Plan Review Details - Permit 09010415
Plan Review Stops For Permit 09010415
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-21 Cont ID  
Sent By rmcdouga Date 2009-04-21 Time 16:30 Rev Time 0.00
Received By rmcdouga Date 2009-04-21 Time 16:30 Sent To  
Notes
2009-04-21 16:32:21REVISION /SHOP DRAWING DETAILS FOR CONTINOUS LOAD PATH
 ARE OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-03-16 Cont ID  
Sent By rmcdouga Date 2009-03-16 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2009-03-16 Time 14:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-17 Cont ID  
Sent By rmcdouga Date 2009-02-17 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2009-02-17 Time 14:21 Sent To P
Notes
2009-02-17 16:36:012004 FBC W2007 REVISIONS
 LEVEL 3 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) ON SHEET SP-1 UNDER DESIGN CRITERIA A CHANGE WAS
 MADE BY TAPING A PIECE OF PAPER WITH 2006 NFPA-101 ON
 IT TO THE PLANS. THIS TYPE OF CORRECTION IS NOT
 ACCEPTABLE FOR SIGNED AND DRAWINGS. FS 481
  
 2) BASED ON THE SCOPE OF WORK FOR THIS PROJECT, IT IS
 CONSIDERED A LEVEL 3 ALTERATION. PLEASE SPECIFY THE
 LEVEL OF ALTERATION ON THE PLANS. FBC EXISTING BUILDING
 SECTION 305
  
 3) ON SHEET D-1 THE FIRST FLOOR DEMO PLAN DOES NOT
 INDICATE THAT THE EXISTING FOYER WALLS ARE BEING
 REMOVED. SHEET A-1 SPECIFIES NEW EXTERIOR WALLS AT THE
 FOYER. PLEASE REVISE.
  
 4) ON SHEET A-2 THE INTERIOR WALL AT BEDROOM #2 CLOSET
 AND THE HALL IS INCORRECTLY SPECIFIED AS AN (E) -
 EXISTING EXTERIOR WALL. PLEASE REVISE.
  
 5) ON SHEET A-3 THE NOTES SPECIFY CLOSING UP THE
 EXISTING GABLE VENTS ON THE INTERIOR. SHOW THAT
 COMPLIANCE WITH THE FOLLOWING WILL BE MAINTAINED.
 R806.1 VENTILATION REQUIRED. ENCLOSED ATTICS AND
 ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE
 APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF RAFTERS SHALL
 HAVE CROSS VENTILATION FOR EACH SEPARATE SPACE BY
 VENTILATING OPENINGS PROTECTED AGAINST THE ENTRANCE OF
 RAIN. VENTILATING OPENINGS SHALL BE PROVIDED WITH
 CORROSION-RESISTANT WIRE MESH, WITH 1/8 INCH (3.2 MM)
 MINIMUM TO ?? INCH (6.4 MM) MAXIMUM OPENINGS. 806.2
 MINIMUM AREA.THE TOTAL NET FREE VENTILATING AREA SHALL
 NOT BE LESS THAN 1 TO 150 OF THE AREA OF THE SPACE
 VENTILATED EXCEPT THAT THE TOTAL AREA IS PERMITTED TO
 BE REDUCED TO 1 TO 300, PROVIDED AT LEAST 50 PERCENT
 AND NOT MORE THAN 80 PERCENT OF THE REQUIRED
 VENTILATING AREA IS PROVIDED BY VENTILATORS LOCATED IN
 THE UPPER PORTION OF THE SPACE TO BE VENTILATED AT
 LEAST 3 FEET (914 MM) ABOVE EAVE OR CORNICE VENTS WITH
 THE BALANCE OF THE REQUIRED VENTILATION PROVIDED BY
 EAVE OR CORNICE VENTS. AS AN ALTERNATIVE, THE NET FREE
 CROSS-VENTILATION AREA MAY BE REDUCED TO 1 TO 300 WHEN
 A VAPOR BARRIER HAVING A TRANSMISSION RATE NOT
 EXCEEDING 1 PERM (57.4 MG/S ?? M2 ?? PA) IS INSTALLED
 ON THE WARM SIDE OF THE CEILING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-03-10 Cont ID  
Sent By btrobaug Date 2009-03-10 Time 14:15 Rev Time 0.00
Received By btrobaug Date 2009-03-10 Time 11:25 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-11 Cont ID  
Sent By btrobaug Date 2009-02-11 Time 15:32 Rev Time  
Received By btrobaug Date 2009-02-11 Time 10:56 Sent To P
Notes
2009-02-10 08:14:31 
  
 APPLICATION #09010415 ELECTRICAL PLAN REVIEW
 219 DYER ROAD 2/11/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE A PANEL SCHEDULE FOR THE METER/MAIN
 COMBINATION PANEL INCLUDING THE OVERCURRENT PROTECTION
 RATINGS.
  
 2} THIS COMMENT IS IN REGARD TO THE SINGLE GROUND ROD
 ON THE RISER DIAGRAM-SHEET E-1: 250.56 RESISTANCE OF
 ROD, PIPE, AND PLATE ELECTRODES:
 A SINGLE ELECTRODE CONSISTING OF A ROD, PIPE, OR PLATE
 THAT DOES NOT HAVE A RESISTANCE TO GROUND OF 25 OHMS OR
 LESS SHALL BE AUGMENTED BY ONE ADDITIONAL ELECTRODE OF
 ANY OF THE TYPES SPECIFIED BY 250.52(A)(2) THROUGH
 (A)(7). WHERE MULTIPLE ROD, PIPE, OR PLATE ELECTRODES
 ARE INSTALLED TO MEET THE REQUIREMENTS OF THIS SECTION,
 THEY SHALL NOT BE LESS THAN 1.8 M (6 FT) APART.***DUE
 TO SOIL RESISTANCE IN WEST PALM BEACH TWO GROUND RODS
 ARE COMMONLY USED, UNLESS THE CONTRACTOR CAN SHOW THE
 ELECTRICAL INSPECTOR HE/SHE CAN ATTAIN 25 OHMS OF
 RESISTANCE.
  
 3} THE EQUIPMENT GROUND RAN WITH THE FEEDERS TO PANEL
 ???B??? MUST BE A MINIMUM OF #6 CU PER 250.122. SHEET
 E-1 RISER DIAGRAM.
  
 4} THE MICROWAVE AND REFRIGERATOR IN THE KITCHEN, SHEET
 E-2, ARE SHOWN ON CIRCUIT #18 ON THE FLOOR PLAN. THIS
 IS A VIOLATION OF 210.23(A)(1) AND (2),- (1)
 ???CORD-AND-PLUG-CONNECTED EQUIPMENT NOT FASTENED IN
 PLACE THE RATING OF ANY ONE CORD-AND-PLUG-CONNECTED
 UTILIZATION EQUIPMENT NOT FASTENED IN PLACE SHALL NOT
 EXCEED 80 PERCENT OF THE BRANCH-CIRCUIT AMPERE RATING.
 (2) UTILIZATION EQUIPMENT FASTENED IN PLACE THE TOTAL
 RATING OF UTILIZATION EQUIPMENT FASTENED IN PLACE,
 OTHER THAN LUMINAIRES (LIGHTING FIXTURES), SHALL NOT
 EXCEED 50 PERCENT OF THE BRANCH-CIRCUIT AMPERE RATING
 WHERE LIGHTING UNITS, CORD-AND-PLUG-CONNECTED
 UTILIZATION EQUIPMENT NOT FASTENED IN PLACE, OR BOTH,
 ARE ALSO SUPPLIED.???
  
 5} THE MICROWAVE SHOWN ON THE FLOOR PLAN AND LISTED IN
 THE LOAD CALCULATION, IS NOT LISTED ON THE PANEL
 SCHEDULE. SEE COMMENT #4
  
 6} A SMOKE DETECTOR NEEDS TO BE ADDED IN THE 2ND FLOOR
 HALLWAY TO COMPLY WITH R313.1 2.???OUTSIDE EACH
 SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS.???
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
2009-02-09 15:34:38 
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-10 Cont ID  
Sent By adarroug Date 2009-04-10 Time 13:45 Rev Time 0.00
Received By adarroug Date 2009-04-10 Time 13:45 Sent To B
Notes
2009-04-10 13:45:52TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 10:26 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 10:26 Sent To E
Notes
2009-02-09 10:27:28TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-18 Cont ID  
Sent By kstevens Date 2009-02-18 Time 08:43 Rev Time 0.00
Received By kstevens Date 2009-01-28 Time 15:50 Sent To  
Notes
2009-01-28 15:50:22TO "SFR" "Z"

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-02-18 Cont ID  
Sent By kstevens Date 2009-02-18 Time 08:43 Rev Time 0.00
Received By kstevens Date 2009-02-18 Time 08:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-02-06 Cont ID  
Sent By mcruz Date 2009-02-06 Time 13:24 Rev Time 0.00
Received By mcruz Date 2009-02-06 Time 13:18 Sent To I
Notes
2009-02-06 13:24:03*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  