| Plan Review Stops For Permit 09010408 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-07-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-07-10 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-07-10 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-04-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-04-08 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-04-08 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2009-04-08 14:49:54 | 2004 FBC W/2007 REVISIONS | | | LEVEL 2 ALTERATIONS | | | | | | DENIED BY BUILDING | | | | | | 1) CORRECTIONS HAVE BEEN MADE TO SHEET 2 OF THE PLANS | | | BY USING WHITE-OUT. THIS IS NOT ALLOWED TO BE DONE TO | | | SIGNED AND SEALED DRAWINGS. FS 471 AND FBC 106.1.3* | | | CITY AMENDMENTS. SEE PREVIOUS COMMENTS #S 1, 2 AND 3. | | | | | | 2) THE R-VALUE OF THE WALL INSULATION ON SHEET 2 HAS | | | BEEN CHANGED TO R-19. THE PLANS SPECIFY 2 X 4 WOOD | | | FRAME WALLS, THEREFORE ONLY 3-1/2" INSULATION WITH | | | R-11CAN BE CORRECTLY INSTALLED. PLEASE CORRECT PLANS | | | AND REVISE ENERGY CALCULATIONS. FBC 11-600. CHANGES TO | | | SIGNED AND SEALED DRAWINGS ARE REQUIRED TO BE MADE BY | | | THE RESPONSIBLE DESIGN PROFESSIONAL. FS 471. | | | | | | 3) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | CALCULATION FORM. THE FORM INCORRECTLY SPECIFIES R-19 | | | INSULATION IN THE 2 X 4 EXTERIOR WALLS ( PER PLANS) AND | | | THE PROJECT IS AN EXISTING STRUCTURE. PLEASE COORDINATE | | | THE FORM WITH THE PLANS AND MAKE CORRECTIONS. FBC | | | 11-600. SEE PREVIOUS COMMENT #4. | | | | | | NOTE: REMOVE THE OLD SHEETS FROM THE PLANS AND REPLACE | | | WITH THE NEW ONES. LEAVE THE SHEETS THAT HAVE BEEN | | | APPROVED AND STAMPED IN THE PLANS, SO THAT THERE IS TWO | | | COMPLETE SETS. THE OLD SHEETS THAT WERE REMOVED CAN BE | | | SUBMITTED FOR REFERENCE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-02-10 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-02-10 |
Time |
16:41 |
Sent To |
M |
|
| Notes |
| 2009-02-10 16:41:03 | 2004 FBC W/2007 REVISIONS | | | LEVEL 2 ALTERATION | | | | | | DENIED BY BUILDING | | | | | | 1) ON SHEET 2 OF THE PLANS THE LEVEL OF ALTERATION IS | | | INCORRECTLY SPECIFIED AS LEVEL 1. PLEASE CHANGE TO | | | LEVEL 2. SEE 2004 FBC EXISTING BUILDING SECTION 304. | | | | | | 2) UNDER DESIGN PARAMETERS ON SHEET 2 ASCE7-05 IS | | | INCORRECTLY REFERENCED. THE CORRECT REFERENCE FOR THE | | | 2004 FBC IS ASCE7-02. PLEASE CORRECT. | | | | | | 3) THE BATHROOM WINDOWS ARE REQUIRED TO HAVE SAFETY | | | GLAZING BY FBC R308.4 WHERE THE BOTTOM EDGE OF THE | | | GLAZING IS LESS THAN 60 INCHES ABOVE ANY STANDING OR | | | WALKING SURFACE. SPECIFY SAFETY GLAZING ON PLANS OR | | | SHOW THAT WINDOWS ARE 60 INCHES ABOVE TUB OR SHOWER | | | FLOORS. | | | | | | 4) THE ENERGY CALCULATION FORM THAT WAS SUBMITTED | | | CONTAINS SEVERAL ERRORS AND IS NOT SIGNED BY THE | | | OWNER/AGENT. ENERGY CALCULATIONS ARE NOT REQUIRED TO BE | | | SUBMITTED WHEN THE RENOVATION COST IS LESS THAN 30 PER | | | CENT OF THE ASSESSED VALUE OF THE STRUCTURE WHICH | | | APPLIES TO THIS JOB. HOWEVER, THE COMPONENTS BEING | | | INSTALLED ARE REQUIRED TO MEET THE PRESCRIPTIVE | | | REQUIREMENTS OF METHOD C. 13-101.2.3 RENOVATIONS. | | | RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION | | | 202), MEET THE PRESCRIPTIVE REQUIREMENTS CONTAINED IN | | | METHOD C OF SUBCHAPTER 13-6 FOR RESIDENTIAL | | | APPLICATIONS OF THE CODE FOR INSULATION, HVAC SYSTEMS, | | | LIGHTING, WATER HEATING SYSTEMS AND EXTERIOR ENVELOPE | | | FOR THOSE COMPONENTS BEING RETROFITTED OR REPLACED. | | | | | | 5) SPECIFY THE FASTENING OPTION THAT WILL BE USED TO | | | INSTALL THE STORM PANELS. MARK THE APPROPRIATE ITEM ON | | | THE TABLE ON SHEET 3 OF NOA NO. 06-1012.05 INSTALLATION | | | DRAWINGS. | | | | | | 6) THE PRODUCT APPROVALS FOR THE STORM PANELS ARE | | | REQUIRED TO BE APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2009-06-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-06-22 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-06-22 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2009-04-07 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-04-07 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-04-07 |
Time |
12:08 |
Sent To |
B |
|
| Notes |
| 2009-04-07 12:59:54 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | THESE COMMENTS ARE GENERATED FROM SHEET #4. | | | THESE ARE REPEAT COMMENTS THAT WERE NOT RESPONDED TO. | | | SUBMIT WRITTEN RESPONSE TO THE COMMENTS MADE IN THIS | | | REVIEW. | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 | | | FS, RESPECTIVELY. | | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | | IF EXEMPTIONS APPLY. | | | | | | 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT | | | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT | | | PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, | | | 106.3.5.4 FBC AS AMENDED.*** THE "LOAD CALCULATION" | | | SUBMITTED WITH SOME WIRE AND BREAKER SIZES IS | | | INCOMPLETE. THERE ARE BATH CIRCUITS PER 210.11(C)(3), | | | ARC FAULT CIRCUITS PER 210.12 AND DINING ROOM | | | RECEPTACLE CIRCUITS PER 210.52(B)(1) MISSING FOR | | | EXAMPLE. SEE 408.4 NEC. INDICATE THE RATING OF THE | | | EXISTING SERVICE. 215.5 NEC. | | | | | | 3} IF THE PANEL SHOWN ON THE PLAN IS NEW, INDICATE THE | | | DISCONNECTING MEANS (PROVIDE A RISER DIAGRAM) PER | | | 230.70 NEC. | | | | | | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(C), ONE MUST BE ADDED FOR SPACING REQUIREMENTS | | | .NEXT TO THE RANGE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-02-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-02-10 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-02-10 |
Time |
13:54 |
Sent To |
M |
|
| Notes |
| 2009-02-10 15:14:14 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | THESE COMMENTS ARE GENERATED FROM SHEET #4. | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 | | | FS, RESPECTIVELY. | | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | | IF EXEMPTIONS APPLY. | | | | | | 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT | | | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT | | | PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, | | | 106.3.5.4 FBC AS AMENDED.*** THE "LOAD CALCULATION" | | | SUBMITTED WITH SOME WIRE AND BREAKER SIZES IS | | | INCOMPLETE. THERE ARE BATH CIRCUITS PER 210.11(C)(3), | | | ARC FAULT CIRCUITS PER 210.12 AND DINING ROOM | | | RECEPTACLE CIRCUITS PER 210.52(B)(1) MISSING FOR | | | EXAMPLE. SEE 408.4 NEC. INDICATE THE RATING OF THE | | | EXISTING SERVICE. 215.5 NEC. | | | | | | 3} IF THE PANEL SHOWN ON THE PLAN IS NEW, INDICATE THE | | | DISCONNECTING MEANS (PROVIDE A RISER DIAGRAM) PER | | | 230.70 NEC. | | | | | | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(C), ONE MUST BE ADDED FOR SPACING REQUIREMENTS | | | .NEXT TO THE RANGE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-06-18 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-06-12 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-06-12 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-03-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-03-30 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-03-30 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2009-03-30 11:52:29 | TO "R4" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-02-12 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-02-12 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-01-28 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2009-01-28 11:18:33 | TO "SFR " "E" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-07-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-07-10 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-07-10 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2009-02-11 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-02-11 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-02-11 |
Time |
16:22 |
Sent To |
P |
|
| Notes |
| 2009-02-11 16:27:19 | REVISE PLAN TO SHOW MISSING DUCT SIZE. SEE REDLINE | | | NOTES ON PLAN. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2009-07-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-07-10 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-07-10 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2009-02-12 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2009-02-12 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2009-02-12 |
Time |
08:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2009-06-25 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-06-25 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-06-25 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2009-06-25 16:35:04 | PLACED IN R15 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2009-06-25 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-04-06 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-04-06 |
Time |
10:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-02-13 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-02-13 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-02-13 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2009-02-13 08:52:49 | PLANNING AND ZONING DEPT: ***ZONING FAILED*** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | | INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. | | | | | | 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C | | | EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE CITY OF | | | WEST PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS | | | (ZLDR), SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY | | | NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | | | | NOTE: PURSUANT TO THE ZLDR, SECTION 94-72(A)(2): | | | SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT - | | | MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS: | | | | | | A. FRONT: 25 FEET; | | | | | | B. CORNER: 12.5 FEET; | | | | | | C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER | | | IS LESS; | | | | | | D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL. | | | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | |
|
|