| 2009-02-06 08:54:09 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SECTION 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS, SPECIAL INSPECTION AND STRUCTURAL |
| | OBSERVATION PROGRAMS, AND OTHER DATA SHALL BE SUBMITTED |
| | IN TWO OR MORE SETS WITH EACH APPLICATION FOR A PERMIT. |
| | ONLY TWO SETS OF PLANS WERE SUBMITTED WITH TWO PERMIT |
| | APPLICATIONS. EITHER SUBMIT 2 SETS WITH EACH |
| | APPLICATION, OR APPLY FOR ALL WORK ON ONE APPLICATION. |
| | |
| | 2. SHT A-1.0 APPLICABLE CODES TO INCLUDE THE 2007 |
| | AMENDMENTS TO THE FBC-2004 PLUMBING AND INCLUDE |
| | FBC-2004 BUILDING CODE W/2007 AMENDMENTS. |
| | |
| | 3. SHTS P-1.0 & P-2.0 SHOW DRINKING FOUNTAINS TO THE |
| | RIGHT OF THE CENTER STAIRS/ELEVATORS. WILL THESE |
| | DRINKING FOUNTAINS REMAIN? PLEASE CLARIFY. SECTION |
| | 106.2.1. MORE INFORMATION IS REQUIRED. IF DELETING THE |
| | EXISTING DRINKING FOUNTAINS, IN THE REMOVAL OF ANY PART |
| | OF A DRAINAGE SYSTEM, DEAD ENDS ARE PROHIBITED. SECTION |
| | 704.5. |
| | |
| | 4. INFORMATIONAL: A SEPARATE PLUMBING PERMIT IS |
| | REQUIRED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |