Plan Review Details - Permit 09010363
Plan Review Stops For Permit 09010363
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-01 Cont ID  
Sent By shill Date 2009-04-01 Time 15:56 Rev Time 0.00
Received By shill Date 2009-04-01 Time 15:56 Sent To  
Notes
2009-04-01 15:56:36PROVISO - CONTR TO PROVIDE EVIDENCE @ INSPECTION,
 FORMED & POURED TIE BEAM AT TOP CONNECTION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-03-24 Cont ID  
Sent By shill Date 2009-03-24 Time 16:24 Rev Time 0.00
Received By shill Date 2009-03-24 Time 16:24 Sent To  
Notes
2009-03-24 16:39:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SHEET 14, CONCRETE TO BE MINIMUM F'C = 3KSI. PLEASE
 PROVIDE EVIDENCE THAT THE CONCRETE MEETS THIS
 REQUIREMENT, OR A SITE SPECIFIC FROM THE ENGINEER
 ADDRESSING THIS ISSUE, ESPECIALLY AS A RESIDENTIAL
 CONCRETE SLAB IS USUALLY 2500PSI. FBC16
  
 2ND REVIEW, A LETTER FROM A DESIGN PROFESSIONAL WAS
 SUBMITTED WHICH DUPLICATED FBC TABLE 1904.2.2. IT IS
 NOT CLEAR WHY THIS WAS SUBMITTED, FOR THE FOLLOWING
 REASONS:
  
 A. THIS HOUSE WAS NOT CONSTRUCTED UNDER FBC2007, SO
 THIS TABLE WOULD NOT BE INDICATIVE OF HOW THIS
 STRUCTURE WAS BUILT.
  
 B. AN AREA WITH "NEGLIGIBLE EXPOSURE" REQUIRES 2500PSI.
 PLEASE SEE THE MAP ASSOCIATED WITH FBC TABLE 1904.2.2;
 FLORIDA IS IN A "NEGLIGIBLE EXPOSURE" AREA, SO MINIMUM
 DESIGN STRENGTH UNDER CURRENT CODE IS 2500PSI. THE
 PRODUCT APPROVAL SUBMITTED REQUIRES 3000PSI TO USE
 ANCHOR SPACING FOR CONCRETE SUBSTRATE.
  
 2. PLEASE CONTACT ME BY TELEPHONE IF YOU WISH TO
 DISCUSS OPTIONS TO GET THIS MATTER RESOLVED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-27 Cont ID  
Sent By shill Date 2009-01-27 Time 09:58 Rev Time 0.00
Received By shill Date 2009-01-27 Time 09:58 Sent To  
Notes
2009-01-27 10:01:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SHEET 14, CONCRETE TO BE MINIMUM F'C = 3KSI. PLEASE
 PROVIDE EVIDENCE THAT THE CONCRETE MEETS THIS
 REQUIREMENT, OR A SITE SPECIFIC FROM THE ENGINEER
 ADDRESSING THIS ISSUE, ESPECIALLY AS A RESIDENTIAL
 CONCRETE SLAB IS USUALLY 2500PSI. FBC16
  
 2. OPENINGS 1-7,EDGE DISTANCE OF 3 1/4" SPECIFIED ON
 INSTALLATION SCHEDULE. SEE SHEET 14, FACTOR MUST BE
 APPLIED TO ANCHOR SPACING WHEN EDGE DISTANCE IS LESS
 THAN 3 1/2".FBC1609
  
 3. SEE OPENING 14. IF THE EDGE DISTANCE AT THE TOP IS 3
 1/2", IT IS NOT CLEAR HOW YOU'VE ARRIVED AT SPAN.
 PLEASE PROVIDE AN EXPLANATION. FBC1609
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-16 Cont ID  
Sent By adarroug Date 2009-03-16 Time 10:46 Rev Time 0.00
Received By adarroug Date 2009-03-16 Time 10:46 Sent To B
Notes
2009-03-16 10:47:10TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-27 Cont ID  
Sent By shill Date 2009-01-27 Time 10:01 Rev Time 0.00
Received By shill Date 2009-01-26 Time 16:37 Sent To  
Notes
2009-01-26 16:38:16TO "MISC" BOX#1