Plan Review Details - Permit 09020082
Plan Review Stops For Permit 09020082
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-05-26 Cont ID  
Sent By dwise Date 2009-05-26 Time 20:37 Rev Time 0.00
Received By dwise Date 2009-05-26 Time 20:37 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-03-27 Cont ID  
Sent By mjacobs Date 2009-03-27 Time 08:53 Rev Time 0.00
Received By mjacobs Date 2009-03-27 Time 08:23 Sent To  
Notes
2009-03-27 08:53:24PROVISO: FBC 11-7: A PORTION OF THE MAIN COUNTER SHALL
 BE A MINIMUM OF 36 INCHES IN LENGTH AND A MIXIMUM
 HEIGHT OF 36 INCHES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-02-10 Cont ID  
Sent By mjacobs Date 2009-02-10 Time 15:04 Rev Time 0.00
Received By mjacobs Date 2009-02-10 Time 15:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-05-26 Cont ID  
Sent By dwise Date 2009-05-26 Time 20:37 Rev Time 0.00
Received By dwise Date 2009-05-26 Time 20:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-20 Cont ID  
Sent By btrobaug Date 2009-04-20 Time 16:44 Rev Time 0.00
Received By btrobaug Date 2009-04-14 Time 14:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-02-09 Cont ID  
Sent By btrobaug Date 2009-02-09 Time 12:13 Rev Time 0.00
Received By btrobaug Date 2009-02-09 Time 11:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-05-27 Cont ID  
Sent By mawillia Date 2009-05-27 Time 11:17 Rev Time 0.00
Received By mawillia Date 2009-05-27 Time 11:05 Sent To  
Notes
2009-05-27 11:17:18*****REVISION, DATED 5/11/2009, APPROVED*****
  
 REVISED PLAN SHEETS M-1 AND E-2 (OF THE SUBMITTED 4
 SHEETS) WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-03-31 Cont ID  
Sent By mwennerg Date 2009-03-31 Time 11:10 Rev Time 0.00
Received By mwennerg Date 2009-03-31 Time 11:10 Sent To  
Notes
2009-03-31 11:11:52RE-STAMP ONLY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-02-17 Cont ID  
Sent By mwennerg Date 2009-02-17 Time 09:52 Rev Time 0.00
Received By mwennerg Date 2009-02-17 Time 09:52 Sent To  
Notes
2009-02-17 09:53:19LIFE SAFETY SHALL COMPLY WITH FLORIDA FIRE PREVENTION
 CODE, 2007 EDITION TO INCLUDE NFPA 101, 2006 AND NFPA
 1, 2006 SINCE DECEMBER 31, 2008.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-28 Cont ID  
Sent By dpalmer Date 2009-04-28 Time 15:28 Rev Time 0.00
Received By dpalmer Date 2009-04-28 Time 15:28 Sent To  
Notes
2009-04-28 15:29:20TO RR'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-10 Cont ID  
Sent By adarroug Date 2009-03-10 Time 08:38 Rev Time 0.00
Received By adarroug Date 2009-03-10 Time 08:38 Sent To  
Notes
2009-03-10 08:41:57TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-17 Cont ID  
Sent By kstevens Date 2009-02-17 Time 14:51 Rev Time 0.00
Received By kstevens Date 2009-02-05 Time 16:24 Sent To  
Notes
2009-02-05 16:35:46TO "BOB"#9

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-05-04 Cont ID  
Sent By rregueir Date 2009-05-04 Time 11:03 Rev Time 0.00
Received By rregueir Date 2009-05-04 Time 10:54 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-04-02 Cont ID  
Sent By hmoser Date 2009-04-02 Time 13:37 Rev Time 0.00
Received By hmoser Date 2009-04-02 Time 13:37 Sent To  
Notes
2009-04-02 13:46:50PLAN DENIED
 1) PLEASE REFER TO TABLE 403.3 2007 FBC (M) FOR
 BATHROOM EXHAUST 50 CFM PER WATER CLOSET .
 2) PLEASE PROVIDE DUCT SIZE FOR EXISTING SLOT DIFFUSERS
 .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-02-15 Cont ID  
Sent By rregueir Date 2009-02-15 Time 11:03 Rev Time 0.00
Received By rregueir Date 2009-02-15 Time 10:28 Sent To  
Notes
2009-02-15 11:03:47REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-1: NOTE #15 CALLS FOR NEW DUCT PENETRATION OF
 SHAFT ENCLOSURE WITH FIRE DAMPER FOR OUTSIDE AIR. SHAFT
 ENCLOSURES THAT ARE PERMITTED TO BE PENETRATED BY DUCTS
 AND AIR TRANSFER OPENINGS SHALL BE PROTECTED WITH
 APPROVED FIRE AND SMOKE DAMPERS INSTALLED IN ACCORDANCE
 WITH THEIR LISTING PER FBCM 607.5.5.1.
  
 2. PAGE M-1: IS THE CEILING SPACE ABOVE THE EXISTING
 BATHROOMS ISOLATED FROM THE PLENUM CEILING ON THE REST
 OF THE FLOOR? NOTE ON THIS PAGE INDICATES THE CEILING
 SPACE THROUGHOUT IS A RETURN AIR PLENUM.THE DUCT ON THE
 DISCHARGE SIDE OF PROPOSED NEW EF-1 WILL BE UNDER
 POSITIVE PRESSURE AND CANNOT BE LOCATED IN A PLENU IN
 ACCORDANCE WITH FBCM 601.3.
  
 3. M AND P PAGES: MECHANICAL DETAIL CALLS FOR AUXILIARY
 DRAIN PAN WITH A FLOAT SWITCH AND NO SECONDARY DRAIN
 LINE WHILE PLUMBING PLAN SHOWS SECONDARY DRAIN LINE RUN
 FROM THE AUXILIARY DRAIN PAN TO ABOVE A SINK. WHICH IS
 CORRECT? PLEASE COORDINATE PLANS AND SHOW COMPLIANCE
 WITH FBCM 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-03-17 Cont ID  
Sent By kstevens Date 2009-03-17 Time 13:48 Rev Time 0.00
Received By kstevens Date 2009-03-17 Time 13:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-02-17 Cont ID  
Sent By kstevens Date 2009-02-17 Time 13:34 Rev Time 0.00
Received By kstevens Date 2009-02-17 Time 13:34 Sent To  
Notes
2009-02-17 14:51:44DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1. ALL SHEETS WITH BIRSE DESIGN INC TITLE BLOCK. PER
 FAC 61G1-16.004(2) THE FIRM ADDRESS IS REQUIRED. THE
 ADDRESS INDICATED IN THE TITLE BLOCKS, (1511 PROSPERITY
 FARMS ROAD LAKE PARK FLORIDA), DOES NOT REFLECT THE
 ADDRESS OF RECORD ON THE STATE OF FLORIDA DBPR WEBSITE,
 (10096 SEAGRAPE WAY PALM BEACH GARDENS FLORIDA). FS
 481.2055. PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR
 WEBSITE TO MATCH PRIOR TO RESUBMITTING FOR REVIEW.
  
 2. SHT A-1 PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 BREAK ROOM SINK AND THE TURNING AREA AS REQUIRED IN
 CHAPTER 11 SECTIONS 11-4.24.5 AND 11-4.2.3.
  
 3. SHT A-1 DEMO NOTE 4 INDICATES THE SANITARY/WASTE
 LINES TO BE CAPPED OFF FLUSH WITH THE FLOOR. PER
 SECTION 704.5 IN THE REMOVAL OF ANY PART OF A SANITARY
 SYSTEM, DEAD ENDS ARE PROHIBITED. LINES SHALL BE CAPPED
 OFF WITHIN 2 FEET OF A LIVE BRANCH LINE OR COMPLETLY
 REMOVED. PLEASE INDICATE ON PLANS.
  
 4. SHT A-3 DETAIL 1 NOTE INDICATES THAT A GARBAGE
 DISPOSAL SHALL BE PROVIDED. SUBMIT A CUT DETAIL SHOWING
 THE SINK & GARBAGE DISPOSAL AND THE REQUIRED CLEARANCES
 PER SECTION 11-4.24.3. SUBMIT THE MANUF. SPECIFICATIONS
 FOR THE SINK AND THE GARBAGE DISPOSAL THAT INDICATE ADA
 APPROVAL. SECTION 106.1.2.
  
 5. SHT P-2 A TRAP PRIMER IS REQUIRED FOR THE HUB DRAIN
 PER SECTION 1002.4.
  
 6. SHT P-2 THE WATER HEATER SHALL BE RAISED ABOVE THE
 OUTLET OF THE HEATER PAN SO THAT THE HEATER DOES NOT
 SIT IN THE WATER FROM THE EXPANSION VALVE WATTS #530C.
 PLEASE INDICATE ON WATER HEATER DETAIL.
  
 7. SHTS P-1 KEY NOTES #4 INDICATES THE WATER HEATER IS
 A 40 GAL LOW BOY. PLEASE SUBMIT A DETAIL SHOWING HOW
 THE WATER HEATER WILL BE HANGING ABOVE THE CEILING. THE
 WEIGHT OF THE WATER HEATER WHEN FULL WILL BE OVER 375
 LBS AND PER SECTION 501.4 SHALL BE PROVIDED WITH ACCESS
 FOR OBSERVATION, MAINTENANCE, SERVICING AND
 REPLACEMENT. SECTION 106.1.2 (MORE INFORMATION
 REQUIRED).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-03-13 Cont ID  
Sent By eschneid Date 2009-03-13 Time 08:42 Rev Time 0.25
Received By eschneid Date 2009-03-13 Time 08:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-11 Cont ID  
Sent By eschneid Date 2009-02-11 Time 08:38 Rev Time 0.50
Received By eschneid Date 2009-02-11 Time 08:28 Sent To  
Notes
2009-02-11 08:46:26FAILED
  
 ADDITIONAL INFORMATION ON THE ROOFTOP A/C EQUIPMENT IS
 REQUIRED. PLEASE PROVIDE THE HEIGHT OF THE EQUIPMENT
 FROM THE LEVEL OF THE ROOF AND THE HEIGHT OF THE
 EXISTING SCREEN WALL. IF THE A/C EQUIPMENT EXCEEDS THE
 HEIGHT OF THE SCREEN WALL, THEN A LETTER APPROVING THE
 A/C EQUIPMENT IS REQUIRED FROM THE NORTHPOINT
 ARCHITECTURAL REVIEW COMMITTEE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.