| Plan Review Stops For Permit 09020001 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2009-11-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-11-10 |
Time |
12:00 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2009-11-10 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2009-11-10 12:01:33 | REV# 3 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
N |
Date |
2009-03-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-03-16 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-03-16 |
Time |
15:58 |
Sent To |
PC |
|
| Notes |
| 2009-03-16 16:10:24 | 3/16/09 PROCESS PLANS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-03-13 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-03-13 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-03-05 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2009-03-06 13:57:24 | BUILDING PLAN REVIEW | | | PERMIT: 09020001 | | | ADD: 101 NORTH CLEMATIS STREET | | | CONT: MARCINKO AND RAPPA CONST. INC. | | | TEL: (561)793-3191 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3/6/09 | | | REVIEW: 2ND | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) OK | | | 3) OK | | | 4) OK | | | | | | 5) NOTE: THE SECOND FLOOR DEMOLITION PLAN DOES NOT SHOW | | | ANY WALL HANGING OVER THE FIRST FLOOR. PROVIDE A DETAIL | | | DRAWING FOR THE NEW WALL AT THE EXISTING RAILING AND | | | HOW THE TEMPERED GLASS WILL BE HELD IN PLACE SEE SHEET | | | #1. ADDITIONAL INFORMATION IS REQUIRED TO CLEARLY SHOW | | | THE EXTENT OF THE WORK. PROVIDE AN EXISTING AND A | | | PROPOSED FLOOR PLAN SHOWING ALL AFFECTED AREAS. THE | | | DRAWINGS SUBMITTED SHALL BE OF DRAFTSMAN QUALITY | | | SHOWING ALL DIMENSIONS OF THE WORK AREA. NOTE: PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. 106.1.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION | | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | | THE LOCATION, NATURE & EXTENT OF THE WORK PROPOSED & | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS | | | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, AND RULES | | | AND REGULATIONS AS DETERMINED BY THE BUILDING OFFICIAL. | | | PROVIDE A WALL LEGEND SHOWING THE EXISTING WALLS AND | | | THE NEW WALLS WITH A DETAIL OF EACH WALL. | | | | | | 6) OK | | | 7) OK | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-02-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-02-06 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-02-06 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2009-02-06 16:43:00 | BUILDING PLAN REVIEW | | | PERMIT: 09020001 | | | ADD: 101 NORTH CLEMATIS STREET | | | CONT: MARCINKO AND RAPPA CONST. INC. | | | TEL: (561)###-#### | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER | | | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION | | | SHALL BE INDICATED ON THE DRAWINGS. | | | | | | 4) INDICATE THE USE AND OCCUPANCY OF THE BUILDING PER | | | FBC CHAPTER 3 AND TABLE 503 AND THE TYPE OF BUILDING | | | PER CHAPTER 6 AND TABLE 601. | | | | | | 5) ADDITIONAL INFORMATION IS REQUIRED TO CLEARLY SHOW | | | THE EXTENT OF THE WORK. PROVIDE AN EXISTING AND A | | | PROPOSED FLOOR PLAN SHOWING ALL AFFECTED AREAS. THE | | | DRAWINGS SUBMITTED SHALL BE OF DRAFTSMAN QUALITY | | | SHOWING ALL DIMENSIONS OF THE WORK AREA. NOTE: PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. 106.1.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION | | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | | THE LOCATION, NATURE & EXTENT OF THE WORK PROPOSED & | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS | | | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, AND RULES | | | AND REGULATIONS AS DETERMINED BY THE BUILDING OFFICIAL. | | | PROVIDE A WALL LEGEND SHOWING THE EXISTING WALLS AND | | | THE NEW WALLS WITH A DETAIL OF EACH WALL. | | | | | | 6) 2004 FBC (EXISTING) 301.5 A DESIGN PROFESSIONAL OR | | | AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF | | | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF | | | THIS CODE. STATE THE LEVEL OF ALTERATION ON THE PLANS. | | | | | | 7) THE SHEETS SUBMITTED SHALL BE SIGN, SEAL AND DATED | | | PER SECTION 106.1/ FAC 61G15-23.002/ 61G1-16.004 AND | | | 481.221. | | | NOTE: A COMPLETE REVIEW CANNOT BE ACCOMPLISHED WITH THE | | | DRAWINGS SUBMITTED; ADDITIONAL MAY BE MADE WHEN PLANS | | | WITH SUFFICIENT INFORMATION ARE SUBMITTED. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2009-12-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-12-29 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-11-20 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2009-12-29 11:51:35 | | | | | | | REVISION DENIED | | | | | | THE FOLLOWING ARTICLES ARE FROM THE 2005 NEC. | | | | | | 1} 240.24 (E) NOT LOCATED IN BATHROOMS IN DWELLING | | | UNITS AND GUEST ROOMS OR GUEST SUITES OF HOTELS AND | | | MOTELS, OVERCURRENT DEVICES, OTHER THAN SUPPLEMENTARY | | | OVERCURRENT PROTECTION, SHALL NOT BE LOCATED IN | | | BATHROOMS.*** REMOVING THE WALL FROM THE DRESSING AREA | | | NOW CREATES THIS VIOLATION. | | | | | | 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-03-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-03-12 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-03-12 |
Time |
16:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-02-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-02-10 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-02-10 |
Time |
10:05 |
Sent To |
|
|
| Notes |
| 2009-02-10 10:29:35 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 | | | FS, RESPECTIVELY. | | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | | IF EXEMPTIONS APPLY. | | | | | | 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS | | | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES | | | FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3 | | | FBC AS AMENDED. | | | | | | 3} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN | | | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF | | | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE | | | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE PLAN | | | | | | 4} NOT ENOUGH INFORMATION TO DETERMINE COMPLIANCE WITH | | | THE NEC OR OTHER PERTINENT CODES. 106.1.1 FBC | | | "CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL (SEE ALSO SECTION 106.3.5). | | | | | | 5} PLEASE SUBMIT A FLOOR PLAN AND INDICATING THE | | | LOCATION OF ALL EQUIPMENT AND DEVICES BEING INSTALLED | | | UNDER THE SCOPE OF THIS APPLICATION.106.1.1 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-03-16 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-03-16 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-03-16 |
Time |
13:21 |
Sent To |
B1 |
|
| Notes |
| 2009-03-16 13:27:55 | *****APPROVED***** | | | | | | | | | PLAN SHEET 2 OF 2 WAS STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-02-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-02-11 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-02-11 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2009-02-11 10:02:14 | ***DENIED*** | | | | | | PLEASE NOTE THAT MORE INFORMATION IS REQUIRED BEFORE A | | | COMPLETE FIRE REVIEW CAN BE CONDUCTED. CLARIFY THE | | | SCOPE OF WORK AS IT APPLIES TO THIS PERMIT APPLICATION. | | | | | | 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | | SAFETY SHALL COMPLY WITH NFPA 101, 2006. THIS CURRENT | | | CODE EDITION WAS ADOPTED ON DECEMBER 31, 2008. | | | | | | 2) INDICATE THE OCCUPANCY CLASSIFICATION FOR THIS | | | PROJECT. | | | | | | 3) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. FBC 106.1.1 | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-11-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-11-05 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-11-05 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2009-11-05 09:38:11 | SENT TO C-18. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-02-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-26 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-26 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2009-02-26 09:32:26 | TO "BOB"#14 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-02-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-02-11 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-02-03 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2009-02-03 08:48:21 | TO "BOB"#5 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-11-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-11-10 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-11-10 |
Time |
17:04 |
Sent To |
|
|
| Notes |
| 2009-11-10 17:05:21 | REVISION OK -- SANT RISER DIAGRAM & FLOOR PLAN FOR | | | POWDER ROOM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2009-03-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-12 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-12 |
Time |
14:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-02-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-02-05 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-02-05 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2009-02-05 11:08:27 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. MORE INFORMATION IS REQUIRED. SUBMIT AN EXISTING | | | FLOOR PLAN SO THAT THE EXTENT OF WORK CAN BE VERIFIED. | | | SECTION 106.1.2. MORE COMMENTS MAY BE FORTHCOMING. | | | | | | 2. SHEET SUBMITTED SHALL BE SIGNED, SEALED & DATED. | | | SECTION 106.1, FAC 61G1-16.002, 61G1-15.002 & FS | | | 481.2055, 471.025. | | | | | | 3. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW INDETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS AS DETERMINED | | | BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5). | | | SECTION 106.1.1. | | | | | | 4. IT APPEARS THAT TWO SEPARATE UNITS ARE BEING | | | COMBINED INTO ONE SINGLE UNIT. PLEASE CLARIFY. SECTION | | | 106.1.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2009-02-03 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2009-02-03 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2009-02-03 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2009-02-03 10:43:06 | ZONING REVIEW: NOT REQUIRED | | | | | | ** INTERIOR REMODEL ONLY | | | | | | MATT FLIS - 822-1445 |
|
|