Plan Review Details - Permit 09020014
Plan Review Stops For Permit 09020014
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-10-07 Cont ID  
Sent By rregueir Date 2009-10-07 Time 16:15 Rev Time 0.00
Received By rregueir Date 2009-10-07 Time 16:15 Sent To  
Notes
2009-10-07 16:16:04ELECTRICAL REVIEW COMPLETED AND PASSED UNDER MASTER
 #09070384

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-04 Cont ID  
Sent By btrobaug Date 2009-02-04 Time 09:13 Rev Time 0.00
Received By btrobaug Date 2009-02-04 Time 06:53 Sent To I
Notes
2009-02-04 07:29:29 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.*** COPIES OF ENGINEERED DRAWINGS CANNOT BE
 SUBMITTED OR REVIEWED.
  
 2} THE PLANS SUBMITTED DO NOT CORRELATE WITH THE
 DESCRIPTION ON THE APPLICATION. SUBMIT FLOOR PLANS
 SHOWING THE LOCATION OF THE PANEL AND THE
 EQUIPMENT.106.1.1 FBC.
  
 3} THE #1/0 FEEDERS FROM DISCONNECT "E" (FUSED AT 150
 AMPS) ARE NOT RATED FOR THE 152.5 AMPS GIVEN IN THE
 CALCULATIONS.. 310.16 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-07-17 Cont ID  
Sent By kstevens Date 2009-07-17 Time 11:06 Rev Time 0.00
Received By kstevens Date 2009-07-17 Time 11:06 Sent To  
Notes
2009-07-17 11:11:43ATTACHED TO PERMIT 09070384 IN C-38

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-14 Cont ID  
Sent By mjacobs Date 2009-04-14 Time 13:55 Rev Time 0.00
Received By mjacobs Date 2009-04-14 Time 13:55 Sent To E
Notes
2009-04-14 13:56:04SENT TO BT DESK MJ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-04 Cont ID  
Sent By btrobaug Date 2009-02-04 Time 09:13 Rev Time 0.00
Received By btrobaug Date 2009-02-04 Time 06:53 Sent To PC
Notes
2009-02-04 07:55:47 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.*** COPIES OF ENGINEERED DRAWINGS CANNOT BE
 SUBMITTED OR REVIEWED.
  
 2} A PERMIT FOR THE HOOD MUST BE APPLIED FOR PRIOR TO
 OR IN CONJUNCTION WITH THE THIS APPLICATION, FOR
 MECHANICAL REVIEW. 106.1 FBC.
  
 3} PLANS FOR THE SUPPRESSION SYSTEM MUST BE SUBMITTED
 FOR FIRE REVIEW. 106.1.1.1 FBC AS AMENDED.
  
 4} THE PLANS SUBMITTED DO NOT CORRELATE WITH THE
 DESCRIPTION ON THE APPLICATION. SUBMIT FLOOR PLANS
 SHOWING THE LOCATION OF THE PANEL AND THE
 EQUIPMENT.106.1.1 FBC.
  
 5} THE #1/0 FEEDERS FROM DISCONNECT "E" (FUSED AT 150
 AMPS) ARE NOT RATED FOR THE 152.5 AMPS GIVEN IN THE
 CALCULATIONS.. 310.16 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-07-29 Cont ID  
Sent By astelly Date 2009-07-29 Time 14:17 Rev Time 0.00
Received By astelly Date 2009-07-29 Time 14:17 Sent To  
Notes
***NONE***