Plan Review Details - Permit 09010408
Plan Review Stops For Permit 09010408
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-07-10 Cont ID  
Sent By rmcdouga Date 2009-07-10 Time 09:37 Rev Time 0.00
Received By rmcdouga Date 2009-07-10 Time 09:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-04-08 Cont ID  
Sent By rmcdouga Date 2009-04-08 Time 14:01 Rev Time 0.00
Received By rmcdouga Date 2009-04-08 Time 14:01 Sent To  
Notes
2009-04-08 14:49:542004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) CORRECTIONS HAVE BEEN MADE TO SHEET 2 OF THE PLANS
 BY USING WHITE-OUT. THIS IS NOT ALLOWED TO BE DONE TO
 SIGNED AND SEALED DRAWINGS. FS 471 AND FBC 106.1.3*
 CITY AMENDMENTS. SEE PREVIOUS COMMENTS #S 1, 2 AND 3.
  
 2) THE R-VALUE OF THE WALL INSULATION ON SHEET 2 HAS
 BEEN CHANGED TO R-19. THE PLANS SPECIFY 2 X 4 WOOD
 FRAME WALLS, THEREFORE ONLY 3-1/2" INSULATION WITH
 R-11CAN BE CORRECTLY INSTALLED. PLEASE CORRECT PLANS
 AND REVISE ENERGY CALCULATIONS. FBC 11-600. CHANGES TO
 SIGNED AND SEALED DRAWINGS ARE REQUIRED TO BE MADE BY
 THE RESPONSIBLE DESIGN PROFESSIONAL. FS 471.
  
 3) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM. THE FORM INCORRECTLY SPECIFIES R-19
 INSULATION IN THE 2 X 4 EXTERIOR WALLS ( PER PLANS) AND
 THE PROJECT IS AN EXISTING STRUCTURE. PLEASE COORDINATE
 THE FORM WITH THE PLANS AND MAKE CORRECTIONS. FBC
 11-600. SEE PREVIOUS COMMENT #4.
  
 NOTE: REMOVE THE OLD SHEETS FROM THE PLANS AND REPLACE
 WITH THE NEW ONES. LEAVE THE SHEETS THAT HAVE BEEN
 APPROVED AND STAMPED IN THE PLANS, SO THAT THERE IS TWO
 COMPLETE SETS. THE OLD SHEETS THAT WERE REMOVED CAN BE
 SUBMITTED FOR REFERENCE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-10 Cont ID  
Sent By rmcdouga Date 2009-02-10 Time 16:41 Rev Time 0.00
Received By rmcdouga Date 2009-02-10 Time 16:41 Sent To M
Notes
2009-02-10 16:41:032004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) ON SHEET 2 OF THE PLANS THE LEVEL OF ALTERATION IS
 INCORRECTLY SPECIFIED AS LEVEL 1. PLEASE CHANGE TO
 LEVEL 2. SEE 2004 FBC EXISTING BUILDING SECTION 304.
  
 2) UNDER DESIGN PARAMETERS ON SHEET 2 ASCE7-05 IS
 INCORRECTLY REFERENCED. THE CORRECT REFERENCE FOR THE
 2004 FBC IS ASCE7-02. PLEASE CORRECT.
  
 3) THE BATHROOM WINDOWS ARE REQUIRED TO HAVE SAFETY
 GLAZING BY FBC R308.4 WHERE THE BOTTOM EDGE OF THE
 GLAZING IS LESS THAN 60 INCHES ABOVE ANY STANDING OR
 WALKING SURFACE. SPECIFY SAFETY GLAZING ON PLANS OR
 SHOW THAT WINDOWS ARE 60 INCHES ABOVE TUB OR SHOWER
 FLOORS.
  
 4) THE ENERGY CALCULATION FORM THAT WAS SUBMITTED
 CONTAINS SEVERAL ERRORS AND IS NOT SIGNED BY THE
 OWNER/AGENT. ENERGY CALCULATIONS ARE NOT REQUIRED TO BE
 SUBMITTED WHEN THE RENOVATION COST IS LESS THAN 30 PER
 CENT OF THE ASSESSED VALUE OF THE STRUCTURE WHICH
 APPLIES TO THIS JOB. HOWEVER, THE COMPONENTS BEING
 INSTALLED ARE REQUIRED TO MEET THE PRESCRIPTIVE
 REQUIREMENTS OF METHOD C. 13-101.2.3 RENOVATIONS.
 RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION
 202), MEET THE PRESCRIPTIVE REQUIREMENTS CONTAINED IN
 METHOD C OF SUBCHAPTER 13-6 FOR RESIDENTIAL
 APPLICATIONS OF THE CODE FOR INSULATION, HVAC SYSTEMS,
 LIGHTING, WATER HEATING SYSTEMS AND EXTERIOR ENVELOPE
 FOR THOSE COMPONENTS BEING RETROFITTED OR REPLACED.
  
 5) SPECIFY THE FASTENING OPTION THAT WILL BE USED TO
 INSTALL THE STORM PANELS. MARK THE APPROPRIATE ITEM ON
 THE TABLE ON SHEET 3 OF NOA NO. 06-1012.05 INSTALLATION
 DRAWINGS.
  
 6) THE PRODUCT APPROVALS FOR THE STORM PANELS ARE
 REQUIRED TO BE APPROVED IN WRITING BY THE DESIGNER OF
 RECORD.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-06-22 Cont ID  
Sent By btrobaug Date 2009-06-22 Time 14:52 Rev Time 0.00
Received By btrobaug Date 2009-06-22 Time 14:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-04-07 Cont ID  
Sent By btrobaug Date 2009-04-07 Time 12:59 Rev Time 0.00
Received By btrobaug Date 2009-04-07 Time 12:08 Sent To B
Notes
2009-04-07 12:59:54 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 THESE COMMENTS ARE GENERATED FROM SHEET #4.
 THESE ARE REPEAT COMMENTS THAT WERE NOT RESPONDED TO.
 SUBMIT WRITTEN RESPONSE TO THE COMMENTS MADE IN THIS
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC,
 106.3.5.4 FBC AS AMENDED.*** THE "LOAD CALCULATION"
 SUBMITTED WITH SOME WIRE AND BREAKER SIZES IS
 INCOMPLETE. THERE ARE BATH CIRCUITS PER 210.11(C)(3),
 ARC FAULT CIRCUITS PER 210.12 AND DINING ROOM
 RECEPTACLE CIRCUITS PER 210.52(B)(1) MISSING FOR
 EXAMPLE. SEE 408.4 NEC. INDICATE THE RATING OF THE
 EXISTING SERVICE. 215.5 NEC.
  
 3} IF THE PANEL SHOWN ON THE PLAN IS NEW, INDICATE THE
 DISCONNECTING MEANS (PROVIDE A RISER DIAGRAM) PER
 230.70 NEC.
  
 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(C), ONE MUST BE ADDED FOR SPACING REQUIREMENTS
 .NEXT TO THE RANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-10 Cont ID  
Sent By btrobaug Date 2009-02-10 Time 15:14 Rev Time 0.00
Received By btrobaug Date 2009-02-10 Time 13:54 Sent To M
Notes
2009-02-10 15:14:14 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 THESE COMMENTS ARE GENERATED FROM SHEET #4.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC,
 106.3.5.4 FBC AS AMENDED.*** THE "LOAD CALCULATION"
 SUBMITTED WITH SOME WIRE AND BREAKER SIZES IS
 INCOMPLETE. THERE ARE BATH CIRCUITS PER 210.11(C)(3),
 ARC FAULT CIRCUITS PER 210.12 AND DINING ROOM
 RECEPTACLE CIRCUITS PER 210.52(B)(1) MISSING FOR
 EXAMPLE. SEE 408.4 NEC. INDICATE THE RATING OF THE
 EXISTING SERVICE. 215.5 NEC.
  
 3} IF THE PANEL SHOWN ON THE PLAN IS NEW, INDICATE THE
 DISCONNECTING MEANS (PROVIDE A RISER DIAGRAM) PER
 230.70 NEC.
  
 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(C), ONE MUST BE ADDED FOR SPACING REQUIREMENTS
 .NEXT TO THE RANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-06-18 Cont ID  
Sent By lmartine Date 2009-06-12 Time 15:58 Rev Time 0.00
Received By lmartine Date 2009-06-12 Time 15:58 Sent To  
Notes
2009-06-18 15:59:12R-15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-30 Cont ID  
Sent By adarroug Date 2009-03-30 Time 11:49 Rev Time 0.00
Received By adarroug Date 2009-03-30 Time 11:49 Sent To  
Notes
2009-03-30 11:52:29TO "R4"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-12 Cont ID  
Sent By lmartine Date 2009-02-12 Time 16:43 Rev Time 0.00
Received By lmartine Date 2009-01-28 Time 11:18 Sent To  
Notes
2009-01-28 11:18:33TO "SFR " "E"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-10 Cont ID  
Sent By rmcdouga Date 2009-07-10 Time 09:36 Rev Time 0.00
Received By rmcdouga Date 2009-07-10 Time 09:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-02-11 Cont ID  
Sent By rregueir Date 2009-02-11 Time 16:22 Rev Time 0.00
Received By rregueir Date 2009-02-11 Time 16:22 Sent To P
Notes
2009-02-11 16:27:19REVISE PLAN TO SHOW MISSING DUCT SIZE. SEE REDLINE
 NOTES ON PLAN.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-07-10 Cont ID  
Sent By rmcdouga Date 2009-07-10 Time 09:36 Rev Time 0.00
Received By rmcdouga Date 2009-07-10 Time 09:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-02-12 Cont ID  
Sent By lwagner Date 2009-02-12 Time 09:48 Rev Time 0.00
Received By lwagner Date 2009-02-12 Time 08:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2009-06-25 Cont ID  
Sent By mcruz Date 2009-06-25 Time 16:34 Rev Time 0.00
Received By mcruz Date 2009-06-25 Time 16:30 Sent To  
Notes
2009-06-25 16:35:04PLACED IN R15

Review Stop Z ZONING
Rev No 2 Status P Date 2009-06-25 Cont ID  
Sent By mcruz Date 2009-04-06 Time 16:30 Rev Time 0.00
Received By mcruz Date 2009-04-06 Time 10:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-13 Cont ID  
Sent By mcruz Date 2009-02-13 Time 08:53 Rev Time 0.00
Received By mcruz Date 2009-02-13 Time 08:49 Sent To  
Notes
2009-02-13 08:52:49PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDR), SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY
 NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 NOTE: PURSUANT TO THE ZLDR, SECTION 94-72(A)(2):
 SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT -
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET;
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  