| Plan Review Stops For Permit 09020107 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-05-20 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-05-20 |
Time |
19:30 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-05-20 |
Time |
19:28 |
Sent To |
PC |
|
| Notes |
| 2009-05-20 19:34:42 | APPROVED WITH PROVISOS AS NOTED BY JULIO GOMEZ IN PRIOR | | | REVIEW, EXCEPT: | | | 1. MUST PROVIDE ELEVATION CERTIFICATES A. PRIOR TO THE | | | CONSTRUCTION OF THE LOWEST FLOOR LEVEL. B.AFTER THE | | | FIRST FLOOR LEVEL IS CONSTRUCTED, AND C. AT THE TIME OF | | | THE FINAL INSPECTION. ALL ELEVATION CERTIFICATES ARE TO | | | SIGNED AND SEALED AS APPROPRIATE BY A PROFESSIONAL LAND | | | SURVEYOR AND ARE TO BE PROVIDED TO THE FIELD INSPECTOR | | | FOR RETURN TO THE CITY FILE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-05-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-04-30 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-04-30 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2009-04-30 17:10:28 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- PROVIDE COMPLETE DETAILS/SPECS FOR STAIRWAY | | | HANDRAILS. SEC. R311.5.6. | | | 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS (DCA RULE | | | 9B-72) FOR: A) LOUVERED DOOR IN GENERATOR ROOM. B) NEW | | | FOLDING DOORS IN CABANA ROOM. C) PRECAST LINTELS (ONE | | | SUBMITTED IS MISSING THE DRAWINGS). D) GENERATOR | | | LOUVERS (INFORMATION SUBMITTED IS NOT THE APPROVED | | | PRODUCT APPROVAL FL 10088). E) FLAT ROOF (CIRCLE | | | SELECTED APPROVED ASSEMBLY AND RE-SUBMIT PACKAGE). | | | ***REMAINDER: DESIGNER OF RECORD TO REVIEW AND APPROVE | | | ALL PRODUCT APPROVALS. | | | 3- PROVIDE SIZES FOR CABANA ROOF SCUPPERS (SEC. R903.4) | | | AND OVERFLOW SCUPPERS TO COMPLY WITH SEC. R903.4.1. | | | 4- RE-SUBMIT SOIL TEST REPORT WITH ENGINEER'S ORIGINAL | | | SIGNATURE (NOT COLOR COPY) AND PROVIDE ENGINEERING FIRM | | | CERTIFICATE OF AUTHORIZATION NUMBER (SEC. | | | 61G15-23.001). | | | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE REVISED | | | PRODUCT APPROVAL FOR ROLL UP SHUTTERS AND RE-SUBMIT | | | PACKAGE. | | | 6- RE-SUBMIT SITE SPECIFIC ENGINEERING FOR BALCONY | | | GUARDRAIL SYSTEM. SEE COMMENTS ON PACKAGE SUBMITTED. | | | 7- ENERGY CALCULATIONS ARE TAKING THE WHITE ROOF | | | CREDIT. PROVIDE WHITE ROOF TEST RESULTS AS REQUIRED BY | | | SEC. 13-607.1.A.5 FBC 2004. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-02-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-02-24 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-02-24 |
Time |
11:01 |
Sent To |
E |
|
| Notes |
| 2009-02-24 11:15:10 | NEW RESIDENTIAL CONSTRUCTION (R3) , BUILDING REVIEW | | | CHECKLIST. | | | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 | | | REVISIONS. | | | | | | 1- PROPERTY IS LOCATED ON FLOOD ZONE A5. ELEVATION | | | CERTIFICATE WILL BE REQUIRED PRIOR TO CERTIFICATE OF | | | OCCUPANCY. THIS IS JUST A REMAINDER. | | | | | | 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | | FL. ST. | | | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK | | | UP. | | | | | | 3- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD | | | (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING | | | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE | | | DUE. | | | | | | 4- PROVIDE SPECIFICATIONS FOR FIRE RATED CEILING ABOVE | | | GARAGE AS REQUIRED BY SEC. R309.2 OF 2004 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 5- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR | | | HANDRAILS TO VERIFY COMPLIANCE WITH SEC. R311.5..6 OF | | | 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 6- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2004 | | | FLORIDA RESIDENTIAL CODE. | | | | | | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9B-72 FOR: | | | A) LOUVERED DOORS, INCLUDING DOUBLE DOORS AS SHOWN ON | | | GENERATOR ROOM AND ON CABANA BUILDING. | | | | | | B) WINDOW MULLIONS FOR CLERESTORY WINDOWS ON CABANA | | | BUILDING. AND, CLEARLY MARK SPECIFIC MULLION SIZE AND | | | ANCHORS TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES. | | | | | | C) PRECAST LINTELS. | | | | | | D) FLAT ROOF PRODUCT APPROVAL FOR CABANA ROOF. | | | NOTE: CHECK THE DESIGN PRESSURES FOR CORNER AND | | | PERIMETER AREAS. CHECK GENERAL LIMITATIONS AND PROVIDE | | | REQUIRED INFORMATION. | | | | | | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO | | | FBC 2004. | | | | | | 9- MINIMUM ROOF SLOPE FOR LOW SLOPE ROOF IS 1/4" PER | | | FOOT AS REQUIRED BY SEC. R905.9 OR R905.11 OF 2004 | | | FLORIDA RESIDENTIAL CODE. REVISE 4" SLOPE SHOWN FOR | | | CABANA FLAT ROOF. 4" DOESN'T PROVIDE THE 1/4" PER FOOT | | | SLOPE. | | | | | | 10- PROVIDE DETAILS AND SPECIFICATIONS FOR ROOF | | | DRAINAGE INCLUDING THE SCUPPERS AS REQUIRED BY SEC. | | | R903.4 OF 2004 FLORIDA RESIDENTIAL CODE. SPECIFY | | | LOCATION AND SIZES. | | | | | | 11- COORDINATE DESIGN PRESSURES SHOWN ON SHEET A400 | | | WITH THE DESIGN PRESSURES SHOWN ON SHEET S100. | | | | | | 12- SPECIFY FIREBLOCKING MATERIAL AND LOCATION ON | | | STAIRWAY AS REQUIRED BY SEC. R602.1.2 OF 2004 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 13- CLARIFY IF ALL WINDOWS ARE FIXED WINDOWS. AND, | | | COORDINATE MANUFACTURER SPECIFIED ON WINDOW SCHEDULE | | | AND PRODUCT APPROVAL SUBMITTED. THERE ARE TWO DIFFERENT | | | MANUFACTURERS. MARVIN AND ULTIMATE. | | | | | | 14- THERE IS A BALANCE OF $15,239.36. | | | | | | 15- SPECIFY ATTIC SIZE AND LOCATION TO COMPLY WITH | | | SECTION R807 OF 2004 FLORIDA RESIDENTIAL CODE. NOTE: | | | MAKE SURE ENOUGH CLEARANCE IS PROVIDED FOR AIR HANDLER | | | UNIT. ALSO, CLARIFY CEILING CONSTRUCTION ON MAIN HOUSE. | | | IS IT VAULTED CEILING OR FLAT CEILING. BUILDING SECTION | | | SHOWS VAULTED CEILING. | | | | | | 16- SHEET S100: | | | A) SPECIFY FINISH FLOOR ELEVATION FOR LAUNDRY ROOM AND | | | GENERATOR ROOM. REMEMBER THAT PROPERTY IS LOCATED ON | | | FLOOD ZONE A5. | | | | | | B) REVISE MIN. DIMENSION FOR ZONE "A". MINIMUM | | | DIMENSION IS 4'-0" AS REQUIRED BY FOOTNOTE A ON FIGURE | | | R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 17- SHEET S103: | | | A) SPECIFY FINISH FLOOR ELEVATION FOR ALL ROOMS. | | | REMEMBER PROPERTY LOCATED ON FLOOD ZONE A5. | | | | | | B) REVISE MIN. DIMENSION FOR ZONE "A". MINIMUM | | | DIMENSION IS 4'-0" AS REQUIRED BY FOOTNOTE A ON FIGURE | | | R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 18- SHEET S200: REVISE FINISH FLOOR ELEVATION ON DETAIL | | | 1/S200. COORDINATE WITH ITEM #17 ABOVE. | | | | | | 19- SHEET S301: REVISE SIZE OF STRUCTURAL BUCK ON | | | TYPICAL DOOR BUCK DETAIL. NEED SIZE THAT PROVIDES FULL | | | SUPPORT TO DOOR FRAME. SEE PRODUCT APPROVAL FOR SIZE OF | | | JAMB AND REVISE AS REQUIRED. SEC. R613.6 OF 2004 | | | FLORIDA RESIDENTIAL CODE. | | | | | | 20- CHECK SIZE OF GENERATOR AND SIZE OF GENERATOR ROOM. | | | ACCORDING TO INFORMATION SUBMITTED, GENERATOR ROOM MAY | | | NOT BE ADEQUATE FOR SIZE OF GENERATOR. CHECK IF IT | | | MEETS THE VENTILATION AND ACCESS REQUIREMENTS. | | | | | | 21- GUARDRAIL ENGINEERING: | | | A) ENGINEER TO PROVIDE ORIGINAL SEAL, SIGNATURE AND | | | DATE IN ALL SHEETS AS REQUIRED BY SEC. 61G15-23.002 | | | FLORIDA ADMINISTRATIVE CODE AND CHAPTER 471 FL. ST. | | | | | | B) SPECIFY FBC SPECIFIC EDITION (2007 WITH 2007 | | | REVISIONS). | | | | | | C) CLEARLY IDENTIFY INFORMATION THAT APPLIES TO THIS | | | SITE SPECIFIC PROJECT. EG: SPECIFIC GLASS THICKNESS, | | | GUARDRAIL CAP SIZE, ANCHORS AND SPACING, ETC. ALSO, | | | ENGINEER TO WRITE JOB ADDRESS FOR THIS SITE SPECIFIC | | | PROJECT. | | | | | | 22- ROLL SHUTTERS PRODUCT APPROVAL: | | | A) PROVIDE COMPLETE INFORMATION ON SHEET 21 OF 21. | | | | | | B) CLEARLY IDENTIFY WHICH MOUNTING CONDITIONS SHOWN ON | | | SHUTTERS DRAWINGS APPLY TO THE PROPOSED INSTALLATION. | | | SEE SHEET 2 OF 21. IF PROPOSED INSTALLATION IS NOT ON | | | DRAWINGS, THEN SITE SPECIFIC ENGINEERING WILL BE | | | REQUIRED.. SEE GENERAL NOTE #9 ON SHEET 1 OF 21. | | | | | | C) SPECIFY HOW MANY SPANS WILL BE REQUIRED FOR EACH | | | OPENING. | | | | | | D) CHECK ANCHOR SPACING. COORDINATE WITH ITEM #22C | | | ABOVE. | | | | | | 23- ENERGY CALCULATIONS: | | | A) COORDINATE WALL TYPES WITH THOSE SHOWN ON FLOOR | | | PLANS. THERE ARE NOT STEEL ADJACENT WALLS. SEE PLANS. | | | | | | B) CLARIFY WHAT TYPE OF CEILING IS "RBS' AS SPECIFIED | | | ON ITEM #10. | | | | | | C) ENGINEER TO PROVIDE HIS NAME AND LICENSE NUMBER AS | | | REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE | | | CODE AND CHAPTER 471 FL. ST. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-04-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-04-29 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-04-29 |
Time |
08:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-02-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-02-25 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-02-25 |
Time |
10:39 |
Sent To |
M |
|
| Notes |
| 2009-02-25 14:49:23 | | | | | | | | | | APPLICATION #09020107 ELECTRICAL PLAN REVIEW | | | 3600 N. FLAGLER DRIVE 2/25/09 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | COMMENTS FROM SHEET E200 RISER DIAGRAM. | | | | | | 1} THE MANUFACTURERS SPECIFICATIONS SUBMITTED FOR THE | | | GENERATOR ARE FOR A 70 KW GENERAC, NOTE #10, SHEET E200 | | | REFERENCES A KOHLER MODEL 60RZG. CORRELATE THESE AND | | | SUBMIT SPECIFICATIONS FOR THE INTENDED INSTALLATION. | | | | | | 2} THE GROUNDING ELECTRODE CONDUCTOR (NOTE #3 ON THE | | | PLAN) MUST BE SIZED PER 250.66, SEE NOTE #1 FOR | | | PARALLEL CONDUCTORS "1. WHERE MULTIPLE SETS OF | | | SERVICE-ENTRANCE CONDUCTORS ARE USED AS PERMITTED IN | | | 230.40, EXCEPTION NO. 2, THE EQUIVALENT SIZE OF THE | | | LARGEST SERVICE-ENTRANCE CONDUCTOR SHALL BE DETERMINED | | | BY THE LARGEST SUM OF THE AREAS OF THE CORRESPONDING | | | CONDUCTORS OF EACH SET". | | | | | | 3} THE EQUIPMENT GROUND RAN TO ATS FROM PANEL ECB (NOTE | | | #5 ON THE PLAN) MUST COMPLY WITH 250.122 (F)(1)- (F) | | | CONDUCTORS IN PARALLEL WHERE CONDUCTORS ARE RUN IN | | | PARALLEL IN MULTIPLE RACEWAYS OR CABLES AS PERMITTED IN | | | 310.4, THE EQUIPMENT GROUNDING CONDUCTORS, WHERE USED, | | | SHALL BE RUN IN PARALLEL IN EACH RACEWAY OR CABLE. ONE | | | OF THE METHODS IN 250.122(F)(1) OR (F)(2) SHALL BE USED | | | TO ENSURE THE EQUIPMENT GROUNDING CONDUCTORS ARE | | | PROTECTED. | | | (1) BASED ON RATING OF OVERCURRENT PROTECTIVE DEVICE | | | EACH PARALLEL EQUIPMENT GROUNDING CONDUCTOR SHALL BE | | | SIZED ON THE BASIS OF THE AMPERE RATING OF THE | | | OVERCURRENT DEVICE PROTECTING THE CIRCUIT CONDUCTORS IN | | | THE RACEWAY OR CABLE IN ACCORDANCE WITH TABLE 250.122. | | | | | | 4} NOTE #6 ON THE PLAN INDICATES #4/0 CONDUCTORS FROM | | | THE GENERATOR TO THE ATS, INDICATE THE OVERCURRENT | | | PROTECTION RATING OF THE GENERATOR BREAKER, SEE | | | 310.15(B)(6). | | | | | | 5} REGARDING THE FEED TO PANEL "DP" FROM THE ATS, SEE | | | COMMENT #3, EQUIPMENT GROUND SIZING PER 250.122. | | | THESE COMMENTS ARE IN REFERENCE TO THE SERVICE LOAD | | | CALCULATION | | | | | | 6} THE GENERAL LIGHTING LOAD APPEARS TO BE INCORRECT AT | | | 4773 WATTS. THE SQUARE FOOTAGE FOR THE CALCULATION MUST | | | COMPLY WITH 220.12-A UNIT LOAD OF NOT LESS THAN THAT | | | SPECIFIED IN TABLE 220.12 FOR OCCUPANCIES SPECIFIED | | | THEREIN SHALL CONSTITUTE THE MINIMUM LIGHTING LOAD. THE | | | FLOOR AREA FOR EACH FLOOR SHALL BE CALCULATED FROM THE | | | OUTSIDE DIMENSIONS OF THE BUILDING, DWELLING UNIT, OR | | | OTHER AREA INVOLVED. FOR DWELLING UNITS, THE CALCULATED | | | FLOOR AREA SHALL NOT INCLUDE OPEN PORCHES, GARAGES, OR | | | UNUSED OR UNFINISHED SPACES NOT ADAPTABLE FOR FUTURE | | | USE. THE LIGHTING LOAD IN THE CALCULATION DIFFERS FROM | | | THE ONE ON PANEL SCHEDULE-DP. | | | | | | 7} PER 210.11(C) (1) SMALL-APPLIANCE BRANCH CIRCUITS IN | | | ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY | | | OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE | | | SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR | | | ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B). ONLY ONE | | | IS CALCULATED. | | | | | | 8} THE UNDER COUNTER REFRIGERATORS MARE CALCULATED AT | | | 600 WATTS BUT ARE LISTED AS 2000 WATTS TOTAL ON THE | | | PANEL SCHEDULES. 220.14(A), 2005 NEC. | | | | | | 9} THE AIR HANDLERS ARE MARKED #3&4 ON THE PANEL | | | SCHEDULE BUT ARE MARKED #1&2 ON SHEET M200, CORRELATE | | | SAME. | | | | | | 10} THE VOLTAGE FOR THE A/C EQUIPMENT IS SHOWN AS 208 | | | ON SHEET M200. VERIFY WITH THE MANUFACTURER THAT THEY | | | CAN OPERATE ON A 240 VOLT SYSTEM THAT IS THE OPERATING | | | SYSTEM SHOWN IN THE LOAD CALCULATION | | | | | | 11} THE PANEL LOCATION IN THE STORAGE ROOM IS IN | | | VIOLATION OF 240.24(D) IF ANY IGNITABLE MATERIAL IS | | | STORED IN THAT ROOM, INCLUDING POOL CHEMICALS, LAWN | | | MOWERS (GAS), GASOLINE CONTAINERS ETC. THE PANEL SHOULD | | | BE RELOCATED. | | | | | | 12 A RECEPTACLE PER 210.63 IS REQUIRED FOR THE | | | CONDENSING UNIT, WITHIN 25' | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2009-05-20 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-05-20 |
Time |
19:39 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-05-20 |
Time |
19:38 |
Sent To |
|
|
| Notes |
| 2009-05-20 19:39:23 | GAS IS UNDER SEPERATE PERMIT AND REVIEW. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2009-05-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-04 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-05-04 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2009-05-04 14:12:23 | DENIED | | | REFERENCE: | | | FBC-2004 RESIDENTIAL | | | FBC-2004 FUEL GAS | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | A. ENERGY EFFECENCY CODE INDICATES GAS WATER HEATERS. | | | SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT THE | | | FOLLOWING INFORMATION FOR REVIEW: | | | | | | 1. OK | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | ****RESPONSE NOTED, BUT THE PIPE SIZE FOR THE GENERATOR | | | & TANKLESS WATER HEATER, (989MBTU), REQUIRES 1-1/2" | | | GALVANIZED THRU THE SHUT OFF VALVE FOR THE GENERATOR. | | | 3/4" IS SHOWN. TABLE G2413.4(1) @ 30 FEET. | | | | | | 3. OK | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | ****RESPONSE NOTED, BUT THE BTU LOAD INDICATED ON THE | | | ISOMETRIC RISER DIAGRAM FOR THE GENERATOR, (748MBTU), | | | DOES NOT REFLECT THE MANUF. SUBMITTAL, (790MBTU). ALSO | | | THE ISOMETRIC INDICATES THE TANKLESS WATER HEATERS AS | | | 240MBTU, BUT THE MANUF SHEETS INDICATE THEM AT 199MBTU. | | | PLEASE CORRELATE. TOTAL BTU'S ON THE SYSTEM IS 1588MBTU | | | WITH ADJUSTMENTS. PLEASE INDICATE ON RISER DIAGRAM. | | | | | | 5. OK | | | 6. OK | | | 8. OK | | | 9. OK | | | | | | ****NEW COMMENT**** | | | | | | 1B. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE | | | LISTED REGULATORS. INDICATE THE MODEL NUMBERS AND SHOW | | | THE CAPACITY MULTIPLE APPLIANCE FOR EACH REGULATOR. | | | UNIONS ARE REQUIRED PAST THE SHUT OFF VALVES FOR THE | | | REGULATORS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2009-03-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-06 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-06 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2009-03-06 10:38:08 | DENIED | | | REFERENCE: | | | FBC-2004 RESIDENTIAL | | | FBC-2004 FUEL GAS | | | | | | A. ENERGY EFFECENCY CODE INDICATES GAS WATER HEATERS. | | | SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT THE | | | FOLLOWING INFORMATION FOR REVIEW: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2010-05-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-05-11 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-05-11 |
Time |
16:53 |
Sent To |
M |
|
| Notes |
| 2010-05-11 16:54:29 | A/C REVISION SENT TO H. MOSER'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-10-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-10-14 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2009-10-14 09:53:42 | LANDSCAPE REVISION TO ZONING BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-04-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-28 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-28 |
Time |
17:18 |
Sent To |
|
|
| Notes |
| 2009-04-28 17:18:44 | BIN R-19 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-03-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-06 |
Time |
10:04 |
Rev Time |
|
| Received By |
kstevens |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2009-02-05 10:02:35 | TO "SFR" "Z" | | | | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
P |
Date |
2009-10-16 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-10-16 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-10-16 |
Time |
11:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
2009-05-13 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-05-13 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-05-13 |
Time |
16:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2009-02-23 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-02-23 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-02-23 |
Time |
10:07 |
Sent To |
PC |
|
| Notes |
| 2009-02-23 10:41:55 | ***LANDSCAPE REVIEW FAILED*** | | | | | | 1. PROVIDE A CERTIFIED COST ESTIMATE THAT INCLUDES THE | | | TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR. | | | | | | 2. PROVIDE THE SPACING OF ALL PROPOSED PLANT MATERIAL. | | | | | | 3. THE VEHICULAR USE AREA/DRIVEWAY SHOWN ON THE SITE | | | PLAN IS DIFFERENT FROM THE LANDSCAPE PLAN. ALL PLANS | | | SHALL BE CONSISTENT. | | | | | | 4. STAFF SUGGESTS THAT THE FRONT WALL BE SET IN FROM | | | THE PROPERTY LINE AND LANDSCAPING SHALL BE ADDED WITHIN | | | THE PROPERTY BOUNDARY ON THE STREET SIDE OF THE WALL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-05-11 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2009-05-11 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2009-05-11 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2009-05-11 14:46:42 | PASS PROVISO | | | PLEASE HAVE ENGINEER OF RECORD PROVIDE A LETTER SHOWING | | | EQUIPMENT SCHEDULE FOR FINAL INSPECTION . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 . |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-03-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2009-03-05 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2009-03-05 |
Time |
08:27 |
Sent To |
P |
|
| Notes |
| 2009-03-05 08:57:04 | PLAN DENIED | | | PLEASE PROVIDE DUCT SIZE ON FLEX FOR LAUNDRY ROOM # 109 | | | ON PLANS . | | | PLEASE PROVIDE TYPE OF DOOR USED ON AIR HANDLER CLOSET | | | 1ST FLOOR , AND GRILL SIZE FOR RETURN AIR . | | | PLEASE REFER TO SECTION R-303.3 BATHROOM 2004 FBC(R) , | | | FOR BATH EXHAUST ROOM 105 AND 203 . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-05-20 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-05-20 |
Time |
19:45 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-05-20 |
Time |
19:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2009-05-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-04 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-05-04 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2009-05-04 13:31:48 | DENIED | | | REFERENCE: | | | FBC-2004 RESIDENTIAL | | | FBC-2004 BUILDING | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | | | | 2. SHTS 200 & A201 GUTTERS & DOWNSPOUTS ARE REQUIRED | | | PER SECTIONS 1503.6 & R320.7 AS WELL AS TABLES 1106.3 & | | | 1106.7. | | | ****RESPONSE NOTED, BUT THE GUTTER SIZE AND DRAIN SIZE | | | ARE NOT INDICATED. ALSO INDICATE WHERE THE DOWNSPOUTS | | | TERMINATE. SEE SECTION R320.7. | | | | | | 3. OK | | | | | | 4. SUBMIT A ROOF PLAN FOR THE POOL CABANA. SECTION | | | 106.1.2. SHOW THE LOCATION OF ALL REQUIRED PRIMARY AND | | | SECONDARY ROOF DRAINS. SECTIONS 1106 & 1107 WITH ALL | | | SUBSECTIONS AND TABLES. SHOW THE SIZE OF ALL | | | DRAINS/SCUPPERS. (HEIGHT & WIDTH). | | | *****RESPONSE NOTED, BUT SCUPPER SIZE IS NOT INDICATED | | | ON THE PLANS. ALSO THE OVERFLOW SCUPPERS SHALL BE A | | | MINIMUM OF 2" AND A MAXIMUM OF 4" ABOVE THE ROOF TO THE | | | FLOW LINE OF THE SCUPPER. THE SOUTH ELEVATION INDICATES | | | ALL SCUPPERS TO BE AT ROOF LEVEL. | | | | | | 5. SUBMIT CALCULATIONS FOR THE ROOF DRAINS FOR THE | | | CABANA. SHOW THE SQUARE FOOT AREA OF EACH DRAIN AND 1/2 | | | AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS IN THE | | | CALCULATION FOR EACH DRAIN. SECTIONS 1106 & 1107 WITH | | | ALL SUBSECTIONS & TABLES. | | | ****RESPONSE NOTED, BUT THE UPPER ROOF ON THE CABANA | | | APPEARS TO HAVE PARAPET WALLS AROUND THE ROOF AND AS | | | SUCH REQUIRES FOOR DRAINS OR SCUPPERS PER SECTION | | | R903.4. IN ORDER TO PROPERLY SIZE THE SCUPPERS | | | INDICATED, CALCULATIONS ARE REQUIRED SHOWING THE TOTAL | | | SQUARE FOOTAGE, (INCLUDING 1/2 THE AREA OF ALL PARAPET | | | WALLS), AND TOTAL AREA BEING DRAIN BY EACH PRIMARY & | | | SECONDARY SCUPPER. | | | | | | 6. OK | | | | | | 7. SUBMIT A PLUMBING PLAN & A SANITARY ISOMETRIC RISER | | | DIAGRAM. SHOW ALL PIPE SIZES, TRAPS & VENTS ETC. | | | SECTIONS 106.3.5.1.3, P3004.1, P3005.1, P3005.4.1, | | | P3101.2, P3101.2.1, P3102.1, P3201.6 & P3201.7. | | | ****RESPONSE, NOTED, BUT THE SANITARY ISOMETRIC RISER | | | DIAGRAM FOR THE POOL HOUSE ON SHT P101 SHOWS A FLOOR | | | DRAIN THAT IS NOT SHOWN ON THE FLOOR PLAN. PLEASE | | | CORRELATE. ALSO INDICATE WHAT WILL BE DRAINING INTO THE | | | FLOOR DRAIN. (INFORMATIONAL: FLOOR DRAINS ARE NOT | | | APPROVED INDIRECT WASTE INTERCEPTORS. A FLOOR SINK OR | | | HUB DRAIN IS REQUIRED PER SECTIONS 802.3 & 802.3.2). ON | | | SHT P200 RISER S/1 THE SINK SHALL NOT DRAIN THROUGH THE | | | HORIZONTAL WET VENT FOR THE BATHROOM FIXTURES. SECTION | | | 909.1. THE SINK SHALL DISCHARGE DOWNSTREAM OF THE | | | BATHROOM FIXTURES. | | | | | | 8. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ****NO RESPONSE, COMMENT NOT ADDRESSED AS ONE SET OF | | | VOIDED SHEETS WAS NOT SUBMITTED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-03-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-06 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-06 |
Time |
08:25 |
Sent To |
ENG |
|
| Notes |
| 2009-03-06 10:28:06 | DENIED | | | REFERENCE: | | | FBC-2004 RESIDENTIAL | | | FBC-2004 BUILDING | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHT A101 THE SHOWER COMPARTMENT SHALL HAVE AT LEAST | | | 900 SF OF INTERIOR CROSS SECTIONAL AREA & SHALL BE NOT | | | LESS THAN 30 INCHES IN MINIMUM DIMENSION MEASURED FROM | | | FINISHED INTERIOR. SECTION P2708.1 SHOW DIMENSIONS. | | | PLEASE INDICATE THE DIMENSIONS FOR THE SHOWER. | | | | | | 2. SHTS 200 & A201 GUTTERS & DOWNSPOUTS SECTIONS 1503.6 | | | & R320.7 AS WELL AS TABLES 1106.3 & 1106.7. | | | | | | 3. SUBMIT A SOUTH ELEVATION AND SHOW ROOF | | | DRAINAGE/SCUPPERS REQUIRED. SECTION 106.1.2 (MORE | | | INFORMATION REQUIRED), AS WELL AS SECTIONS 1106 & 1107 | | | WITH ALL SUBSECTIONS AND TABLES. | | | | | | 4. SUBMIT A ROOF PLAN FOR THE POOL CABANA. SECTION | | | 106.1.2. SHOW THE LOCATION OF ALL REQUIRED PRIMARY AND | | | SECONDARY ROOF DRAINS. SECTIONS 1106 & 1107 WITH ALL | | | SUBSECTIONS AND TABLES. SHOW THE SIZE OF ALL | | | DRAINS/SCUPPERS. (HEIGHT & WIDTH). | | | | | | 5. SUBMIT CALCULATIONS FOR THE ROOF DRAINS FOR THE | | | CABANA. SHOW THE SQUARE FOOT AREA OF EACH DRAIN AND 1/2 | | | AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS IN THE | | | CALCULATION FOR EACH DRAIN. SECTIONS 1106 & 1107 WITH | | | ALL SUBSECTIONS & TABLES. | | | | | | 6. SHT A301 DETAIL 2/A301 ROOF AT LOGGIA APPEARS TO BE | | | DRAINING IN THE WALL. PLEASE CLARIFY. SECTION 106.1.1 | | | | | | 7. SUBMIT A PLUMBING PLAN & A SANITARY ISOMETRIC RISER | | | DIAGRAM. SHOW ALL PIPE SIZES, TRAPS & VENTS ETC. | | | SECTIONS 106.3.5.1.3, P3004.1, P3005.1, P3005.4.1, | | | P3101.2, P3101.2.1, P3102.1, P3201.6 & P3201.7. | | | | | | 8. NOTE: PLANS DO NOT APPEAR TO BE 100% COMPLIANT AT | | | THIS TIME. MORE COMMENTS MAY BE FORTHCOMING DEPENDING | | | ON THE NEW INFORMATION AND COMMENT RESPONSES. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2009-05-13 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-05-13 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-05-13 |
Time |
10:04 |
Sent To |
L |
|
| Notes |
| 2009-05-13 10:36:10 | PASSED WITH PROVISOS: | | | | | | 1. LANDSCAPE AND IRRIGATION PLAN SHALL BE APPROVED | | | PRIOR TO FINAL C.O. | | | 2. DRIVEWAY/POOL/DOCK SHALL BE SUBMITTED UNDER SEPARATE | | | PERMITS. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-02-23 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-02-23 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-02-23 |
Time |
06:53 |
Sent To |
L |
|
| Notes |
| 2009-02-23 07:34:44 | PLANNING AND ZONING DEPT: ***ZONING FAILED*** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | 2. PROVIDE THE TOTAL HEIGHT OF THE STRUCTURES AS | | | FOLLOWS: PURSUANT TO THE CITY OF WEST PALM BEACH ZONING | | | AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION | | | 94-611, THE HEIGHT SHALL BE MEASURED AS THE VERTICAL | | | DISTANCE FROM THE AVERAGE ELEVATION OF THE FINISHED | | | GRADE OF THE BUILDING TO THE MEAN HEIGHT LEVEL BETWEEN | | | EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL ROOFS. | | | | | | 3. THE ACCESSORY STRUCTURE EXCEEDS THE MAXIMUM SQUARE | | | FOOTAGE ALLOWED BY CODE. PURSUANT THE THE ZLDR, SECTION | | | 94-304(B)(1): ACCESSORY STRUCTURES IN RESIDENTIAL | | | DISTRICTS. | | | MAXIMUM SQUARE FOOTAGE. THE TOTAL FLOOR AREA OF ALL | | | ROOFED ACCESSORY BUILDINGS ON A PROPERTY SHALL NOT | | | EXCEED 75 PERCENT OF THE GROSS FLOOR AREA OF THE | | | PRIMARY STRUCTURE WITH A MAXIMUM FLOOR AREA OF 1,000 | | | SQUARE FEET. NOTE: NO 220 CONNECTIONS ARE ALLOWED IN | | | ACCESSORY STRUCTURES WITHIN THE SINGLE FAMILY LOW | | | DENSITY (SF7) RESIDENTIAL DISTRICT. | | | | | | 4. INDICATE THE TYPE OF THE STRUCTURE ON THE ELEVATION | | | PLANS, I.E. PRINCIPAL VS ACCESSORY. | | | | | | 5. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C | | | EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR, | | | SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | | | | 6. INDICATE THE OVERHANG DIMENSIONS. PURSUANT TO THE | | | ZLDR, SECTION 94-305(B): OVERHANGS SHALL NOT PROJECT | | | MORE THAN THREE (3) FEET INTO A REQUIRED SETBACK. | | | | | | 7. THE FOLLOWING ITEMS SHALL BE APPLIED UNDER SEPARATE | | | PERMIT (PLEASE LABEL AS SUCH ON PLAN): | | | | | | - POOL/POOL EQUIPMENT, | | | - BOAT LIFT/DOCK. | | | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | |
|
|