| Plan Review Stops For Permit 09010434 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2009-12-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-12-15 |
Time |
20:21 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2009-12-15 |
Time |
20:21 |
Sent To |
|
|
| Notes |
| 2009-12-15 20:22:05 | LS1.1 REVISION# 9 12-09-09 | | | A1.0 REVISION# 9 12-09-09 | | | A1.1 REVISION# 9 12-09-09 | | | A2.0 REVISION# 9 12-09-09 | | | A2.1 REVISION# 9 12-09-09 | | | A2.2 REVISION# 9 12-09-09 | | | A4.1 REVISION# 9 12-09-09 | | | A4.2 REVISION# 9 12-09-09 | | | A7.1 REVISION# 9 12-09-09 | | | A8.1 REVISION# 9 12-09-09 | | | A9.1 REVISION# 9 12-09-09 | | | A10.1 REVISION# 9 12-09-09 | | | A11.2 REVISION# 9 12-09-09 | | | A11.3 REVISION# 9 12-09-09 | | | A11.4 REVISION# 9 12-09-09 | | | 12.1 REVISION# 9 12-09-09 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2009-11-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-11-30 |
Time |
14:39 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2009-11-30 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2009-11-30 14:42:55 | REVISION# 09110506 | | | | | | A2.0 REV# 4 9-11-09 | | | A2.2 REV# 4 9-11-09 | | | A8.1 REV# 4 9-11-09 | | | A9.1 REV# 4 9-11-09 | | | RE-5 REV# 5 9-08-09 | | | RE-6 REV#5 9-08-09 | | | RE-7 REV# 5 9-08-09 | | | RE-8 REV# 5 9-08-09 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2009-10-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-10-29 |
Time |
09:30 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2009-10-29 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2009-10-29 09:31:39 | 1 PAGE MISSING FORM ONE SET LAST REVISION # 7 10-27-09 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2009-10-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-10-26 |
Time |
17:58 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2009-10-26 |
Time |
17:03 |
Sent To |
|
|
| Notes |
| 2009-10-26 17:42:46 | | | | 3 SETS OF PLANS/ 2 SETS OF PRODUCT APPROVALS | | | REVISIONS: | | | T1.1 REV# 7 10-21-09 | | | LS1 REV# 7 10-21-09 | | | A1.1 REV# 7 10-21-09 | | | A12.1 REV# 5 10-05-09 | | | | | | NOTE 3RD SET OF PLANS IS MISSING A12.1 REV# 5 10-05-09 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2009-10-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-10-08 |
Time |
18:30 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2009-10-08 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2009-10-08 18:30:08 | BUILDING PLAN REVIEW | | | PERMIT: 09010434 | | | ADD: 651 OKKECHOBEE BLVD SUITE 150 | | | CONT: SHAWMUT DESIGN & CONSTRUCTION | | | TEL: (561)856-6655 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | OCT. 8/2009 | | | REVISION# 4 REVIEW | | | ACTION: DENIED | | | | | | 1) PLEASE PROVIDE A NEW UPDATED LIFE SAFETY PLAN PER | | | 106.3.5.1.1(7). | | | 1A)COMPLIED. | | | | | | 1B) COMPLIED. | | | | | | 1C) SECOND REQUEST, THE MAIN ENTRY DOOR ON TTHE | | | ORIGINAL PLANS WAS A PAIR OF DOORS. THE CURRENT | | | REVISION HAS MOVED THE MAIN ENTRY DOOR AND DOWN SIZED | | | IT TO A SINGLE 3'-4" DOOR.THE ALLOWABLE OCCUPANT LOAD | | | THROUGH THE 38" 9CLEAR OPENING) DIVIDE BY .2= 190 | | | OCCUPANTS. THE UPDATED OCCUPANCY COUNT IS 409. THE DOOR | | | WIDTH IS SHORT OF THE REQUIRED WIDTHFOR 205 OR 41 | | | INCHES CLEAR OPENINGA MINIMUM OF 43" DOOR. PLEASE | | | REVIEW SECTION 1025.2 ASSEMBLY MAIN EXIT. | | | | | | 1D) SEECOND REQUEST, A1.1 OPEN AIR DINING PLEASE | | | INDICATE OPENING# 108E TO BE A REQUIRED 90 MINUTE | | | OPENING PROTECTIVE AS PER SHEET A4.2 AND TABLE 704.8 | | | PRODUCT APPROVALS SUBMITTED ARE FOR A 16'-0" ROLLING | | | STEEL DOOR NOA 08-0805.15. | | | | | | 1E)COMPLIED. | | | | | | 2) COMPLIED. | | | | | | 3) SEMI-COMPLIED. MISSING ROLL DOWN FIRE SHUTTER WITH | | | LARGE MISILLEIMPACT TESTING. SHEET A1.1 INDICATES NEW | | | EXTERIOR OPENINGS PLEASE INDICATE COMPLIANCE WITH | | | 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS | | | REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE | | | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS | | | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF | | | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE | | | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES | | | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH | | | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS | | | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE | | | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. | | | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE | | | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. | | | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) | | | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL | | | MISSILE TEST. | | | | | | FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2 | | | COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE | | | AS FOLLOWS: | | | 3A) EXTERIOR FOLDING DOOR SYSTEMS- NO APPROVAL WAS | | | SUBMITTED | | | 3B) EXTERIOR GLAZED DOORS W/ SIDE LITES & TRANSOM | | | (100A)- NO APPROVAL WAS SUBMITTED | | | 3C)HORIZONTAL MULLIONS- NO APPROVAL WAS SUBMITTED | | | 3D) ROLL DOWN SHUTTERS SUBMITTAL REVIEWED | | | 3E) ROLL DOWN FIRE SHUTTER W/ LARGE MISSILE IMPACT | | | TESTING | | | 3F) CURTAIN WALL- SUBMITTED -NOT REQUIRED? | | | | | | 4) SEECOND REQUEST, 106.3.3 PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72 | | | SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | 5)SEECOND REQUEST 50% OF THE OCCUPANT LOAD NEEDS TO BE | | | ABLE TO COME BACK THROUGH THE MAIN ENTRY PLEASE SEE | | | COMMENT 1C/ SECTION 1025.2. . DISCREPANCY IN PLANS | | | PLEASE REVIEW A1.1(FLOOR PLAN), A10.1 DETAIL 2( FRONT | | | ENTRY INTERIOR ELEVATION) AND A4.1(ELEVATIONS) ON THE | | | FRONT ELEVATIONS MAIN ENTRY MISSING THE DOUBLE DOORS | | | PLEASE CORRECT THE DISCREPANCY. WITH THE ELIMINATION OF | | | THE DOUBLE FRONT ENTRY DOOR PLEASE PROVIDE COMPLIANCE | | | WITH1024.2. | | | | | | 6) COMPLIED. | | | | | | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES | | | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER | | | NOTICE. | | | | | | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM | | | - 5:00 PM. | | | | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2009-09-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-09-28 |
Time |
18:30 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2009-09-28 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2009-09-28 18:31:45 | BUILDING PLAN REVIEW | | | PERMIT: 09010434 | | | ADD: 651 OKKECHOBEE BLVD SUITE 150 | | | CONT: SHAWMUT DESIGN & CONSTRUCTION | | | TEL: (561)856-6655 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION# 4 REVIEW | | | ACTION: DENIED | | | | | | 1) PLEASE PROVIDE A NEW UPDATED LIFE SAFETY PLAN PER | | | 106.3.5.1.1(7). | | | 1A) SHEET A1.0 INDICATES A PRIVATE DINING ROOM# 3 BUT | | | THE OCCUPANT LOAD IS NOT FIGURED IN ON THE OCCUPANCY | | | LOADS SHEET T1.1. | | | | | | 1B) SHEET A1.0 & A1.1 BOTH INDICATE A SLIDING DOOR | | | LEAVING ONLY ONE EGRESS DOOR INTO AND EXITING THE | | | PRIVATE DINING ROOM# 3 PLEASE REVIEW SECTION TABLE | | | 1014.1 SPACES WITH ONE MEANS OF EGRESS, IF 50 OR MORE | | | OCUPANTS TWO EGRESS DOORS WILL BE REQUIRED . | | | | | | 1C) SHEET A1.1 MAIN ENTRY HAS BEEN SHIFTED TO WHERE AN | | | EXISTING COLUMN IS WITHIN 2'-0" OF THE DOUBLE DOORS | | | BLOCKING EGRESS FROM ONE OF THE DOORS, PLEASE REVISE | | | THE MINIMUM CLEAR WIDTH OF EXIT DOORS FOUND ON THE T1.1 | | | SHEET TO REFLECT THE ONE DOOR NOT BEING ACTIVE. | | | | | | 1D) A1.1 OPEN AIR DINING PLEASE INDICATE OPENING# 108E | | | TO BE A REQUIRED 90 MINUTE OPENING PROTECTIVE AS PER | | | SHEET A4.2 AND TABLE 704.8 | | | | | | 1E) PLEASE ALSO INDICATE THE LOCATION OF PORTABLE FIRE | | | EXTINGUISHERS AS PER SECTION 906.1. | | | | | | 2) PLANS INDICATE NEW WINDOWS AND DOORS WITHIN THE | | | EXTERIOR ENVELOPE OF THE BUILDING. PLEASE PROVIDE THE | | | POSSITIVE AND NEGATIVE PRESSURES FOR THE HIGHRISE AS | | | PER ASCE 7-05, NEGATIVE PRESSURES ARE TAKEN FROM ROOF | | | LEVEL, POSITIVE FROM GROUND LEVEL. | | | | | | 3) SHEET A1.1 INDICATES NEW EXTERIOR OPENINGS PLEASE | | | INDICATE COMPLIANCE WITH 1609.1.4 PROTECTION OF | | | OPENINGS IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING | | | THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET | | | (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS | | | AND THE BALANCE OF GLAZED OPENINGS IN THE REST OF THE | | | BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS SUCH | | | GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT | | | RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT | | | COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E | | | 1886 AND ASTM E 1996, OR MIAMI-DADE TAS 201, 202 AND | | | 203 REFERENCED THEREIN AS FOLLOWS: 1. GLAZED OPENINGS | | | LOCATED WITHIN 30 FEET (9.1 M) OF GRADE SHALL MEET THE | | | REQUIREMENTS OF THE LARGE MISSILE TEST. 2. GLAZED | | | OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) ABOVE GRADE | | | SHALL MEET THE PROVISIONS OF THE SMALL MISSILE TEST. | | | | | | FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2 | | | COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE | | | AS FOLLOWS: | | | 3A) EXTERIOR FOLDING DOOR SYSTEMS | | | 3B) EXTERIOR GLAZED DOORS W/ SIDE LITES & TRANSOM | | | (100A) | | | 3C)HORIZONTAL MULLIONS | | | 3D) ROLL DOWN SHUTTERS | | | 3E) ROLL DOWN FIRE SHUTTER W/ LARGE MISSILE IMPACT | | | TESTING | | | | | | 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE | | | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 5) DISCREPANCY IN PLANS PLEASE REVIEW A1.1(FLOOR PLAN), | | | A10.1 DETAIL 2( FRONT ENTRY INTERIOR ELEVATION) AND | | | A4.1(ELEVATIONS) ON THE FRONT ELEVATIONS MAIN ENTRY | | | MISSING THE DOUBLE DOORS PLEASE CORRECT THE | | | DISCREPANCY. WITH THE ELIMINATION OF THE DOUBLE FRONT | | | ENTRY DOORPLEASE PROVIDE COMPLIANCE WITH1024.2. | | | | | | 6) SHEET A12.1 INDICATES IN THE MAIN DINING ROOM# 1 | | | (106) AN ACCESSIBLE LOCATION AT A TABLE JUST TO THE | | | RIGHT OF THE MAIN ENTRY PLEASE REVIEW SECTION | | | 1024.9.1.1 REQUIRING A CLEARR 44" MEANS OF EGRESS WHEN | | | SERVING AN OCCUPANT LOAD OF 50 OR MORE. | | | | | | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES | | | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER | | | NOTICE. | | | | | | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM | | | - 5:00 PM. | | | | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-07-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-07-06 |
Time |
14:18 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2009-07-06 |
Time |
13:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-05-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-05-19 |
Time |
14:53 |
Rev Time |
0.88 |
| Received By |
jwitmer |
Date |
2009-05-19 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-02-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-02-11 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-02-11 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2009-02-11 16:55:38 | BUILDING PLAN REVIEW | | | PERMIT: 09010434 | | | ADD: 651 OKEECHOBEE BLVD SUITE 150 | | | CONT: SHAWMUT WOODWORKING AND SUPPLY INC. | | | TEL: (617)622-7000 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW1 | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 3) 61G1-16.004 THE TITLE BLOCK SHALL MEET THE | | | REQUIREMENTS BELOW. | | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT. | | | | | | 4) FBC 11-5. THE PLANS NEED TO INDICATE THE ACCESSIBLE | | | DINING AT THE BAR, LOUNGE AND THE THREE PRIVATE DINNING | | | AREAS. ACCESSIBLE FIXED TABLES SHALL BE DISTRIBUTED | | | THROUGHOUT THE SPACE OR FACILITY. NO ACCESSIBLE SPACES | | | ARE SHOWN IN THE AREAS MENTION ABOVE. SHOW COMPLIANCE. | | | | | | 5) THE DRAWING SHALL BE APPROVED BY THE CITY PLACE | | | OFFICE AND CONTAIN THE STAMP OF APPROVAL FROM THAT | | | OFFICE WITH THE INITIAL OF THE PERSON STAMPING THE | | | PLANS. NOTE: EACH SHEET REQUIRES THE CITY PLACE OFFICE | | | STAMP. | | | | | | 6) NOTE: FBC 11-4.32.2 SEATING. IF SEATING SPACES FOR | | | PEOPLE IN WHEELCHAIRS ARE PROVIDED AT FIXED TABLES OR | | | COUNTERS, CLEAR FLOOR SPACE COMPLYING WITH SECTION | | | 11-4.2.4 SHALL BE PROVIDED. SUCH CLEAR FLOOR SPACE | | | SHALL NOT OVERLAP KNEE SPACE BY MORE THAN 19 INCHES | | | (SEE FIGURE 45). ALL FIXED SEATING IN PUBLIC FOOD | | | SERVICE ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED | | | UNDER THE BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, | | | AND IN ALL OTHER FACILITIES GOVERNED BY REFERENCE | | | SECTION 11-4.1 SHALL BE DESIGNED AND CONSTRUCTED IN | | | ACCORDANCE WITH THE FOLLOWING REQUIREMENTS: | | | (1) ALL AISLES ADJACENT TO FIXED SEATING SHALL PROVIDE | | | CLEAR FLOOR SPACE FOR WHEELCHAIRS. | | | (2) WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES OF | | | SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52 | | | INCHES (1321 MM) WIDE. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | PHONE (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2009-10-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-10-16 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-10-16 |
Time |
10:02 |
Sent To |
PC |
|
| Notes |
| 2009-10-16 10:03:42 | SEPARATE PERMITS STILL REQUIRED FOR LOW VOLTAGE, FIRE | | | ALARM AND FIRE SPRINKLER. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2009-10-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-10-09 |
Time |
17:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-10-09 |
Time |
17:37 |
Sent To |
|
|
| Notes |
| 2009-10-09 17:37:22 | | | | | | | ** DENIED ** | | | | | | | | | 1) NOTE: PLEASE SEE NOTES FORM PREVIOUS REVIEW. PLANS | | | STILL INDICATE STANDARD LIGHTING CONTROL DEVICES SUCH | | | AS SP DIMMERS. PLAN CONTAINS | | | A NOTE WHICH MENTION TO SEE DETAILS ON SHEET E2.1. | | | HOWEVER THE DETAIL AND TYPES OF DEVICES DO NOT COMPLY | | | WITH SECTIONS FOR PRESCRIPTIVE REQUIREMENTS FOR NEW | | | BEING INSTALLED. | | | THE NEW TYPES OF SWITCHES ARE DEVICES WHICH GO UP TO | | | 8HRS. THE CODE DOES NOT ALLOW MORE THAN FOUR. THE CODE | | | REQUIRES THE OCCUPANT TO SEE ALL LIGHTING WHICH IS | | | BEING OVER RIDDEN OR MEET EXCEPTIONS. THE DEVICE IS NOT | | | LOCATED SO THE OCCUPANT CAN SEE LIGHTING BEING | | | CONTROLLED AND THE OVER RIDE DEVICE SPECIFIED ON PLANS | | | ( SSA-200) DOES NOT MEET EXCEPTION FOR PILOT/INDICATOR | | | LIGHTS. | | | THE DIAGRAM ALSO INDICATES A SQUARE D PRODUCT | | | #8501C015V20 WHICH DOES NOT COME UP ON THEIR WEBSITE | | | BUT IS ACTUALLY NOTED AS A MANUAL OVER RIDE OF TIMED | | | SYSTEM WHICH CAN LEAVE ON DEVICES PERMANENTLY WITHOUT | | | AUTOMATED CONTROL. AS SHOWN ON DETAIL THE SPDT SWITCH | | | WILL BYPASS TIMED OVER RIDE ENERGIZING THE COIL ON LCP | | | AND LEAVE LIGHTS ON INDEFINITELY. THIS DOES NOT MEET | | | THE INTENT OF ENERGY CODE WHICH WILL TURN OFF LIGHTING | | | WHEN A BUILDING IS NO OCCUPIED. | | | | | | THE LIGHTING CONTROLS FOR EXTERIOR LIGHTS CAN NOT BE | | | CONFIRMED MEETING 13-415.1.ABC.1.4. THIS SECTION OF THE | | | CODE REQUIRES ONE OF THE TWO METHODS OR BOTH. NOTE ON | | | PLANS MENTIONS TO EXISTING CONTROL HOWEVER NO | | | INFORMATION COULD BE LOCATED. PLEASE VERIFY WHAT IS | | | EXISTING IF NEW CONTROL IS NOT INSTALLED. | | | THE CODE REQUIRES THIS TO BE AN ASTRONOMICAL TIME CLOCK | | | WITH A MINIMUM BACK UP FOR PROGRAMMING. CURRENT CODE | | | REQUIRES 10HRS BACK UP. WHEN LOCATION WAS ORIGINALLY | | | BUILT IT WOULD BE UNDER MINIMUM OF THE 2001 FBC IF NOT | | | INSTALLING NEW CONTROLS. | | | SEE NEW AREAS OUTSIDE. | | | PRESCRIPTIVE C NOW SUBMITTED FOR FOR TOTAL AREAS ( NEW | | | ONLY). CALL AS THIS CAN BE GONE OVER. PREVIOUS METHOD | | | SUBMITTED WAS B, NOW METHOD IS C. | | | | | | 2) NOTE: AS NOTED ON THE PREVIOUS REVIEW. REVIEW FOR | | | MINIMUM CODE COMPLIANCE FOR LIGHTING PERFORMANCE | | | CALCULATIONS CAN NOT BE DONE WITHOUT A COMPLETE FIXTURE | | | LEGEND/SCHEDULE. THE A SHEETS ARE NOT SUBMITTED WIHT | | | THE ELECTRICAL. THANK YOU FOR THE COPY ON THE BACK OF | | | THE CALCULATIONS, HOWEVER BASED ON THE FIXTURES LISTED, | | | NOT ALL FIXTURES WHICH ARE ON PLANS ARE SHOWN/NOTED. | | | IS THERE ANY INFORMATION ON EIXSTING FIXTURES? | | | PLEASE SUBMIT A FIXTURE LEGEND/SCHEDULE ON ELECTRICAL | | | PLANS FOR REVIEW. | | | 13-415.2.ABC.1.1,.1.2, 13-415.2.ABC.1, 13-415.2.C | | | | | | 3) NOTE: TO DATE NO SUB-PERMITS HAVE BEEN APPLIED FOR | | | ELECTRICAL, PLUMBING, MECHANICAL, FIRE ALARM, OR LOW | | | VOLTAGE SYSTEMS. | | | FBC 105.1 | | | | | | 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY | | | NOTICE GIVEN AT THIS TIME DUE TO REPEAT COMMENTS FOR | | | CODE COMPLIANCE. | | | | | | 5) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO THE | | | VALUATION OF THE PROJECT. NO ADJUSTMENT FOR APPLIED | | | SCOPE OF WORK HAS BEEN SUBMITTED FOR VERIFICATION. | | | ALL LABOUR, MATERIALS, EQUIPMENT, DESIGN COSTS ETC ARE | | | REQUIRED TO BE FIGURED EVEN IF OWNER SUPPLIED. FBC | | | 108.3 | | | THE ORIGINAL SCOPE OF WORK AND APPLIED VALUE IS | | | SUBSTANTIALLY LESS THAN THE WORK AT THIS TIME. | | | | | | | | | | | | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2009-09-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-09-25 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-09-25 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2009-09-25 16:49:36 | | | | | | | | | | ** DENIED PLANS ** | | | | | | ** PERMIT WAS APPLIED FOR UNDER THE 2004 FBC W/ 2007 | | | REVISIONS. | | | | | | | | | | | | 1) NOTE: THE SUBMITTED LIGHTING CALCULATIONS ARE FROM | | | FLA COM METHOD B UNDER THE NEW CODE. | | | PLEASE KNOW THAT CALCULATIONS SHOULD BE UNDER THE CODE | | | IN WHICH THE APPLICATION IS UNDER. IF USING THE NEW | | | MORE RESTRICTIVE CODE AS SUBMITTED THE DESIGN WATTAGE | | | IS HIGHER THAN THE ALLOWANCE. THE EFFECTIVE IS SHOWN | | | LOWER THAN ALLOWANCE HOWEVER PER 13-415.AB.5, DISPLAY, | | | DECRETIVE LIGHTING IS NO LONGER EXEMPT, OR ALLOWS ANY | | | ADDITIONAL ALLOWANCES. | | | | | | ** PLEASE SUBMIT COMPLIANCE UNDER THE CODE IN WHICH | | | PERMIT WAS MADE. | | | ** PLEASE CALL TO GO OVER AS THIS IS A TOPIC WHICH HAS | | | BEEN TAKEN UP WITH THE STATE ON THE CODE CHANGES AND | | | THE ITEMS NOT BEING CHANGED OR REVISED IN THE FLA COM | | | PROGRAM. | | | | | | ** AS THERE IS NO FIXTURE LEGEND/INFORMATION SUBMITTED | | | REVIEW FOR CODE COMPLIANCE CAN NOT FULLY BE DONE. | | | | | | ** METHOD OF CONTROL ON THE IDR IS NOT ALL GOING TO BE | | | *MANUAL ON/ OFF* | | | | | | 2) NOTE: PLEASE SEE 13-415.A.ABC.1.1,.1.2, .1.3 AND | | | .1.4. | | | PREVIOUS PLANS INDICATED THAT ALL EXISTING LIGHTING | | | CONTROLS WERE TO REMAIN. HOWEVER NEW PLANS SHOW | | | SUBSTANTIAL AMOUNT OF NEW LIGHTING AND WIRING. | | | MUST MEET PRESCRIPTIVE FOR NEW CONTROLS BEING | | | INSTALLED. | | | | | | 3) NOTE: NEW EXTERIOR LIGHTING SHALL MEET | | | 13-415.1.ABC.1.4 FOR CONTROLS. NO INFORMATION ON PLANS. | | | | | | 4) NOTE: PLEASE SEE 13-415.2.ABC.1.1, .1.2 FOR EXTERIOR | | | LIGHTING ALLOWANCES. | | | | | | 5) NOTE: PLEASE SEE NOTES FROM PREVIOUS PROVISO FOR | | | REQUIRED UPDATING OF LOAD CALCULATIONS. THE PLANS DO | | | HAVE REVISIONS HOWEVER PLANS ALSO INDICATE CALCULATIONS | | | AND CODE SECTIONS WHICH ARE NO LONGER APPLICABLE. SE3E | | | E2.1 WHICH SHOWS NEC 220.35. THIS SECTION WAS FROM THE | | | 2002 NEC. | | | PLEASE UPDATE AND REVISE. | | | | | | 6) NOTE: PLANS CONTAIN SEVERAL NEW FIRE ALARM DEVICES | | | HOWEVER PER THE SYMBOL LEGEND NO INFORMATION IS | | | PROVIDED FOR DEVICES MEETING FBC 11-4.28.1, .2 AND .3. | | | ** PLEASE KNOW THAT EVEN AS SEPARATE FIRE ALARM PERMIT | | | WILL BE REQUIRED, THE BASE PLANS SHALL SHOW BASE DESIGN | | | REQUIRED FOR FIRE, LIFE SAFETY AND ADA COMPLIANCE. | | | | | | 7) NOTE: THE SCOPE OF WORK HAS SUBSTANTIALLY INCREASED. | | | THE APPLIED VALUE NEEDS TO BE ADJUSTED PER FBC 108.3 | | | THE SCOPE SHALL INCLUDE ALL LABOR, MATERIALS, FIXTURES, | | | EQUIPMENT, DESIGN COST ETC EVEN IF ANY OF THESE ITEMS | | | ARE OWNER SUPPLIED AND NOT PART EQUIPMENT AND OTHER | | | ITEMS SUPPLIED BY THE CONTRACTOR. | | | | | | ** AS STATED ABOVE THERE IS INFORMATION NOT YET | | | SUBMITTED FOR REVIEW FOR CODE COMPLIANCE REVIEW? THERE | | | MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN | | | NOT BE MADE AT THIS TIME. | | | | | | | | | | | | | | | ** IMPORTANT** | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-07-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-03 |
Time |
17:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-03 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2009-07-03 17:22:12 | | | | | | | ** PROVISO ** | | | | | | 1) NOTE: AS NOTED ON PREVIOUS REVIEW THERE IS AN | | | INCREASE ON LOAD ON MORE THAN ONE CIRCUIT. IT IS | | | UNDERSTOOD THAT THE OVER ALL LOAD MAY NOT BE AFFECT | | | HOWEVER THE SPECIFIC CIRCUIT LOAD FOR #29 AND #30 HAS | | | INCREASED. THERE IS NO INDICATION ON THE ACTUAL BRANCH | | | CIRCUIT PROVIDED AS EXISTING. | | | REVISED CIRCUITING ON PLANS COORDINATING WITH REVISED | | | PANEL SCHEDULE(S) WILL BE REQUIRED. | | | 408.4,220,310.16 ETC | | | FBC 106.1.1,106.1.2, 106.5 AS RECORD PLANS SHALL | | | INCLUDE AN ACCURATE DEPICTION OF WHAT IS LOCATED | | | ON-SITE. | | | | | | ** THESE NEED TO BE SUBMITTED BEFORE INSPECTIONS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2009-07-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-03 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-03 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2009-07-03 14:05:46 | | | | ** TEMP/DENIED | | | | | | | | | 1) NOTE: CALLED ENGINEER, CONTRACTOR AND PERMIT | | | EXPEDITOR. | | | THE SELECTIVE COORDINATION STUDY HAS SOME CONFLICTS | | | WITH A PORTION DATED APRIL OF 2009 WITH COVER SHEET | | | COMPARED TO THE REPORT OF JUNE 2009. A CALLED WAS | | | PLACED TO ENGINEER HOWEVER OFFICE WAS CLOSED. NEED TO | | | GO OVER AS TITLE DOES LIST SECTION TWO AS NORMAL AND | | | SECTION THREE AS EMERGENCY WHEN IN FACT IT APPEARS EACH | | | SECTION CONTAINS NORMAL AND EMERGENCY. ONE DATED IN | | | 04/09 AND THE OTHER 06/09. IT APPEARS THE 04/09 SHOUDL | | | NTO BE IN THE SUBMITTED DOCUMENTS AS THE TIME CURVES | | | AND OTHER SUPPORTING INFORMATION WAS ALL RUN IN 06/09. | | | | | | 2) NOTE: NEED SECOND SET OF SIGNED, DATED AND SEALED | | | FLA-COM LIGHTING PERFORMANCE CALCULATIONS. FBC 13-103, | | | FS 471.025. SPOKE TO NAT HEALY AS NEW CALCULATIONS WILL | | | BE SENT FED-EX. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2009-05-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-05-14 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-05-14 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2009-05-14 08:17:39 | **DENIED REVIEW ** | | | | | | | | | | | | 1) NOTE: PREVIOUS REVIEW NOTE: PLEASE SEE FBC | | | 13-415.2,13-415.2.ABC.1.1, .1.2. THE NEW SUBMITTED | | | ENERGY CALCULATIONS CAN NOT BE VERIFIED AS THE PLANS DO | | | NOT LIST THE FIXTURE, FIXTURE TYPES, FIXTURES WATTAGES | | | ETC. | | | NO COMPLIANCE CAN BE KNOWN BASED ON INFORMATION NOT YET | | | RECEIVED. IT IS NOT POSSIBLE TO REVIEW THE INPUT DATA | | | REPORT AND COMPARE TO PLANS FOR FIXTURE COUNTS AND TYPE | | | FOR COMPLIANCE. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE | | | FIXTURES BEING ADDED WHICH MUST BE LISTED WITH A | | | NATIONALLY RECOGNIZED TESTING LABORATORY. ( NRTL). | | | EXAMPLES OF SOME HOWEVER NOT ALL WOULD BE. CSA, MET, | | | ETL, TUV, TUV AMERICA, UL, ETC. PLEASE SEE THE ADOPTED | | | LIST PER OSHA. | | | BASED ON THE PRODUCT DATA SUBMITTED THERE WAS NO | | | LISTING FROM A NRTL READILY SEEN? | | | NEC 110.3 | | | | | | 3) NOTE: SEVERAL NOTES ON THE PLANS STATE ALL LOCATIONS | | | NOTED HAVE EQUAL OR LESSER POWER REQUIREMENT THAN | | | PREVIOUS CONNECTED LOADS. HOWEVER BASED ON THE | | | EQUIPMENT PLANS SUBMITTED THERE IS NEW EQUIPMENT WHICH | | | DOES INCREASE LOADS. AN EXAMPLE OF THIS IS THE NEW | | | ELECTRIC OVEN, TILTING SKILLET ETC. | | | NEED TO SUBMIT THE EXISTING LOADS WITH THE INCREASED | | | LOADS AND PANEL SCHEDULE SPECIFIC TO THE NEW EQUIPMENT. | | | BASED ON THE PLANS IT CAN NOT BE DETERMINED IF THE | | | EXISTING PANELS AND LOADS ON THE SERVICE EQUIPMENT IS | | | ADEQUATE. | | | PLEASE COMPLETE AND SUBMIT. | | | 240.4,310.16,408.4, 220. | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-02-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-12 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-12 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2009-02-12 13:29:34 | ** DENIED REVIEW ** | | | | | | 1) NOTE: ALL PLANS SHALL CONTAIN CITY PLACE MANAGEMENT | | | STAMP AS REVIEWED. THIS IS A CITY PLACE REQUIREMENT NOT | | | A LOCAL CODE, ORDINANCE OR LOCAL ADMINISTRATIVE CODE | | | REQUIREMENT. | | | | | | 2) NOTE: ALL TITLE BLOCKS FOR ALL DESIGN TEAMS ARE | | | REQUIRED TO MEET FLORIDA ADMINISTRATIVE CODE | | | 61G1-16.004 AND 61G15-23.002. | | | FLORIDA STATUTES 481.229 AND 471.023 ALSO APPLY FOR | | | CERTIFICATE OF AUTHORIZATION NUMBERS WHEN APPLICABLE. | | | PLEASE SEE THAT SOME INFORMATION IS CURRENTLY MISSING | | | FROM THE ARCHITECTURAL TITLE BLOCKS. | | | | | | 3) NOTE: PLEAS KNOW AS OF DECEMBER 31ST, 2008 THE NEW | | | ADOPTED FLORIDA FIRE PREVENTION CODE AND LIFE SAFETY | | | CODE CAN BE FOUND ON THE STATE FIRE MARSHAL WEB SITE. | | | PLEASE SEE COMMENTS FROM FIRE MARSHAL WITH RESPECT TO | | | THE CORRECT NFPA-1. THE ADOPTED NFPA-101 IS THE 2006 | | | EDITION. NOT THE 2003 AS STATED ON PLANS. | | | | | | 4) NOTE: PLEASE SUBMIT ELECTRICAL PLANS FOR REMODEL | | | SCOPE OF WORK INCLUDING ANY NEW LIGHT FIXTURE | | | LOCATIONS, REPLACEMENT, NEW ETC. | | | AS THERE ARE SEVERAL NEW ITEMS SHOWN FOR EQUIPMENT, | | | PLANS SHOWING ELECTRICAL CIRCUITING, RECEPTACLES ETC IS | | | NEEDED TO SHOW MINIMUM CODE COMPLIANCE. | | | PLEASE BE SURE TO SEE THE 2005 NEC FOR CIRCUITING, | | | SIZING, LOADS, LOAD CALCULATIONS, OVER CURRENT | | | PROTECTION ETC | | | 408.4,310.16,240.4,240,220 ETC | | | SPECIFIC SECTIONS OF CODES CAN NOT REALLY BE GIVEN | | | BASED ON THE FACT NO ELECTRICAL PLANS WERE SUBMITTED. | | | FBC 106.1.1,106.1.2,106.3.5.1.2,106.5 AS ADOPTED BY THE | | | CITY OF WEST PALM BEACH. PLANS REQUIRED FOR CLARITY, | | | ADDITIONAL INFORMATION, SCOPE AND RECORD SETS OF PLANS | | | FOR SCOPE. | | | | | | 5) NOTE: *** IMPORTANT. PLEASE SEE FBC | | | 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 WITH RESPECT TO | | | ANY *NEW* LIGHTING CONTROLS BEING INSTALLED. THIS IS | | | NOT FOR EXISTING TO REMAIN THIS IS FOR NEW ONLY. THE | | | PLANS STATE FOR EXAMPLE NEW TIME CLOCKS HOWEVER DO NOT | | | SHOW ANY OF THESE. ARE THEY FOR INSIDE OR OUTSIDE | | | LIGHTING? | | | PLEASE BE SURE TO SEE THESE SECTIONS AS NOTED AND CALL | | | TO GO OVER ANY COMMENTS OR CONCERNS. | | | | | | | | | 6) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1,.1.2 | | | FOR LIGHTING PERFORMANCE CALCULATIONS. | | | PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE | | | CALCULATIONS FOR ALL EXISTING PROPOSED NEW FIXTURES. | | | THE ADDITIONS OF NEW LIGHTING FIXTURES WITH WATTAGES | | | ARE NOT PERMITTED UNTIL VERIFICATION OF THE EXISTING | | | LEVELS CAN BE CONFIRMED. IF THE EXISTING DESIGN EXCEEDS | | | THE STATED MAXIMUM ALLOWANCES IN THE CURRENT CODE THEN | | | NEW FIXTURES MAY NOT BE ADDED. | | | ALL OF THESE NEED TO BE SPECIFIC TO THE NEW AND | | | EXISTING. | | | | | | 7) NOTE: PLEASE PROVIDE MANUFACTURES SPECS/CUT SHEETS | | | FOR NEW PROPOSED LIGHTING. ALL LIGHTING FIXTURES SHALL | | | BE LISTED AND BY A NRTL. (NATIONALLY RECOGNIZED TESTING | | | LABORATORY). | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2009-10-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-10-26 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-10-26 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2009-10-26 15:47:20 | *****REVISION #7, DATED 10/21/2009, APPROVED***** | | | | | | | | | REVISED PLAN SHEET LS1.1 AND A1.1 WERE STAMPED, | | | INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2009-10-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-10-26 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-10-26 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2009-10-26 15:32:53 | *****REVISION #5, DATED 10/05/2009, APPROVED***** | | | | | | | | | REVISED PLAN SHEET LS1.1, A1.1, AND A12.1 WERE STAMPED, | | | INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2009-09-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-09-28 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-09-28 |
Time |
10:41 |
Sent To |
B1 |
|
| Notes |
| 2009-09-28 11:07:41 | *****REVISION #4, DATED 9/11/09, APPROVED***** | | | | | | | | | REVISED SHEET A4.1 STAMPED, INITIALED, AND DATED; SHEET | | | E1.2 TO BE FIRE-STAMPED WHEN THE ELECTRICAL EXAMINER'S | | | COMMENT HAS BEEN SATISFIED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-07-06 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-07-06 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-07-06 |
Time |
13:38 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2009-05-15 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-05-15 |
Time |
22:08 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-05-15 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2009-05-18 11:43:16 | *****FIRE- STAMPING NEEDED***** | | | | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE REVIEW HAVE BEEN | | | ADDRESSED; HOWEVER THE APPROPIATE PLAN SHEETS TO BE | | | FIRE-STAMPED WHEN THE OTHER PLAN EXAMINERS' COMMENTS | | | HAVE BEEN SATISFIED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-02-24 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-02-24 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-02-24 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2009-02-24 15:13:10 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH THE FLORIDA FIRE | | | PREVENTION CODE 2007 WHICH INCLUDES NFPA 101, 2006 AND | | | NFPA 1, 2006 AS OF DECEMBER 31, 2008. FAC 69A-60.004 | | | AND FAC 69A-60.003. | | | | | | 2) ALL SHEETS ARE TO BE PROVIDED WITH THE STAMP BY CITY | | | PLACE MANAGEMENT OFFICE. | | | | | | 3) SEE OTHER REVIEW COMMENTS REGARDING FAC AND FS | | | REQUIREMENTS FOR TITLE BLOCKS. | | | | | | 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 5) IF NOT ALREADY PROVIDED, OCCUPANT LOAD SIGNS SHALL | | | BE POSTED. PLEASE CONTACT BUREAU OF FIRE PREVENTION AT | | | (561) 804-4724 FOR ASSISTANCE. | | | | | | 6) PLANS INDICATE SUITE #150. ALL APPLICABLE ADDRESS | | | NUMBERS ARE TO BE NEAR THE FRONT DOOR AND SHALL MEET | | | THE CITY OF WEST PALM BEACH SIZE REQUIREMENTS FOR | | | COMMERCIAL BUILDINGS. | | | | | | 7) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILINGS. | | | | | | 8) ALTHOUGH NOT IDENTIFIED AS EXITS, IT WOULD APPEAR | | | THAT A TABLE AND CHAIR ARRANGEMENT IS OBSTRUCTING EXIT | | | DOORS AT THE SOUTHEAST CORNER OF THE BUILDING. | | | | | | 9) WILL THIS WORK IMACT EXISTING FIRE SPRINKLER AND | | | FIRE ALARM SYSTEMS? | | | | | | | | | MIKE WENNERGREN, | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2009-06-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-06-12 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-06-12 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2009-06-12 15:21:14 | SEPARATE GAS PERMIT/PLANS REQUIRED. PLANS AND GAS | | | APPLICATION TO BE SUBMITTED PRIOR TO GAS WORK/APPLIANCE | | | INSTALLATION. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2009-05-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-06 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-05-06 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2009-05-06 13:02:36 | DENIED | | | REFERENCE: | | | FBC-2004 FUEL GAS | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE | | | FOLLOWING INFORMATION FOR REVIEW: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | ****RESPONSE, NOTED, COMMENT NOT ADDRESSED. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | ****RESPONSE NOTED, INFORMATION REQUIRED ON PLANS. | | | | | | D. OK | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. | | | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. | | | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT THE BTU LOAD FOR THE RANGE, | | | (120,000) DOES NOT REFLECT THE BTU LOAD ON SHT RE-2 GAS | | | APPLIANCE TABLE, (180,000). PLEASE CORRELATE. | | | | | | H. N/A | | | | | | I. N/A | | | | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****RESPONSE NOTED, TO BE SHOWN ON RISER DIAGRAM. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2009-03-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-03 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-03 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2009-03-03 12:20:07 | DENIED | | | REFERENCE: | | | FBC-2004 FUEL GAS | | | | | | 1. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE | | | FOLLOWING INFORMATION FOR REVIEW: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | H. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | I. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2009-12-14 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-12-14 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-12-14 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2009-12-14 16:55:53 | ******************EXPEDITED******************* | | | C--6 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2009-11-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-11-19 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-11-19 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2009-11-19 09:41:18 | SENT TO FIRE. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2009-10-26 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-10-22 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-10-22 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2009-10-26 09:42:53 | ROUTED ON 10/26/09 | | 2009-10-26 09:42:10 | *****************EXPEDITED*************** | | | GAVE TO JIM |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2009-10-07 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-10-07 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-10-07 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2009-10-07 17:01:11 | **********EXPEDITED************ | | | GAVE TO DEWEY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2009-10-07 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-10-07 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-10-07 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2009-10-07 16:43:30 | ***********EXPEDITED**************** | | | GAVE TO JIM |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-09-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-09-16 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-09-16 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2009-09-16 08:53:01 | SENT TO C-35. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-06-18 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-06-17 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-06-17 |
Time |
11:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-04-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-29 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-29 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2009-04-29 09:13:14 | TO C25 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-03-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-03 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-29 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2009-01-29 16:53:14 | TO "COMM" BD#34 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-09-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-09-22 |
Time |
17:55 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-09-22 |
Time |
17:31 |
Sent To |
|
|
| Notes |
| 2009-09-22 17:56:31 | NEW SHEETS: M1.0, M2.0 MINOR DUCT AND EQUIPMENT | | | LOCATION CHANGES, NEW DIFFUSERS ON EXISTING DUCTS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2009-02-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-02-22 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-02-22 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2009-02-22 13:47:34 | ACCORDING TO PLANS, ALL HVAC AND KITCHEN EXHAUST | | | EQUIPMENT IS EXISTING TO REMAIN. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2009-09-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-09-24 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-09-23 |
Time |
17:54 |
Sent To |
|
|
| Notes |
| 2009-09-24 08:01:52 | REVISIONS OK -- SHTS P-1, P-2, P-3, P-4 & P-5 ALL NEW | | | SHEETS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2009-06-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-06-10 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-06-10 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2009-06-10 13:53:36 | PER PLANS ALL DRAINAGE PIPING AND WATER SUPPLY PIPING | | | IN PLACE. NEW FIXTURES BEING ADDED OR RELOCATED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2009-05-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-06 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-05-06 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2009-05-06 13:00:37 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | CITY WPB MUNICIPAL CODE | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | | | | 4. SHT RE-1 ITEM 33 GLASS WASHER INDICATES 140 DEGREE | | | HOT WATER BUT SHOWS NO WATER CONNECTION. PLEASE | | | CLARIFY. SECTIONS 106.1.2 & 601.1. | | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED ON SHT RE-1 | | | TABLE. | | | | | | 5. OK | | | | | | 6. PLEASE CONTACT THE UTILITY DEPT, INDUSTRIAL | | | PRETREATMENT, ENVIRONMENTAL COMPLIANCE FOR THE REQUIRED | | | GREASE INTERCEPTOR. PLEASE CONTACT HOLLY MCGRATH, | | | LABORATORY SUPERVISOR TO DETERMINE THE SIZING OF THE | | | INTERCEPTOR AND TO DETERMINE THE PROPER OPERATION OF | | | THE EXISTING GREASE INTERCEPTOR(S). ARTICLE III, | | | SECTION 90-124(7). | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | 7. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE | | | FOLLOWING INFORMATION FOR REVIEW: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | ****RESPONSE, NOTED, COMMENT NOT ADDRESSED. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | ****RESPONSE NOTED, INFORMATION REQUIRED ON PLANS. | | | | | | D. OK | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. | | | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. | | | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT THE BTU LOAD FOR THE RANGE, | | | (120,000) DOES NOT REFLECT THE BTU LOAD ON SHT RE-2 GAS | | | APPLIANCE TABLE, (180,000). PLEASE CORRELATE. | | | | | | H. N/A | | | | | | I. N/A | | | | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****RESPONSE NOTED, TO BE SHOWN ON RISER DIAGRAM. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-03-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-03 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-03 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2009-03-03 12:17:21 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | CITY WPB MUNICIPAL CODE | | | | | | 1. ALL SHEETS SHALL CONTAIN THE CITY PLACE MANAGEMENT | | | STAMP AS REVIEWED AND SHALL BE INITIALED BY THE | | | REVIEWER. THIS IS A CITY PLACE REQUIREMENT. | | | | | | 2. ALL ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE | | | PERSON SEALING THE DOCUMENTS SHALL BE INDICATED IN THE | | | TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(6) & FS | | | 481.2055. | | | | | | 3. SHT T1.1 APPLICABLE CODES SHALL INCLUDE THE 2007 | | | REVISIONS. SECTION 106.1.1. | | | | | | 4. SHT RE-1 ITEM 33 GLASS WASHER INDICATES 140 DEGREE | | | HOT WATER BUT SHOWS NO WATER CONNECTION. PLEASE | | | CLARIFY. SECTIONS 106.1.2 & 601.1. | | | | | | 5. PLEASE SUBMIT PLUMBING PLANS FOR THE NEW WORK | | | INDICATED ON SHT RE-1 ITEMS 24, 25, 27 & 29. SUBMIT A | | | WATER RISER DIAGRAM SHOWING ALL PIPE SIZES, VALVES & | | | POINT OF CONNECTION TO THE EXISTING WATER SUPPLY | | | MAIN(S). SECTIONS 106.3.5.1.3 & 601.1. | | | | | | 6. PLEASE CONTACT THE UTILITY DEPT, INDUSTRIAL | | | PRETREATMENT, ENVIRONMENTAL COMPLIANCE FOR THE REQUIRED | | | GREASE INTERCEPTOR. PLEASE CONTACT HOLLY MCGRATH, | | | LABORATORY SUPERVISOR TO DETERMINE THE SIZING OF THE | | | INTERCEPTOR AND TO DETERMINE THE PROPER OPERATION OF | | | THE EXISTING GREASE INTERCEPTOR(S). ARTICLE III, | | | SECTION 90-124(7). | | | | | | 7. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE | | | FOLLOWING INFORMATION FOR REVIEW: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | H. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | I. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2009-09-22 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2009-09-22 |
Time |
15:10 |
Rev Time |
0.75 |
| Received By |
eschneid |
Date |
2009-09-22 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2009-09-22 15:51:25 | PASSED | | | | | | SIGNS AND AWNINGS REQUIRE SEPARATE PERMITS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2009-05-01 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2009-05-01 |
Time |
16:55 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2009-05-01 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2009-05-01 16:55:57 | PASSED | | | | | | SIGNS AND AWNINGS REQUIRE A SEPARATE PERMIT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-02-09 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2009-02-09 |
Time |
13:36 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2009-02-09 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2009-02-09 13:37:44 | FAILED | | | | | | 1) CITYPLACE STAMP IS REQUIRED ON ALL PLANS. | | | | | | 2) PLANS OK FOR ZONING ONCE STAMP PROVIDED. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|