Plan Review Details - Permit 09010434
Plan Review Stops For Permit 09010434
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2009-12-15 Cont ID  
Sent By jwitmer Date 2009-12-15 Time 20:21 Rev Time 1.50
Received By jwitmer Date 2009-12-15 Time 20:21 Sent To  
Notes
2009-12-15 20:22:05LS1.1 REVISION# 9 12-09-09
 A1.0 REVISION# 9 12-09-09
 A1.1 REVISION# 9 12-09-09
 A2.0 REVISION# 9 12-09-09
 A2.1 REVISION# 9 12-09-09
 A2.2 REVISION# 9 12-09-09
 A4.1 REVISION# 9 12-09-09
 A4.2 REVISION# 9 12-09-09
 A7.1 REVISION# 9 12-09-09
 A8.1 REVISION# 9 12-09-09
 A9.1 REVISION# 9 12-09-09
 A10.1 REVISION# 9 12-09-09
 A11.2 REVISION# 9 12-09-09
 A11.3 REVISION# 9 12-09-09
 A11.4 REVISION# 9 12-09-09
 12.1 REVISION# 9 12-09-09

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-11-30 Cont ID  
Sent By jwitmer Date 2009-11-30 Time 14:39 Rev Time 3.33
Received By jwitmer Date 2009-11-30 Time 14:39 Sent To  
Notes
2009-11-30 14:42:55REVISION# 09110506
  
 A2.0 REV# 4 9-11-09
 A2.2 REV# 4 9-11-09
 A8.1 REV# 4 9-11-09
 A9.1 REV# 4 9-11-09
 RE-5 REV# 5 9-08-09
 RE-6 REV#5 9-08-09
 RE-7 REV# 5 9-08-09
 RE-8 REV# 5 9-08-09
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-10-29 Cont ID  
Sent By jwitmer Date 2009-10-29 Time 09:30 Rev Time 0.50
Received By jwitmer Date 2009-10-29 Time 09:00 Sent To  
Notes
2009-10-29 09:31:391 PAGE MISSING FORM ONE SET LAST REVISION # 7 10-27-09

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-10-26 Cont ID  
Sent By jwitmer Date 2009-10-26 Time 17:58 Rev Time 0.00
Received By jwitmer Date 2009-10-26 Time 17:03 Sent To  
Notes
2009-10-26 17:42:46 
 3 SETS OF PLANS/ 2 SETS OF PRODUCT APPROVALS
 REVISIONS:
 T1.1 REV# 7 10-21-09
 LS1 REV# 7 10-21-09
 A1.1 REV# 7 10-21-09
 A12.1 REV# 5 10-05-09
  
 NOTE 3RD SET OF PLANS IS MISSING A12.1 REV# 5 10-05-09

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2009-10-08 Cont ID  
Sent By jwitmer Date 2009-10-08 Time 18:30 Rev Time 1.50
Received By jwitmer Date 2009-10-08 Time 15:08 Sent To  
Notes
2009-10-08 18:30:08BUILDING PLAN REVIEW
 PERMIT: 09010434
 ADD: 651 OKKECHOBEE BLVD SUITE 150
 CONT: SHAWMUT DESIGN & CONSTRUCTION
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 OCT. 8/2009
 REVISION# 4 REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE A NEW UPDATED LIFE SAFETY PLAN PER
 106.3.5.1.1(7).
 1A)COMPLIED.
  
 1B) COMPLIED.
  
 1C) SECOND REQUEST, THE MAIN ENTRY DOOR ON TTHE
 ORIGINAL PLANS WAS A PAIR OF DOORS. THE CURRENT
 REVISION HAS MOVED THE MAIN ENTRY DOOR AND DOWN SIZED
 IT TO A SINGLE 3'-4" DOOR.THE ALLOWABLE OCCUPANT LOAD
 THROUGH THE 38" 9CLEAR OPENING) DIVIDE BY .2= 190
 OCCUPANTS. THE UPDATED OCCUPANCY COUNT IS 409. THE DOOR
 WIDTH IS SHORT OF THE REQUIRED WIDTHFOR 205 OR 41
 INCHES CLEAR OPENINGA MINIMUM OF 43" DOOR. PLEASE
 REVIEW SECTION 1025.2 ASSEMBLY MAIN EXIT.
  
 1D) SEECOND REQUEST, A1.1 OPEN AIR DINING PLEASE
 INDICATE OPENING# 108E TO BE A REQUIRED 90 MINUTE
 OPENING PROTECTIVE AS PER SHEET A4.2 AND TABLE 704.8
 PRODUCT APPROVALS SUBMITTED ARE FOR A 16'-0" ROLLING
 STEEL DOOR NOA 08-0805.15.
  
 1E)COMPLIED.
  
 2) COMPLIED.
  
 3) SEMI-COMPLIED. MISSING ROLL DOWN FIRE SHUTTER WITH
 LARGE MISILLEIMPACT TESTING. SHEET A1.1 INDICATES NEW
 EXTERIOR OPENINGS PLEASE INDICATE COMPLIANCE WITH
 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 3A) EXTERIOR FOLDING DOOR SYSTEMS- NO APPROVAL WAS
 SUBMITTED
 3B) EXTERIOR GLAZED DOORS W/ SIDE LITES & TRANSOM
 (100A)- NO APPROVAL WAS SUBMITTED
 3C)HORIZONTAL MULLIONS- NO APPROVAL WAS SUBMITTED
 3D) ROLL DOWN SHUTTERS SUBMITTAL REVIEWED
 3E) ROLL DOWN FIRE SHUTTER W/ LARGE MISSILE IMPACT
 TESTING
 3F) CURTAIN WALL- SUBMITTED -NOT REQUIRED?
  
 4) SEECOND REQUEST, 106.3.3 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5)SEECOND REQUEST 50% OF THE OCCUPANT LOAD NEEDS TO BE
 ABLE TO COME BACK THROUGH THE MAIN ENTRY PLEASE SEE
 COMMENT 1C/ SECTION 1025.2. . DISCREPANCY IN PLANS
 PLEASE REVIEW A1.1(FLOOR PLAN), A10.1 DETAIL 2( FRONT
 ENTRY INTERIOR ELEVATION) AND A4.1(ELEVATIONS) ON THE
 FRONT ELEVATIONS MAIN ENTRY MISSING THE DOUBLE DOORS
 PLEASE CORRECT THE DISCREPANCY. WITH THE ELIMINATION OF
 THE DOUBLE FRONT ENTRY DOOR PLEASE PROVIDE COMPLIANCE
 WITH1024.2.
  
 6) COMPLIED.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-09-28 Cont ID  
Sent By jwitmer Date 2009-09-28 Time 18:30 Rev Time 1.50
Received By jwitmer Date 2009-09-28 Time 17:01 Sent To  
Notes
2009-09-28 18:31:45BUILDING PLAN REVIEW
 PERMIT: 09010434
 ADD: 651 OKKECHOBEE BLVD SUITE 150
 CONT: SHAWMUT DESIGN & CONSTRUCTION
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION# 4 REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE A NEW UPDATED LIFE SAFETY PLAN PER
 106.3.5.1.1(7).
 1A) SHEET A1.0 INDICATES A PRIVATE DINING ROOM# 3 BUT
 THE OCCUPANT LOAD IS NOT FIGURED IN ON THE OCCUPANCY
 LOADS SHEET T1.1.
  
 1B) SHEET A1.0 & A1.1 BOTH INDICATE A SLIDING DOOR
 LEAVING ONLY ONE EGRESS DOOR INTO AND EXITING THE
 PRIVATE DINING ROOM# 3 PLEASE REVIEW SECTION TABLE
 1014.1 SPACES WITH ONE MEANS OF EGRESS, IF 50 OR MORE
 OCUPANTS TWO EGRESS DOORS WILL BE REQUIRED .
  
 1C) SHEET A1.1 MAIN ENTRY HAS BEEN SHIFTED TO WHERE AN
 EXISTING COLUMN IS WITHIN 2'-0" OF THE DOUBLE DOORS
 BLOCKING EGRESS FROM ONE OF THE DOORS, PLEASE REVISE
 THE MINIMUM CLEAR WIDTH OF EXIT DOORS FOUND ON THE T1.1
 SHEET TO REFLECT THE ONE DOOR NOT BEING ACTIVE.
  
 1D) A1.1 OPEN AIR DINING PLEASE INDICATE OPENING# 108E
 TO BE A REQUIRED 90 MINUTE OPENING PROTECTIVE AS PER
 SHEET A4.2 AND TABLE 704.8
  
 1E) PLEASE ALSO INDICATE THE LOCATION OF PORTABLE FIRE
 EXTINGUISHERS AS PER SECTION 906.1.
  
 2) PLANS INDICATE NEW WINDOWS AND DOORS WITHIN THE
 EXTERIOR ENVELOPE OF THE BUILDING. PLEASE PROVIDE THE
 POSSITIVE AND NEGATIVE PRESSURES FOR THE HIGHRISE AS
 PER ASCE 7-05, NEGATIVE PRESSURES ARE TAKEN FROM ROOF
 LEVEL, POSITIVE FROM GROUND LEVEL.
  
 3) SHEET A1.1 INDICATES NEW EXTERIOR OPENINGS PLEASE
 INDICATE COMPLIANCE WITH 1609.1.4 PROTECTION OF
 OPENINGS IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING
 THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET
 (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS
 AND THE BALANCE OF GLAZED OPENINGS IN THE REST OF THE
 BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT
 RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E
 1886 AND ASTM E 1996, OR MIAMI-DADE TAS 201, 202 AND
 203 REFERENCED THEREIN AS FOLLOWS: 1. GLAZED OPENINGS
 LOCATED WITHIN 30 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST. 2. GLAZED
 OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) ABOVE GRADE
 SHALL MEET THE PROVISIONS OF THE SMALL MISSILE TEST.
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 3A) EXTERIOR FOLDING DOOR SYSTEMS
 3B) EXTERIOR GLAZED DOORS W/ SIDE LITES & TRANSOM
 (100A)
 3C)HORIZONTAL MULLIONS
 3D) ROLL DOWN SHUTTERS
 3E) ROLL DOWN FIRE SHUTTER W/ LARGE MISSILE IMPACT
 TESTING
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) DISCREPANCY IN PLANS PLEASE REVIEW A1.1(FLOOR PLAN),
 A10.1 DETAIL 2( FRONT ENTRY INTERIOR ELEVATION) AND
 A4.1(ELEVATIONS) ON THE FRONT ELEVATIONS MAIN ENTRY
 MISSING THE DOUBLE DOORS PLEASE CORRECT THE
 DISCREPANCY. WITH THE ELIMINATION OF THE DOUBLE FRONT
 ENTRY DOORPLEASE PROVIDE COMPLIANCE WITH1024.2.
  
 6) SHEET A12.1 INDICATES IN THE MAIN DINING ROOM# 1
 (106) AN ACCESSIBLE LOCATION AT A TABLE JUST TO THE
 RIGHT OF THE MAIN ENTRY PLEASE REVIEW SECTION
 1024.9.1.1 REQUIRING A CLEARR 44" MEANS OF EGRESS WHEN
 SERVING AN OCCUPANT LOAD OF 50 OR MORE.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-07-06 Cont ID  
Sent By jwitmer Date 2009-07-06 Time 14:18 Rev Time 1.11
Received By jwitmer Date 2009-07-06 Time 13:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-05-19 Cont ID  
Sent By jwitmer Date 2009-05-19 Time 14:53 Rev Time 0.88
Received By jwitmer Date 2009-05-19 Time 13:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-11 Cont ID  
Sent By mjacobs Date 2009-02-11 Time 16:55 Rev Time 0.00
Received By mjacobs Date 2009-02-11 Time 16:55 Sent To  
Notes
2009-02-11 16:55:38BUILDING PLAN REVIEW
 PERMIT: 09010434
 ADD: 651 OKEECHOBEE BLVD SUITE 150
 CONT: SHAWMUT WOODWORKING AND SUPPLY INC.
 TEL: (617)622-7000
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW1
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) 61G1-16.004 THE TITLE BLOCK SHALL MEET THE
 REQUIREMENTS BELOW.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 4) FBC 11-5. THE PLANS NEED TO INDICATE THE ACCESSIBLE
 DINING AT THE BAR, LOUNGE AND THE THREE PRIVATE DINNING
 AREAS. ACCESSIBLE FIXED TABLES SHALL BE DISTRIBUTED
 THROUGHOUT THE SPACE OR FACILITY. NO ACCESSIBLE SPACES
 ARE SHOWN IN THE AREAS MENTION ABOVE. SHOW COMPLIANCE.
  
 5) THE DRAWING SHALL BE APPROVED BY THE CITY PLACE
 OFFICE AND CONTAIN THE STAMP OF APPROVAL FROM THAT
 OFFICE WITH THE INITIAL OF THE PERSON STAMPING THE
 PLANS. NOTE: EACH SHEET REQUIRES THE CITY PLACE OFFICE
 STAMP.
  
 6) NOTE: FBC 11-4.32.2 SEATING. IF SEATING SPACES FOR
 PEOPLE IN WHEELCHAIRS ARE PROVIDED AT FIXED TABLES OR
 COUNTERS, CLEAR FLOOR SPACE COMPLYING WITH SECTION
 11-4.2.4 SHALL BE PROVIDED. SUCH CLEAR FLOOR SPACE
 SHALL NOT OVERLAP KNEE SPACE BY MORE THAN 19 INCHES
 (SEE FIGURE 45). ALL FIXED SEATING IN PUBLIC FOOD
 SERVICE ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED
 UNDER THE BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES,
 AND IN ALL OTHER FACILITIES GOVERNED BY REFERENCE
 SECTION 11-4.1 SHALL BE DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH THE FOLLOWING REQUIREMENTS:
 (1) ALL AISLES ADJACENT TO FIXED SEATING SHALL PROVIDE
 CLEAR FLOOR SPACE FOR WHEELCHAIRS.
 (2) WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES OF
 SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52
 INCHES (1321 MM) WIDE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2009-10-16 Cont ID  
Sent By dpalmer Date 2009-10-16 Time 10:02 Rev Time 0.00
Received By dpalmer Date 2009-10-16 Time 10:02 Sent To PC
Notes
2009-10-16 10:03:42SEPARATE PERMITS STILL REQUIRED FOR LOW VOLTAGE, FIRE
 ALARM AND FIRE SPRINKLER.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2009-10-09 Cont ID  
Sent By dpalmer Date 2009-10-09 Time 17:37 Rev Time 0.00
Received By dpalmer Date 2009-10-09 Time 17:37 Sent To  
Notes
2009-10-09 17:37:22 
  
 ** DENIED **
  
  
 1) NOTE: PLEASE SEE NOTES FORM PREVIOUS REVIEW. PLANS
 STILL INDICATE STANDARD LIGHTING CONTROL DEVICES SUCH
 AS SP DIMMERS. PLAN CONTAINS
 A NOTE WHICH MENTION TO SEE DETAILS ON SHEET E2.1.
 HOWEVER THE DETAIL AND TYPES OF DEVICES DO NOT COMPLY
 WITH SECTIONS FOR PRESCRIPTIVE REQUIREMENTS FOR NEW
 BEING INSTALLED.
 THE NEW TYPES OF SWITCHES ARE DEVICES WHICH GO UP TO
 8HRS. THE CODE DOES NOT ALLOW MORE THAN FOUR. THE CODE
 REQUIRES THE OCCUPANT TO SEE ALL LIGHTING WHICH IS
 BEING OVER RIDDEN OR MEET EXCEPTIONS. THE DEVICE IS NOT
 LOCATED SO THE OCCUPANT CAN SEE LIGHTING BEING
 CONTROLLED AND THE OVER RIDE DEVICE SPECIFIED ON PLANS
 ( SSA-200) DOES NOT MEET EXCEPTION FOR PILOT/INDICATOR
 LIGHTS.
 THE DIAGRAM ALSO INDICATES A SQUARE D PRODUCT
 #8501C015V20 WHICH DOES NOT COME UP ON THEIR WEBSITE
 BUT IS ACTUALLY NOTED AS A MANUAL OVER RIDE OF TIMED
 SYSTEM WHICH CAN LEAVE ON DEVICES PERMANENTLY WITHOUT
 AUTOMATED CONTROL. AS SHOWN ON DETAIL THE SPDT SWITCH
 WILL BYPASS TIMED OVER RIDE ENERGIZING THE COIL ON LCP
 AND LEAVE LIGHTS ON INDEFINITELY. THIS DOES NOT MEET
 THE INTENT OF ENERGY CODE WHICH WILL TURN OFF LIGHTING
 WHEN A BUILDING IS NO OCCUPIED.
  
 THE LIGHTING CONTROLS FOR EXTERIOR LIGHTS CAN NOT BE
 CONFIRMED MEETING 13-415.1.ABC.1.4. THIS SECTION OF THE
 CODE REQUIRES ONE OF THE TWO METHODS OR BOTH. NOTE ON
 PLANS MENTIONS TO EXISTING CONTROL HOWEVER NO
 INFORMATION COULD BE LOCATED. PLEASE VERIFY WHAT IS
 EXISTING IF NEW CONTROL IS NOT INSTALLED.
 THE CODE REQUIRES THIS TO BE AN ASTRONOMICAL TIME CLOCK
 WITH A MINIMUM BACK UP FOR PROGRAMMING. CURRENT CODE
 REQUIRES 10HRS BACK UP. WHEN LOCATION WAS ORIGINALLY
 BUILT IT WOULD BE UNDER MINIMUM OF THE 2001 FBC IF NOT
 INSTALLING NEW CONTROLS.
 SEE NEW AREAS OUTSIDE.
 PRESCRIPTIVE C NOW SUBMITTED FOR FOR TOTAL AREAS ( NEW
 ONLY). CALL AS THIS CAN BE GONE OVER. PREVIOUS METHOD
 SUBMITTED WAS B, NOW METHOD IS C.
  
 2) NOTE: AS NOTED ON THE PREVIOUS REVIEW. REVIEW FOR
 MINIMUM CODE COMPLIANCE FOR LIGHTING PERFORMANCE
 CALCULATIONS CAN NOT BE DONE WITHOUT A COMPLETE FIXTURE
 LEGEND/SCHEDULE. THE A SHEETS ARE NOT SUBMITTED WIHT
 THE ELECTRICAL. THANK YOU FOR THE COPY ON THE BACK OF
 THE CALCULATIONS, HOWEVER BASED ON THE FIXTURES LISTED,
 NOT ALL FIXTURES WHICH ARE ON PLANS ARE SHOWN/NOTED.
 IS THERE ANY INFORMATION ON EIXSTING FIXTURES?
 PLEASE SUBMIT A FIXTURE LEGEND/SCHEDULE ON ELECTRICAL
 PLANS FOR REVIEW.
 13-415.2.ABC.1.1,.1.2, 13-415.2.ABC.1, 13-415.2.C
  
 3) NOTE: TO DATE NO SUB-PERMITS HAVE BEEN APPLIED FOR
 ELECTRICAL, PLUMBING, MECHANICAL, FIRE ALARM, OR LOW
 VOLTAGE SYSTEMS.
 FBC 105.1
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY
 NOTICE GIVEN AT THIS TIME DUE TO REPEAT COMMENTS FOR
 CODE COMPLIANCE.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO THE
 VALUATION OF THE PROJECT. NO ADJUSTMENT FOR APPLIED
 SCOPE OF WORK HAS BEEN SUBMITTED FOR VERIFICATION.
 ALL LABOUR, MATERIALS, EQUIPMENT, DESIGN COSTS ETC ARE
 REQUIRED TO BE FIGURED EVEN IF OWNER SUPPLIED. FBC
 108.3
 THE ORIGINAL SCOPE OF WORK AND APPLIED VALUE IS
 SUBSTANTIALLY LESS THAN THE WORK AT THIS TIME.
  
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2009-09-25 Cont ID  
Sent By dpalmer Date 2009-09-25 Time 16:49 Rev Time 0.00
Received By dpalmer Date 2009-09-25 Time 16:49 Sent To  
Notes
2009-09-25 16:49:36 
  
  
 ** DENIED PLANS **
  
 ** PERMIT WAS APPLIED FOR UNDER THE 2004 FBC W/ 2007
 REVISIONS.
  
  
  
 1) NOTE: THE SUBMITTED LIGHTING CALCULATIONS ARE FROM
 FLA COM METHOD B UNDER THE NEW CODE.
 PLEASE KNOW THAT CALCULATIONS SHOULD BE UNDER THE CODE
 IN WHICH THE APPLICATION IS UNDER. IF USING THE NEW
 MORE RESTRICTIVE CODE AS SUBMITTED THE DESIGN WATTAGE
 IS HIGHER THAN THE ALLOWANCE. THE EFFECTIVE IS SHOWN
 LOWER THAN ALLOWANCE HOWEVER PER 13-415.AB.5, DISPLAY,
 DECRETIVE LIGHTING IS NO LONGER EXEMPT, OR ALLOWS ANY
 ADDITIONAL ALLOWANCES.
  
 ** PLEASE SUBMIT COMPLIANCE UNDER THE CODE IN WHICH
 PERMIT WAS MADE.
 ** PLEASE CALL TO GO OVER AS THIS IS A TOPIC WHICH HAS
 BEEN TAKEN UP WITH THE STATE ON THE CODE CHANGES AND
 THE ITEMS NOT BEING CHANGED OR REVISED IN THE FLA COM
 PROGRAM.
  
 ** AS THERE IS NO FIXTURE LEGEND/INFORMATION SUBMITTED
 REVIEW FOR CODE COMPLIANCE CAN NOT FULLY BE DONE.
  
 ** METHOD OF CONTROL ON THE IDR IS NOT ALL GOING TO BE
 *MANUAL ON/ OFF*
  
 2) NOTE: PLEASE SEE 13-415.A.ABC.1.1,.1.2, .1.3 AND
 .1.4.
 PREVIOUS PLANS INDICATED THAT ALL EXISTING LIGHTING
 CONTROLS WERE TO REMAIN. HOWEVER NEW PLANS SHOW
 SUBSTANTIAL AMOUNT OF NEW LIGHTING AND WIRING.
 MUST MEET PRESCRIPTIVE FOR NEW CONTROLS BEING
 INSTALLED.
  
 3) NOTE: NEW EXTERIOR LIGHTING SHALL MEET
 13-415.1.ABC.1.4 FOR CONTROLS. NO INFORMATION ON PLANS.
  
 4) NOTE: PLEASE SEE 13-415.2.ABC.1.1, .1.2 FOR EXTERIOR
 LIGHTING ALLOWANCES.
  
 5) NOTE: PLEASE SEE NOTES FROM PREVIOUS PROVISO FOR
 REQUIRED UPDATING OF LOAD CALCULATIONS. THE PLANS DO
 HAVE REVISIONS HOWEVER PLANS ALSO INDICATE CALCULATIONS
 AND CODE SECTIONS WHICH ARE NO LONGER APPLICABLE. SE3E
 E2.1 WHICH SHOWS NEC 220.35. THIS SECTION WAS FROM THE
 2002 NEC.
 PLEASE UPDATE AND REVISE.
  
 6) NOTE: PLANS CONTAIN SEVERAL NEW FIRE ALARM DEVICES
 HOWEVER PER THE SYMBOL LEGEND NO INFORMATION IS
 PROVIDED FOR DEVICES MEETING FBC 11-4.28.1, .2 AND .3.
 ** PLEASE KNOW THAT EVEN AS SEPARATE FIRE ALARM PERMIT
 WILL BE REQUIRED, THE BASE PLANS SHALL SHOW BASE DESIGN
 REQUIRED FOR FIRE, LIFE SAFETY AND ADA COMPLIANCE.
  
 7) NOTE: THE SCOPE OF WORK HAS SUBSTANTIALLY INCREASED.
 THE APPLIED VALUE NEEDS TO BE ADJUSTED PER FBC 108.3
 THE SCOPE SHALL INCLUDE ALL LABOR, MATERIALS, FIXTURES,
 EQUIPMENT, DESIGN COST ETC EVEN IF ANY OF THESE ITEMS
 ARE OWNER SUPPLIED AND NOT PART EQUIPMENT AND OTHER
 ITEMS SUPPLIED BY THE CONTRACTOR.
  
 ** AS STATED ABOVE THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW FOR CODE COMPLIANCE REVIEW? THERE
 MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN
 NOT BE MADE AT THIS TIME.
  
  
  
  
 ** IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-07-03 Cont ID  
Sent By dpalmer Date 2009-07-03 Time 17:22 Rev Time 0.00
Received By dpalmer Date 2009-07-03 Time 17:22 Sent To  
Notes
2009-07-03 17:22:12 
  
 ** PROVISO **
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW THERE IS AN
 INCREASE ON LOAD ON MORE THAN ONE CIRCUIT. IT IS
 UNDERSTOOD THAT THE OVER ALL LOAD MAY NOT BE AFFECT
 HOWEVER THE SPECIFIC CIRCUIT LOAD FOR #29 AND #30 HAS
 INCREASED. THERE IS NO INDICATION ON THE ACTUAL BRANCH
 CIRCUIT PROVIDED AS EXISTING.
 REVISED CIRCUITING ON PLANS COORDINATING WITH REVISED
 PANEL SCHEDULE(S) WILL BE REQUIRED.
 408.4,220,310.16 ETC
 FBC 106.1.1,106.1.2, 106.5 AS RECORD PLANS SHALL
 INCLUDE AN ACCURATE DEPICTION OF WHAT IS LOCATED
 ON-SITE.
  
 ** THESE NEED TO BE SUBMITTED BEFORE INSPECTIONS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-07-03 Cont ID  
Sent By dpalmer Date 2009-07-03 Time 14:02 Rev Time 0.00
Received By dpalmer Date 2009-07-03 Time 14:02 Sent To  
Notes
2009-07-03 14:05:46 
 ** TEMP/DENIED
  
  
 1) NOTE: CALLED ENGINEER, CONTRACTOR AND PERMIT
 EXPEDITOR.
 THE SELECTIVE COORDINATION STUDY HAS SOME CONFLICTS
 WITH A PORTION DATED APRIL OF 2009 WITH COVER SHEET
 COMPARED TO THE REPORT OF JUNE 2009. A CALLED WAS
 PLACED TO ENGINEER HOWEVER OFFICE WAS CLOSED. NEED TO
 GO OVER AS TITLE DOES LIST SECTION TWO AS NORMAL AND
 SECTION THREE AS EMERGENCY WHEN IN FACT IT APPEARS EACH
 SECTION CONTAINS NORMAL AND EMERGENCY. ONE DATED IN
 04/09 AND THE OTHER 06/09. IT APPEARS THE 04/09 SHOUDL
 NTO BE IN THE SUBMITTED DOCUMENTS AS THE TIME CURVES
 AND OTHER SUPPORTING INFORMATION WAS ALL RUN IN 06/09.
  
 2) NOTE: NEED SECOND SET OF SIGNED, DATED AND SEALED
 FLA-COM LIGHTING PERFORMANCE CALCULATIONS. FBC 13-103,
 FS 471.025. SPOKE TO NAT HEALY AS NEW CALCULATIONS WILL
 BE SENT FED-EX.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-05-14 Cont ID  
Sent By dpalmer Date 2009-05-14 Time 08:17 Rev Time 0.00
Received By dpalmer Date 2009-05-14 Time 08:17 Sent To  
Notes
2009-05-14 08:17:39**DENIED REVIEW **
  
  
  
 1) NOTE: PREVIOUS REVIEW NOTE: PLEASE SEE FBC
 13-415.2,13-415.2.ABC.1.1, .1.2. THE NEW SUBMITTED
 ENERGY CALCULATIONS CAN NOT BE VERIFIED AS THE PLANS DO
 NOT LIST THE FIXTURE, FIXTURE TYPES, FIXTURES WATTAGES
 ETC.
 NO COMPLIANCE CAN BE KNOWN BASED ON INFORMATION NOT YET
 RECEIVED. IT IS NOT POSSIBLE TO REVIEW THE INPUT DATA
 REPORT AND COMPARE TO PLANS FOR FIXTURE COUNTS AND TYPE
 FOR COMPLIANCE.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE
 FIXTURES BEING ADDED WHICH MUST BE LISTED WITH A
 NATIONALLY RECOGNIZED TESTING LABORATORY. ( NRTL).
 EXAMPLES OF SOME HOWEVER NOT ALL WOULD BE. CSA, MET,
 ETL, TUV, TUV AMERICA, UL, ETC. PLEASE SEE THE ADOPTED
 LIST PER OSHA.
 BASED ON THE PRODUCT DATA SUBMITTED THERE WAS NO
 LISTING FROM A NRTL READILY SEEN?
 NEC 110.3
  
 3) NOTE: SEVERAL NOTES ON THE PLANS STATE ALL LOCATIONS
 NOTED HAVE EQUAL OR LESSER POWER REQUIREMENT THAN
 PREVIOUS CONNECTED LOADS. HOWEVER BASED ON THE
 EQUIPMENT PLANS SUBMITTED THERE IS NEW EQUIPMENT WHICH
 DOES INCREASE LOADS. AN EXAMPLE OF THIS IS THE NEW
 ELECTRIC OVEN, TILTING SKILLET ETC.
 NEED TO SUBMIT THE EXISTING LOADS WITH THE INCREASED
 LOADS AND PANEL SCHEDULE SPECIFIC TO THE NEW EQUIPMENT.
 BASED ON THE PLANS IT CAN NOT BE DETERMINED IF THE
 EXISTING PANELS AND LOADS ON THE SERVICE EQUIPMENT IS
 ADEQUATE.
 PLEASE COMPLETE AND SUBMIT.
 240.4,310.16,408.4, 220.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-12 Cont ID  
Sent By dpalmer Date 2009-02-12 Time 13:29 Rev Time 0.00
Received By dpalmer Date 2009-02-12 Time 13:29 Sent To  
Notes
2009-02-12 13:29:34** DENIED REVIEW **
  
 1) NOTE: ALL PLANS SHALL CONTAIN CITY PLACE MANAGEMENT
 STAMP AS REVIEWED. THIS IS A CITY PLACE REQUIREMENT NOT
 A LOCAL CODE, ORDINANCE OR LOCAL ADMINISTRATIVE CODE
 REQUIREMENT.
  
 2) NOTE: ALL TITLE BLOCKS FOR ALL DESIGN TEAMS ARE
 REQUIRED TO MEET FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND 61G15-23.002.
 FLORIDA STATUTES 481.229 AND 471.023 ALSO APPLY FOR
 CERTIFICATE OF AUTHORIZATION NUMBERS WHEN APPLICABLE.
 PLEASE SEE THAT SOME INFORMATION IS CURRENTLY MISSING
 FROM THE ARCHITECTURAL TITLE BLOCKS.
  
 3) NOTE: PLEAS KNOW AS OF DECEMBER 31ST, 2008 THE NEW
 ADOPTED FLORIDA FIRE PREVENTION CODE AND LIFE SAFETY
 CODE CAN BE FOUND ON THE STATE FIRE MARSHAL WEB SITE.
 PLEASE SEE COMMENTS FROM FIRE MARSHAL WITH RESPECT TO
 THE CORRECT NFPA-1. THE ADOPTED NFPA-101 IS THE 2006
 EDITION. NOT THE 2003 AS STATED ON PLANS.
  
 4) NOTE: PLEASE SUBMIT ELECTRICAL PLANS FOR REMODEL
 SCOPE OF WORK INCLUDING ANY NEW LIGHT FIXTURE
 LOCATIONS, REPLACEMENT, NEW ETC.
 AS THERE ARE SEVERAL NEW ITEMS SHOWN FOR EQUIPMENT,
 PLANS SHOWING ELECTRICAL CIRCUITING, RECEPTACLES ETC IS
 NEEDED TO SHOW MINIMUM CODE COMPLIANCE.
 PLEASE BE SURE TO SEE THE 2005 NEC FOR CIRCUITING,
 SIZING, LOADS, LOAD CALCULATIONS, OVER CURRENT
 PROTECTION ETC
 408.4,310.16,240.4,240,220 ETC
 SPECIFIC SECTIONS OF CODES CAN NOT REALLY BE GIVEN
 BASED ON THE FACT NO ELECTRICAL PLANS WERE SUBMITTED.
 FBC 106.1.1,106.1.2,106.3.5.1.2,106.5 AS ADOPTED BY THE
 CITY OF WEST PALM BEACH. PLANS REQUIRED FOR CLARITY,
 ADDITIONAL INFORMATION, SCOPE AND RECORD SETS OF PLANS
 FOR SCOPE.
  
 5) NOTE: *** IMPORTANT. PLEASE SEE FBC
 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 WITH RESPECT TO
 ANY *NEW* LIGHTING CONTROLS BEING INSTALLED. THIS IS
 NOT FOR EXISTING TO REMAIN THIS IS FOR NEW ONLY. THE
 PLANS STATE FOR EXAMPLE NEW TIME CLOCKS HOWEVER DO NOT
 SHOW ANY OF THESE. ARE THEY FOR INSIDE OR OUTSIDE
 LIGHTING?
 PLEASE BE SURE TO SEE THESE SECTIONS AS NOTED AND CALL
 TO GO OVER ANY COMMENTS OR CONCERNS.
  
  
 6) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1,.1.2
 FOR LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS FOR ALL EXISTING PROPOSED NEW FIXTURES.
 THE ADDITIONS OF NEW LIGHTING FIXTURES WITH WATTAGES
 ARE NOT PERMITTED UNTIL VERIFICATION OF THE EXISTING
 LEVELS CAN BE CONFIRMED. IF THE EXISTING DESIGN EXCEEDS
 THE STATED MAXIMUM ALLOWANCES IN THE CURRENT CODE THEN
 NEW FIXTURES MAY NOT BE ADDED.
 ALL OF THESE NEED TO BE SPECIFIC TO THE NEW AND
 EXISTING.
  
 7) NOTE: PLEASE PROVIDE MANUFACTURES SPECS/CUT SHEETS
 FOR NEW PROPOSED LIGHTING. ALL LIGHTING FIXTURES SHALL
 BE LISTED AND BY A NRTL. (NATIONALLY RECOGNIZED TESTING
 LABORATORY).
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2009-10-26 Cont ID  
Sent By mawillia Date 2009-10-26 Time 15:47 Rev Time 0.00
Received By mawillia Date 2009-10-26 Time 15:39 Sent To  
Notes
2009-10-26 15:47:20*****REVISION #7, DATED 10/21/2009, APPROVED*****
  
  
 REVISED PLAN SHEET LS1.1 AND A1.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-10-26 Cont ID  
Sent By mawillia Date 2009-10-26 Time 15:38 Rev Time 0.00
Received By mawillia Date 2009-10-26 Time 15:22 Sent To  
Notes
2009-10-26 15:32:53*****REVISION #5, DATED 10/05/2009, APPROVED*****
  
  
 REVISED PLAN SHEET LS1.1, A1.1, AND A12.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-09-28 Cont ID  
Sent By mawillia Date 2009-09-28 Time 11:10 Rev Time 0.00
Received By mawillia Date 2009-09-28 Time 10:41 Sent To B1
Notes
2009-09-28 11:07:41*****REVISION #4, DATED 9/11/09, APPROVED*****
  
  
 REVISED SHEET A4.1 STAMPED, INITIALED, AND DATED; SHEET
 E1.2 TO BE FIRE-STAMPED WHEN THE ELECTRICAL EXAMINER'S
 COMMENT HAS BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-07-06 Cont ID  
Sent By mwennerg Date 2009-07-06 Time 13:38 Rev Time 0.00
Received By mwennerg Date 2009-07-06 Time 13:38 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-05-15 Cont ID  
Sent By mawillia Date 2009-05-15 Time 22:08 Rev Time 0.00
Received By mawillia Date 2009-05-15 Time 15:24 Sent To  
Notes
2009-05-18 11:43:16*****FIRE- STAMPING NEEDED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE REVIEW HAVE BEEN
 ADDRESSED; HOWEVER THE APPROPIATE PLAN SHEETS TO BE
 FIRE-STAMPED WHEN THE OTHER PLAN EXAMINERS' COMMENTS
 HAVE BEEN SATISFIED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-02-24 Cont ID  
Sent By mwennerg Date 2009-02-24 Time 15:01 Rev Time 0.00
Received By mwennerg Date 2009-02-24 Time 15:01 Sent To  
Notes
2009-02-24 15:13:10***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE 2007 WHICH INCLUDES NFPA 101, 2006 AND
 NFPA 1, 2006 AS OF DECEMBER 31, 2008. FAC 69A-60.004
 AND FAC 69A-60.003.
  
 2) ALL SHEETS ARE TO BE PROVIDED WITH THE STAMP BY CITY
 PLACE MANAGEMENT OFFICE.
  
 3) SEE OTHER REVIEW COMMENTS REGARDING FAC AND FS
 REQUIREMENTS FOR TITLE BLOCKS.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 5) IF NOT ALREADY PROVIDED, OCCUPANT LOAD SIGNS SHALL
 BE POSTED. PLEASE CONTACT BUREAU OF FIRE PREVENTION AT
 (561) 804-4724 FOR ASSISTANCE.
  
 6) PLANS INDICATE SUITE #150. ALL APPLICABLE ADDRESS
 NUMBERS ARE TO BE NEAR THE FRONT DOOR AND SHALL MEET
 THE CITY OF WEST PALM BEACH SIZE REQUIREMENTS FOR
 COMMERCIAL BUILDINGS.
  
 7) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILINGS.
  
 8) ALTHOUGH NOT IDENTIFIED AS EXITS, IT WOULD APPEAR
 THAT A TABLE AND CHAIR ARRANGEMENT IS OBSTRUCTING EXIT
 DOORS AT THE SOUTHEAST CORNER OF THE BUILDING.
  
 9) WILL THIS WORK IMACT EXISTING FIRE SPRINKLER AND
 FIRE ALARM SYSTEMS?
  
  
 MIKE WENNERGREN,
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2009-06-12 Cont ID  
Sent By kstevens Date 2009-06-12 Time 15:19 Rev Time 0.00
Received By kstevens Date 2009-06-12 Time 15:19 Sent To  
Notes
2009-06-12 15:21:14SEPARATE GAS PERMIT/PLANS REQUIRED. PLANS AND GAS
 APPLICATION TO BE SUBMITTED PRIOR TO GAS WORK/APPLIANCE
 INSTALLATION.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2009-05-06 Cont ID  
Sent By kstevens Date 2009-05-06 Time 13:01 Rev Time 0.00
Received By kstevens Date 2009-05-06 Time 13:01 Sent To  
Notes
2009-05-06 13:02:36DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION FOR REVIEW:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE, NOTED, COMMENT NOT ADDRESSED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
 ****RESPONSE NOTED, INFORMATION REQUIRED ON PLANS.
  
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE BTU LOAD FOR THE RANGE,
 (120,000) DOES NOT REFLECT THE BTU LOAD ON SHT RE-2 GAS
 APPLIANCE TABLE, (180,000). PLEASE CORRELATE.
  
 H. N/A
  
 I. N/A
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, TO BE SHOWN ON RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-03-03 Cont ID  
Sent By kstevens Date 2009-03-03 Time 12:17 Rev Time 0.00
Received By kstevens Date 2009-03-03 Time 12:17 Sent To  
Notes
2009-03-03 12:20:07DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION FOR REVIEW:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-12-14 Cont ID  
Sent By lmartine Date 2009-12-14 Time 16:50 Rev Time 0.00
Received By lmartine Date 2009-12-14 Time 16:50 Sent To  
Notes
2009-12-14 16:55:53******************EXPEDITED*******************
 C--6
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-11-19 Cont ID  
Sent By kstevens Date 2009-11-19 Time 09:40 Rev Time 0.00
Received By kstevens Date 2009-11-19 Time 09:40 Sent To  
Notes
2009-11-19 09:41:18SENT TO FIRE.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-10-26 Cont ID  
Sent By lmartine Date 2009-10-22 Time 09:41 Rev Time 0.00
Received By lmartine Date 2009-10-22 Time 09:41 Sent To  
Notes
2009-10-26 09:42:53ROUTED ON 10/26/09
2009-10-26 09:42:10*****************EXPEDITED***************
 GAVE TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-10-07 Cont ID  
Sent By lmartine Date 2009-10-07 Time 16:58 Rev Time 0.00
Received By lmartine Date 2009-10-07 Time 16:58 Sent To  
Notes
2009-10-07 17:01:11**********EXPEDITED************
 GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-10-07 Cont ID  
Sent By lmartine Date 2009-10-07 Time 16:42 Rev Time 0.00
Received By lmartine Date 2009-10-07 Time 16:42 Sent To  
Notes
2009-10-07 16:43:30***********EXPEDITED****************
 GAVE TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-09-16 Cont ID  
Sent By kstevens Date 2009-09-16 Time 08:52 Rev Time 0.00
Received By kstevens Date 2009-09-16 Time 08:52 Sent To  
Notes
2009-09-16 08:53:01SENT TO C-35.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-06-18 Cont ID  
Sent By lmartine Date 2009-06-17 Time 11:57 Rev Time 0.00
Received By lmartine Date 2009-06-17 Time 11:57 Sent To  
Notes
2009-06-18 12:01:26C-4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 09:12 Rev Time 0.00
Received By dpalmer Date 2009-04-29 Time 09:12 Sent To  
Notes
2009-04-29 09:13:14TO C25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-03 Cont ID  
Sent By kstevens Date 2009-03-03 Time 12:20 Rev Time 0.00
Received By kstevens Date 2009-01-29 Time 16:53 Sent To  
Notes
2009-01-29 16:53:14TO "COMM" BD#34

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-09-22 Cont ID  
Sent By rregueir Date 2009-09-22 Time 17:55 Rev Time 0.00
Received By rregueir Date 2009-09-22 Time 17:31 Sent To  
Notes
2009-09-22 17:56:31NEW SHEETS: M1.0, M2.0 MINOR DUCT AND EQUIPMENT
 LOCATION CHANGES, NEW DIFFUSERS ON EXISTING DUCTS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-02-22 Cont ID  
Sent By rregueir Date 2009-02-22 Time 13:47 Rev Time 0.00
Received By rregueir Date 2009-02-22 Time 13:46 Sent To  
Notes
2009-02-22 13:47:34ACCORDING TO PLANS, ALL HVAC AND KITCHEN EXHAUST
 EQUIPMENT IS EXISTING TO REMAIN.

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-09-24 Cont ID  
Sent By kstevens Date 2009-09-24 Time 08:01 Rev Time 0.00
Received By kstevens Date 2009-09-23 Time 17:54 Sent To  
Notes
2009-09-24 08:01:52REVISIONS OK -- SHTS P-1, P-2, P-3, P-4 & P-5 ALL NEW
 SHEETS.

Review Stop P PLUMBING
Rev No 3 Status N Date 2009-06-10 Cont ID  
Sent By kstevens Date 2009-06-10 Time 13:52 Rev Time 0.00
Received By kstevens Date 2009-06-10 Time 13:52 Sent To  
Notes
2009-06-10 13:53:36PER PLANS ALL DRAINAGE PIPING AND WATER SUPPLY PIPING
 IN PLACE. NEW FIXTURES BEING ADDED OR RELOCATED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-05-06 Cont ID  
Sent By kstevens Date 2009-05-06 Time 12:54 Rev Time 0.00
Received By kstevens Date 2009-05-06 Time 12:54 Sent To  
Notes
2009-05-06 13:00:37DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. SHT RE-1 ITEM 33 GLASS WASHER INDICATES 140 DEGREE
 HOT WATER BUT SHOWS NO WATER CONNECTION. PLEASE
 CLARIFY. SECTIONS 106.1.2 & 601.1.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED ON SHT RE-1
 TABLE.
  
 5. OK
  
 6. PLEASE CONTACT THE UTILITY DEPT, INDUSTRIAL
 PRETREATMENT, ENVIRONMENTAL COMPLIANCE FOR THE REQUIRED
 GREASE INTERCEPTOR. PLEASE CONTACT HOLLY MCGRATH,
 LABORATORY SUPERVISOR TO DETERMINE THE SIZING OF THE
 INTERCEPTOR AND TO DETERMINE THE PROPER OPERATION OF
 THE EXISTING GREASE INTERCEPTOR(S). ARTICLE III,
 SECTION 90-124(7).
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 7. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION FOR REVIEW:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE, NOTED, COMMENT NOT ADDRESSED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
 ****RESPONSE NOTED, INFORMATION REQUIRED ON PLANS.
  
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE BTU LOAD FOR THE RANGE,
 (120,000) DOES NOT REFLECT THE BTU LOAD ON SHT RE-2 GAS
 APPLIANCE TABLE, (180,000). PLEASE CORRELATE.
  
 H. N/A
  
 I. N/A
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, TO BE SHOWN ON RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-03-03 Cont ID  
Sent By kstevens Date 2009-03-03 Time 11:49 Rev Time 0.00
Received By kstevens Date 2009-03-03 Time 11:49 Sent To  
Notes
2009-03-03 12:17:21DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. ALL SHEETS SHALL CONTAIN THE CITY PLACE MANAGEMENT
 STAMP AS REVIEWED AND SHALL BE INITIALED BY THE
 REVIEWER. THIS IS A CITY PLACE REQUIREMENT.
  
 2. ALL ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENTS SHALL BE INDICATED IN THE
 TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(6) & FS
 481.2055.
  
 3. SHT T1.1 APPLICABLE CODES SHALL INCLUDE THE 2007
 REVISIONS. SECTION 106.1.1.
  
 4. SHT RE-1 ITEM 33 GLASS WASHER INDICATES 140 DEGREE
 HOT WATER BUT SHOWS NO WATER CONNECTION. PLEASE
 CLARIFY. SECTIONS 106.1.2 & 601.1.
  
 5. PLEASE SUBMIT PLUMBING PLANS FOR THE NEW WORK
 INDICATED ON SHT RE-1 ITEMS 24, 25, 27 & 29. SUBMIT A
 WATER RISER DIAGRAM SHOWING ALL PIPE SIZES, VALVES &
 POINT OF CONNECTION TO THE EXISTING WATER SUPPLY
 MAIN(S). SECTIONS 106.3.5.1.3 & 601.1.
  
 6. PLEASE CONTACT THE UTILITY DEPT, INDUSTRIAL
 PRETREATMENT, ENVIRONMENTAL COMPLIANCE FOR THE REQUIRED
 GREASE INTERCEPTOR. PLEASE CONTACT HOLLY MCGRATH,
 LABORATORY SUPERVISOR TO DETERMINE THE SIZING OF THE
 INTERCEPTOR AND TO DETERMINE THE PROPER OPERATION OF
 THE EXISTING GREASE INTERCEPTOR(S). ARTICLE III,
 SECTION 90-124(7).
  
 7. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION FOR REVIEW:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2009-09-22 Cont ID  
Sent By eschneid Date 2009-09-22 Time 15:10 Rev Time 0.75
Received By eschneid Date 2009-09-22 Time 15:10 Sent To  
Notes
2009-09-22 15:51:25PASSED
  
 SIGNS AND AWNINGS REQUIRE SEPARATE PERMITS.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-05-01 Cont ID  
Sent By eschneid Date 2009-05-01 Time 16:55 Rev Time 0.25
Received By eschneid Date 2009-05-01 Time 16:55 Sent To  
Notes
2009-05-01 16:55:57PASSED
  
 SIGNS AND AWNINGS REQUIRE A SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-09 Cont ID  
Sent By eschneid Date 2009-02-09 Time 13:36 Rev Time 0.50
Received By eschneid Date 2009-02-09 Time 13:36 Sent To  
Notes
2009-02-09 13:37:44FAILED
  
 1) CITYPLACE STAMP IS REQUIRED ON ALL PLANS.
  
 2) PLANS OK FOR ZONING ONCE STAMP PROVIDED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.