERTY IS LOCATED ON FLOOD ZONE A5. ELEVATION
 CERTIFICATE WILL BE REQUIRED PRIOR TO CERTIFICATE OF
 OCCUPANCY. THIS IS JUST A REMAINDER.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FL. ST.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 3- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 4- PROVIDE SPECIFICATIONS FOR FIRE RATED CEILING ABOVE
 GARAGE AS REQUIRED BY SEC. R309.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 5- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR
 HANDRAILS TO VERIFY COMPLIANCE WITH SEC. R311.5..6 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 6- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) LOUVERED DOORS, INCLUDING DOUBLE DOORS AS SHOWN ON
 GENERATOR ROOM AND ON CABANA BUILDING.
  
 B) WINDOW MULLIONS FOR CLERESTORY WINDOWS ON CABANA
 BUILDING. AND, CLEARLY MARK SPECIFIC MULLION SIZE AND
 ANCHORS TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES.
  
 C) PRECAST LINTELS.
  
 D) FLAT ROOF PRODUCT APPROVAL FOR CABANA ROOF.
 NOTE: CHECK THE DESIGN PRESSURES FOR CORNER AND
 PERIMETER AREAS. CHECK GENERAL LIMITATIONS AND PROVIDE
 REQUIRED INFORMATION.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO
 FBC 2004.
  
 9- MINIMUM ROOF SLOPE FOR LOW SLOPE ROOF IS 1/4" PER
 FOOT AS REQUIRED BY SEC. R905.9 OR R905.11 OF 2004
 FLORIDA RESIDENTIAL CODE. REVISE 4" SLOPE SHOWN FOR
 CABANA FLAT ROOF. 4" DOESN'T PROVIDE THE 1/4" PER FOOT
 SLOPE.
  
 10- PROVIDE DETAILS AND SPECIFICATIONS FOR ROOF
 DRAINAGE INCLUDING THE SCUPPERS AS REQUIRED BY SEC.
 R903.4 OF 2004 FLORIDA RESIDENTIAL CODE. SPECIFY
 LOCATION AND SIZES.
  
 11- COORDINATE DESIGN PRESSURES SHOWN ON SHEET A400
 WITH THE DESIGN PRESSURES SHOWN ON SHEET S100.
  
 12- SPECIFY FIREBLOCKING MATERIAL AND LOCATION ON
 STAIRWAY AS REQUIRED BY SEC. R602.1.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 13- CLARIFY IF ALL WINDOWS ARE FIXED WINDOWS. AND,
 COORDINATE MANUFACTURER SPECIFIED ON WINDOW SCHEDULE
 AND PRODUCT APPROVAL SUBMITTED. THERE ARE TWO DIFFERENT
 MANUFACTURERS. MARVIN AND ULTIMATE.
  
 14- THERE IS A BALANCE OF $15,239.36.
  
 15- SPECIFY ATTIC SIZE AND LOCATION TO COMPLY WITH
 SECTION R807 OF 2004 FLORIDA RESIDENTIAL CODE. NOTE:
 MAKE SURE ENOUGH CLEARANCE IS PROVIDED FOR AIR HANDLER
 UNIT. ALSO, CLARIFY CEILING CONSTRUCTION ON MAIN HOUSE.
 IS IT VAULTED CEILING OR FLAT CEILING. BUILDING SECTION
 SHOWS VAULTED CEILING.
  
 16- SHEET S100:
 A) SPECIFY FINISH FLOOR ELEVATION FOR LAUNDRY ROOM AND
 GENERATOR ROOM. REMEMBER THAT PROPERTY IS LOCATED ON
 FLOOD ZONE A5.
  
 B) REVISE MIN. DIMENSION FOR ZONE "A". MINIMUM
 DIMENSION IS 4'-0" AS REQUIRED BY FOOTNOTE A ON FIGURE
 R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE.
  
 17- SHEET S103:
 A) SPECIFY FINISH FLOOR ELEVATION FOR ALL ROOMS.
 REMEMBER PROPERTY LOCATED ON FLOOD ZONE A5.
  
 B) REVISE MIN. DIMENSION FOR ZONE "A". MINIMUM
 DIMENSION IS 4'-0" AS REQUIRED BY FOOTNOTE A ON FIGURE
 R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE.
  
 18- SHEET S200: REVISE FINISH FLOOR ELEVATION ON DETAIL
 1/S200. COORDINATE WITH ITEM #17 ABOVE.
  
 19- SHEET S301: REVISE SIZE OF STRUCTURAL BUCK ON
 TYPICAL DOOR BUCK DETAIL. NEED SIZE THAT PROVIDES FULL
 SUPPORT TO DOOR FRAME. SEE PRODUCT APPROVAL FOR SIZE OF
 JAMB AND REVISE AS REQUIRED. SEC. R613.6 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 20- CHECK SIZE OF GENERATOR AND SIZE OF GENERATOR ROOM.
 ACCORDING TO INFORMATION SUBMITTED, GENERATOR ROOM MAY
 NOT BE ADEQUATE FOR SIZE OF GENERATOR. CHECK IF IT
 MEETS THE VENTILATION AND ACCESS REQUIREMENTS.
  
 21- GUARDRAIL ENGINEERING:
 A) ENGINEER TO PROVIDE ORIGINAL SEAL, SIGNATURE AND
 DATE IN ALL SHEETS AS REQUIRED BY SEC. 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE AND CHAPTER 471 FL. ST.
  
 B) SPECIFY FBC SPECIFIC EDITION (2007 WITH 2007
 REVISIONS).
  
 C) CLEARLY IDENTIFY INFORMATION THAT APPLIES TO THIS
 SITE SPECIFIC PROJECT. EG: SPECIFIC GLASS THICKNESS,
 GUARDRAIL CAP SIZE, ANCHORS AND SPACING, ETC. ALSO,
 ENGINEER TO WRITE JOB ADDRESS FOR THIS SITE SPECIFIC
 PROJECT.
  
 22- ROLL SHUTTERS PRODUCT APPROVAL:
 A) PROVIDE COMPLETE INFORMATION ON SHEET 21 OF 21.
  
 B) CLEARLY IDENTIFY WHICH MOUNTING CONDITIONS SHOWN ON
 SHUTTERS DRAWINGS APPLY TO THE PROPOSED INSTALLATION.
 SEE SHEET 2 OF 21. IF PROPOSED INSTALLATION IS NOT ON
 DRAWINGS, THEN SITE SPECIFIC ENGINEERING WILL BE
 REQUIRED.. SEE GENERAL NOTE #9 ON SHEET 1 OF 21.
  
 C) SPECIFY HOW MANY SPANS WILL BE REQUIRED FOR EACH
 OPENING.
  
 D) CHECK ANCHOR SPACING. COORDINATE WITH ITEM #22C
 ABOVE.
  
 23- ENERGY CALCULATIONS:
 A) COORDINATE WALL TYPES WITH THOSE SHOWN ON FLOOR
 PLANS. THERE ARE NOT STEEL ADJACENT WALLS. SEE PLANS.
  
 B) CLARIFY WHAT TYPE OF CEILING IS "RBS' AS SPECIFIED
 ON ITEM #10.
  
 C) ENGINEER TO PROVIDE HIS NAME AND LICENSE NUMBER AS
 REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 471 FL. ST.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-29 Cont ID  
Sent By btrobaug Date 2009-04-29 Time 10:11 Rev Time 0.00
Received By btrobaug Date 2009-04-29 Time 08:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-25 Cont ID  
Sent By btrobaug Date 2009-02-25 Time 14:51 Rev Time 0.00
Received By btrobaug Date 2009-02-25 Time 10:39 Sent To M
Notes
2009-02-25 14:49:23 
  
  
 APPLICATION #09020107 ELECTRICAL PLAN REVIEW
 3600 N. FLAGLER DRIVE 2/25/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 COMMENTS FROM SHEET E200 RISER DIAGRAM.
  
 1} THE MANUFACTURERS SPECIFICATIONS SUBMITTED FOR THE
 GENERATOR ARE FOR A 70 KW GENERAC, NOTE #10, SHEET E200
 REFERENCES A KOHLER MODEL 60RZG. CORRELATE THESE AND
 SUBMIT SPECIFICATIONS FOR THE INTENDED INSTALLATION.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR (NOTE #3 ON THE
 PLAN) MUST BE SIZED PER 250.66, SEE NOTE #1 FOR
 PARALLEL CONDUCTORS "1. WHERE MULTIPLE SETS OF
 SERVICE-ENTRANCE CONDUCTORS ARE USED AS PERMITTED IN
 230.40, EXCEPTION NO. 2, THE EQUIVALENT SIZE OF THE
 LARGEST SERVICE-ENTRANCE CONDUCTOR SHALL BE DETERMINED
 BY THE LARGEST SUM OF THE AREAS OF THE CORRESPONDING
 CONDUCTORS OF EACH SET".
  
 3} THE EQUIPMENT GROUND RAN TO ATS FROM PANEL ECB (NOTE
 #5 ON THE PLAN) MUST COMPLY WITH 250.122 (F)(1)- (F)
 CONDUCTORS IN PARALLEL WHERE CONDUCTORS ARE RUN IN
 PARALLEL IN MULTIPLE RACEWAYS OR CABLES AS PERMITTED IN
 310.4, THE EQUIPMENT GROUNDING CONDUCTORS, WHERE USED,
 SHALL BE RUN IN PARALLEL IN EACH RACEWAY OR CABLE. ONE
 OF THE METHODS IN 250.122(F)(1) OR (F)(2) SHALL BE USED
 TO ENSURE THE EQUIPMENT GROUNDING CONDUCTORS ARE
 PROTECTED.
 (1) BASED ON RATING OF OVERCURRENT PROTECTIVE DEVICE
 EACH PARALLEL EQUIPMENT GROUNDING CONDUCTOR SHALL BE
 SIZED ON THE BASIS OF THE AMPERE RATING OF THE
 OVERCURRENT DEVICE PROTECTING THE CIRCUIT CONDUCTORS IN
 THE RACEWAY OR CABLE IN ACCORDANCE WITH TABLE 250.122.
  
 4} NOTE #6 ON THE PLAN INDICATES #4/0 CONDUCTORS FROM
 THE GENERATOR TO THE ATS, INDICATE THE OVERCURRENT
 PROTECTION RATING OF THE GENERATOR BREAKER, SEE
 310.15(B)(6).
  
 5} REGARDING THE FEED TO PANEL "DP" FROM THE ATS, SEE
 COMMENT #3, EQUIPMENT GROUND SIZING PER 250.122.
 THESE COMMENTS ARE IN REFERENCE TO THE SERVICE LOAD
 CALCULATION
  
 6} THE GENERAL LIGHTING LOAD APPEARS TO BE INCORRECT AT
 4773 WATTS. THE SQUARE FOOTAGE FOR THE CALCULATION MUST
 COMPLY WITH 220.12-A UNIT LOAD OF NOT LESS THAN THAT
 SPECIFIED IN TABLE 220.12 FOR OCCUPANCIES SPECIFIED
 THEREIN SHALL CONSTITUTE THE MINIMUM LIGHTING LOAD. THE
 FLOOR AREA FOR EACH FLOOR SHALL BE CALCULATED FROM THE
 OUTSIDE DIMENSIONS OF THE BUILDING, DWELLING UNIT, OR
 OTHER AREA INVOLVED. FOR DWELLING UNITS, THE CALCULATED
 FLOOR AREA SHALL NOT INCLUDE OPEN PORCHES, GARAGES, OR
 UNUSED OR UNFINISHED SPACES NOT ADAPTABLE FOR FUTURE
 USE. THE LIGHTING LOAD IN THE CALCULATION DIFFERS FROM
 THE ONE ON PANEL SCHEDULE-DP.
  
 7} PER 210.11(C) (1) SMALL-APPLIANCE BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR
 ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B). ONLY ONE
 IS CALCULATED.
  
 8} THE UNDER COUNTER REFRIGERATORS MARE CALCULATED AT
 600 WATTS BUT ARE LISTED AS 2000 WATTS TOTAL ON THE
 PANEL SCHEDULES. 220.14(A), 2005 NEC.
  
 9} THE AIR HANDLERS ARE MARKED #3&4 ON THE PANEL
 SCHEDULE BUT ARE MARKED #1&2 ON SHEET M200, CORRELATE
 SAME.
  
 10} THE VOLTAGE FOR THE A/C EQUIPMENT IS SHOWN AS 208
 ON SHEET M200. VERIFY WITH THE MANUFACTURER THAT THEY
 CAN OPERATE ON A 240 VOLT SYSTEM THAT IS THE OPERATING
 SYSTEM SHOWN IN THE LOAD CALCULATION
  
 11} THE PANEL LOCATION IN THE STORAGE ROOM IS IN
 VIOLATION OF 240.24(D) IF ANY IGNITABLE MATERIAL IS
 STORED IN THAT ROOM, INCLUDING POOL CHEMICALS, LAWN
 MOWERS (GAS), GASOLINE CONTAINERS ETC. THE PANEL SHOULD
 BE RELOCATED.
  
 12 A RECEPTACLE PER 210.63 IS REQUIRED FOR THE
 CONDENSING UNIT, WITHIN 25'
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2009-05-20 Cont ID  
Sent By dwise Date 2009-05-20 Time 19:39 Rev Time 0.00
Received By dwise Date 2009-05-20 Time 19:38 Sent To  
Notes
2009-05-20 19:39:23GAS IS UNDER SEPERATE PERMIT AND REVIEW.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2009-05-04 Cont ID  
Sent By kstevens Date 2009-05-04 Time 13:56 Rev Time 0.00
Received By kstevens Date 2009-05-04 Time 13:56 Sent To  
Notes
2009-05-04 14:12:23DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 A. ENERGY EFFECENCY CODE INDICATES GAS WATER HEATERS.
 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT THE
 FOLLOWING INFORMATION FOR REVIEW:
  
 1. OK
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 ****RESPONSE NOTED, BUT THE PIPE SIZE FOR THE GENERATOR
 & TANKLESS WATER HEATER, (989MBTU), REQUIRES 1-1/2"
 GALVANIZED THRU THE SHUT OFF VALVE FOR THE GENERATOR.
 3/4" IS SHOWN. TABLE G2413.4(1) @ 30 FEET.
  
 3. OK
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****RESPONSE NOTED, BUT THE BTU LOAD INDICATED ON THE
 ISOMETRIC RISER DIAGRAM FOR THE GENERATOR, (748MBTU),
 DOES NOT REFLECT THE MANUF. SUBMITTAL, (790MBTU). ALSO
 THE ISOMETRIC INDICATES THE TANKLESS WATER HEATERS AS
 240MBTU, BUT THE MANUF SHEETS INDICATE THEM AT 199MBTU.
 PLEASE CORRELATE. TOTAL BTU'S ON THE SYSTEM IS 1588MBTU
 WITH ADJUSTMENTS. PLEASE INDICATE ON RISER DIAGRAM.
  
 5. OK
 6. OK
 8. OK
 9. OK
  
 ****NEW COMMENT****
  
 1B. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 LISTED REGULATORS. INDICATE THE MODEL NUMBERS AND SHOW
 THE CAPACITY MULTIPLE APPLIANCE FOR EACH REGULATOR.
 UNIONS ARE REQUIRED PAST THE SHUT OFF VALVES FOR THE
 REGULATORS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-03-06 Cont ID  
Sent By kstevens Date 2009-03-06 Time 10:33 Rev Time 0.00
Received By kstevens Date 2009-03-06 Time 10:33 Sent To  
Notes
2009-03-06 10:38:08DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 FUEL GAS
  
 A. ENERGY EFFECENCY CODE INDICATES GAS WATER HEATERS.
 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT THE
 FOLLOWING INFORMATION FOR REVIEW:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2010-05-11 Cont ID  
Sent By jgomez Date 2010-05-11 Time 16:53 Rev Time 0.00
Received By jgomez Date 2010-05-11 Time 16:53 Sent To M
Notes
2010-05-11 16:54:29A/C REVISION SENT TO H. MOSER'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-10-14 Cont ID  
Sent By rmcdouga Date 2009-10-14 Time 09:53 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2009-10-14 09:53:42LANDSCAPE REVISION TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-28 Cont ID  
Sent By dpalmer Date 2009-04-28 Time 17:18 Rev Time 0.00
Received By dpalmer Date 2009-04-28 Time 17:18 Sent To  
Notes
2009-04-28 17:18:44BIN R-19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-06 Cont ID  
Sent By kstevens Date 2009-03-06 Time 10:04 Rev Time  
Received By kstevens Date   Time   Sent To  
Notes
2009-02-05 10:02:35TO "SFR" "Z"
  
  
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2009-10-16 Cont ID  
Sent By rkussner Date 2009-10-16 Time 11:36 Rev Time 0.00
Received By rkussner Date 2009-10-16 Time 11:36 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-05-13 Cont ID  
Sent By rkussner Date 2009-05-13 Time 16:23 Rev Time 0.00
Received By rkussner Date 2009-05-13 Time 16:23 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-02-23 Cont ID  
Sent By rkussner Date 2009-02-23 Time 10:32 Rev Time 0.00
Received By rkussner Date 2009-02-23 Time 10:07 Sent To PC
Notes
2009-02-23 10:41:55***LANDSCAPE REVIEW FAILED***
  
 1. PROVIDE A CERTIFIED COST ESTIMATE THAT INCLUDES THE
 TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR.
  
 2. PROVIDE THE SPACING OF ALL PROPOSED PLANT MATERIAL.
  
 3. THE VEHICULAR USE AREA/DRIVEWAY SHOWN ON THE SITE
 PLAN IS DIFFERENT FROM THE LANDSCAPE PLAN. ALL PLANS
 SHALL BE CONSISTENT.
  
 4. STAFF SUGGESTS THAT THE FRONT WALL BE SET IN FROM
 THE PROPERTY LINE AND LANDSCAPING SHALL BE ADDED WITHIN
 THE PROPERTY BOUNDARY ON THE STREET SIDE OF THE WALL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-05-11 Cont ID  
Sent By hmoser Date 2009-05-11 Time 14:29 Rev Time 0.00
Received By hmoser Date 2009-05-11 Time 14:29 Sent To  
Notes
2009-05-11 14:46:42PASS PROVISO
 PLEASE HAVE ENGINEER OF RECORD PROVIDE A LETTER SHOWING
 EQUIPMENT SCHEDULE FOR FINAL INSPECTION .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732 .

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-03-05 Cont ID  
Sent By hmoser Date 2009-03-05 Time 08:45 Rev Time 0.00
Received By hmoser Date 2009-03-05 Time 08:27 Sent To P
Notes
2009-03-05 08:57:04PLAN DENIED
 PLEASE PROVIDE DUCT SIZE ON FLEX FOR LAUNDRY ROOM # 109
 ON PLANS .
 PLEASE PROVIDE TYPE OF DOOR USED ON AIR HANDLER CLOSET
 1ST FLOOR , AND GRILL SIZE FOR RETURN AIR .
 PLEASE REFER TO SECTION R-303.3 BATHROOM 2004 FBC(R) ,
 FOR BATH EXHAUST ROOM 105 AND 203 .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-05-20 Cont ID  
Sent By dwise Date 2009-05-20 Time 19:45 Rev Time 0.00
Received By dwise Date 2009-05-20 Time 19:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-05-04 Cont ID  
Sent By kstevens Date 2009-05-04 Time 13:05 Rev Time 0.00
Received By kstevens Date 2009-05-04 Time 13:56 Sent To  
Notes
2009-05-04 13:31:48DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 BUILDING
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHTS 200 & A201 GUTTERS & DOWNSPOUTS ARE REQUIRED
 PER SECTIONS 1503.6 & R320.7 AS WELL AS TABLES 1106.3 &
 1106.7.
 ****RESPONSE NOTED, BUT THE GUTTER SIZE AND DRAIN SIZE
 ARE NOT INDICATED. ALSO INDICATE WHERE THE DOWNSPOUTS
 TERMINATE. SEE SECTION R320.7.
  
 3. OK
  
 4. SUBMIT A ROOF PLAN FOR THE POOL CABANA. SECTION
 106.1.2. SHOW THE LOCATION OF ALL REQUIRED PRIMARY AND
 SECONDARY ROOF DRAINS. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. SHOW THE SIZE OF ALL
 DRAINS/SCUPPERS. (HEIGHT & WIDTH).
 *****RESPONSE NOTED, BUT SCUPPER SIZE IS NOT INDICATED
 ON THE PLANS. ALSO THE OVERFLOW SCUPPERS SHALL BE A
 MINIMUM OF 2" AND A MAXIMUM OF 4" ABOVE THE ROOF TO THE
 FLOW LINE OF THE SCUPPER. THE SOUTH ELEVATION INDICATES
 ALL SCUPPERS TO BE AT ROOF LEVEL.
  
 5. SUBMIT CALCULATIONS FOR THE ROOF DRAINS FOR THE
 CABANA. SHOW THE SQUARE FOOT AREA OF EACH DRAIN AND 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS IN THE
 CALCULATION FOR EACH DRAIN. SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS & TABLES.
 ****RESPONSE NOTED, BUT THE UPPER ROOF ON THE CABANA
 APPEARS TO HAVE PARAPET WALLS AROUND THE ROOF AND AS
 SUCH REQUIRES FOOR DRAINS OR SCUPPERS PER SECTION
 R903.4. IN ORDER TO PROPERLY SIZE THE SCUPPERS
 INDICATED, CALCULATIONS ARE REQUIRED SHOWING THE TOTAL
 SQUARE FOOTAGE, (INCLUDING 1/2 THE AREA OF ALL PARAPET
 WALLS), AND TOTAL AREA BEING DRAIN BY EACH PRIMARY &
 SECONDARY SCUPPER.
  
 6. OK
  
 7. SUBMIT A PLUMBING PLAN & A SANITARY ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, TRAPS & VENTS ETC.
 SECTIONS 106.3.5.1.3, P3004.1, P3005.1, P3005.4.1,
 P3101.2, P3101.2.1, P3102.1, P3201.6 & P3201.7.
 ****RESPONSE, NOTED, BUT THE SANITARY ISOMETRIC RISER
 DIAGRAM FOR THE POOL HOUSE ON SHT P101 SHOWS A FLOOR
 DRAIN THAT IS NOT SHOWN ON THE FLOOR PLAN. PLEASE
 CORRELATE. ALSO INDICATE WHAT WILL BE DRAINING INTO THE
 FLOOR DRAIN. (INFORMATIONAL: FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE INTERCEPTORS. A FLOOR SINK OR
 HUB DRAIN IS REQUIRED PER SECTIONS 802.3 & 802.3.2). ON
 SHT P200 RISER S/1 THE SINK SHALL NOT DRAIN THROUGH THE
 HORIZONTAL WET VENT FOR THE BATHROOM FIXTURES. SECTION
 909.1. THE SINK SHALL DISCHARGE DOWNSTREAM OF THE
 BATHROOM FIXTURES.
  
 8. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ****NO RESPONSE, COMMENT NOT ADDRESSED AS ONE SET OF
 VOIDED SHEETS WAS NOT SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-03-06 Cont ID  
Sent By kstevens Date 2009-03-06 Time 10:04 Rev Time 0.00
Received By kstevens Date 2009-03-06 Time 08:25 Sent To ENG
Notes
2009-03-06 10:28:06DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 BUILDING
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT A101 THE SHOWER COMPARTMENT SHALL HAVE AT LEAST
 900 SF OF INTERIOR CROSS SECTIONAL AREA & SHALL BE NOT
 LESS THAN 30 INCHES IN MINIMUM DIMENSION MEASURED FROM
 FINISHED INTERIOR. SECTION P2708.1 SHOW DIMENSIONS.
 PLEASE INDICATE THE DIMENSIONS FOR THE SHOWER.
  
 2. SHTS 200 & A201 GUTTERS & DOWNSPOUTS SECTIONS 1503.6
 & R320.7 AS WELL AS TABLES 1106.3 & 1106.7.
  
 3. SUBMIT A SOUTH ELEVATION AND SHOW ROOF
 DRAINAGE/SCUPPERS REQUIRED. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED), AS WELL AS SECTIONS 1106 & 1107
 WITH ALL SUBSECTIONS AND TABLES.
  
 4. SUBMIT A ROOF PLAN FOR THE POOL CABANA. SECTION
 106.1.2. SHOW THE LOCATION OF ALL REQUIRED PRIMARY AND
 SECONDARY ROOF DRAINS. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. SHOW THE SIZE OF ALL
 DRAINS/SCUPPERS. (HEIGHT & WIDTH).
  
 5. SUBMIT CALCULATIONS FOR THE ROOF DRAINS FOR THE
 CABANA. SHOW THE SQUARE FOOT AREA OF EACH DRAIN AND 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS IN THE
 CALCULATION FOR EACH DRAIN. SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS & TABLES.
  
 6. SHT A301 DETAIL 2/A301 ROOF AT LOGGIA APPEARS TO BE
 DRAINING IN THE WALL. PLEASE CLARIFY. SECTION 106.1.1
  
 7. SUBMIT A PLUMBING PLAN & A SANITARY ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, TRAPS & VENTS ETC.
 SECTIONS 106.3.5.1.3, P3004.1, P3005.1, P3005.4.1,
 P3101.2, P3101.2.1, P3102.1, P3201.6 & P3201.7.
  
 8. NOTE: PLANS DO NOT APPEAR TO BE 100% COMPLIANT AT
 THIS TIME. MORE COMMENTS MAY BE FORTHCOMING DEPENDING
 ON THE NEW INFORMATION AND COMMENT RESPONSES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-05-13 Cont ID  
Sent By mcruz Date 2009-05-13 Time 10:36 Rev Time 0.00
Received By mcruz Date 2009-05-13 Time 10:04 Sent To L
Notes
2009-05-13 10:36:10PASSED WITH PROVISOS:
  
 1. LANDSCAPE AND IRRIGATION PLAN SHALL BE APPROVED
 PRIOR TO FINAL C.O.
 2. DRIVEWAY/POOL/DOCK SHALL BE SUBMITTED UNDER SEPARATE
 PERMITS.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-23 Cont ID  
Sent By mcruz Date 2009-02-23 Time 07:34 Rev Time 0.00
Received By mcruz Date 2009-02-23 Time 06:53 Sent To L
Notes
2009-02-23 07:34:44PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE THE TOTAL HEIGHT OF THE STRUCTURES AS
 FOLLOWS: PURSUANT TO THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-611, THE HEIGHT SHALL BE MEASURED AS THE VERTICAL
 DISTANCE FROM THE AVERAGE ELEVATION OF THE FINISHED
 GRADE OF THE BUILDING TO THE MEAN HEIGHT LEVEL BETWEEN
 EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL ROOFS.
  
 3. THE ACCESSORY STRUCTURE EXCEEDS THE MAXIMUM SQUARE
 FOOTAGE ALLOWED BY CODE. PURSUANT THE THE ZLDR, SECTION
 94-304(B)(1): ACCESSORY STRUCTURES IN RESIDENTIAL
 DISTRICTS.
 MAXIMUM SQUARE FOOTAGE. THE TOTAL FLOOR AREA OF ALL
 ROOFED ACCESSORY BUILDINGS ON A PROPERTY SHALL NOT
 EXCEED 75 PERCENT OF THE GROSS FLOOR AREA OF THE
 PRIMARY STRUCTURE WITH A MAXIMUM FLOOR AREA OF 1,000
 SQUARE FEET. NOTE: NO 220 CONNECTIONS ARE ALLOWED IN
 ACCESSORY STRUCTURES WITHIN THE SINGLE FAMILY LOW
 DENSITY (SF7) RESIDENTIAL DISTRICT.
  
 4. INDICATE THE TYPE OF THE STRUCTURE ON THE ELEVATION
 PLANS, I.E. PRINCIPAL VS ACCESSORY.
  
 5. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR,
 SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 6. INDICATE THE OVERHANG DIMENSIONS. PURSUANT TO THE
 ZLDR, SECTION 94-305(B): OVERHANGS SHALL NOT PROJECT
 MORE THAN THREE (3) FEET INTO A REQUIRED SETBACK.
  
 7. THE FOLLOWING ITEMS SHALL BE APPLIED UNDER SEPARATE
 PERMIT (PLEASE LABEL AS SUCH ON PLAN):
  
 - POOL/POOL EQUIPMENT,
 - BOAT LIFT/DOCK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved