Plan Review Details - Permit 09010361
Plan Review Stops For Permit 09010361
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-03-06 Cont ID  
Sent By rmcdouga Date 2009-03-06 Time 15:09 Rev Time 0.00
Received By rmcdouga Date 2009-03-06 Time 15:09 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-04 Cont ID  
Sent By rmcdouga Date 2009-02-04 Time 14:42 Rev Time 0.00
Received By rmcdouga Date 2009-02-04 Time 11:45 Sent To  
Notes
2009-02-04 15:05:292004 FBC W/2007 REVISIONS
 CHILLER REPLACEMENT
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) A BUILDING OR GENERAL CONTRACTOR WILL BE REQUIRED
 FOR THE SCOPE OF WORK INVOLVING THE CUTTING AND
 PATCHING OF THE CONCRETE ROOF SLAB, THE ASPHALT
 PAVEMENT AND SIDEWALK. FS 489
  
 3) ADDITIONAL INFORMATION MAY BE REQUIRED DEPENDING ON
 THE EXTENT AND TYPE OF THE ROOF REPAIRS. FBC EXISTING
 BUILDING 401.3 AND 511.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-03-10 Cont ID  
Sent By btrobaug Date 2009-03-10 Time 09:33 Rev Time 0.00
Received By btrobaug Date 2009-03-10 Time 09:33 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-03-06 Cont ID  
Sent By btrobaug Date 2009-02-26 Time 15:46 Rev Time 0.00
Received By btrobaug Date 2009-02-26 Time 15:31 Sent To M
Notes
2009-02-26 15:46:05 
  
  
 APPLICATION #09010361 ELECTRICAL PLAN REVIEW
 1525 PALM BEACH LAKES BLVD 1/30/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW WITH NO
 CHANGES OR RESPONSE:
  
 1} SHEET E-5 ONE LINE POWER DIAGRAM-NEW WORK DOES NOT
 INDICATE THE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR
 CIRCUITS 6, 7, AND 8 FOR THE NEW EQUIPMENT, LABEL
 SAME.215.5 NEC.
  
 2} AS THE MAIN BONDING JUMPER IS SHOWN IN MSBD (SAME
 DIAGRAM AS ABOVE) INDICATE HOW THE EQUIPMENT MENTIONED
 IN COMMENT #1 WILL BE BONDED PER 250.96(A), CONDUIT OR
 EQUIPMENT GROUNDING CONDUCTOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-03 Cont ID  
Sent By btrobaug Date 2009-02-03 Time 16:21 Rev Time 0.00
Received By btrobaug Date 2009-01-29 Time 06:38 Sent To M
Notes
2009-02-03 16:22:18 
  
  
 APPLICATION #09010361 ELECTRICAL PLAN REVIEW
 1525 PALM BEACH LAKES BLVD 1/30/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET E-5 ONE LINE POWER DIAGRAM-NEW WORK DOES NOT
 INDICATE THE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR
 CIRCUITS 6, 7, AND 8 FOR THE NEW EQUIPMENT, LABEL
 SAME.215.5 NEC.
  
 2} AS THE MAIN BONDING JUMPER IS SHOWN IN MSBD (SAME
 DIAGRAM AS ABOVE) INDICATE HOW THE EQUIPMENT MENTIONED
 IN COMMENT #1 WILL BE BONDED PER 250.96(A), CONDUIT OR
 EQUIPMENT GROUNDING CONDUCTOR.
  
 3} SHEET E-1 IN THE GENERAL ELECTRICAL NOTES #1,
 REFERENCE THE CODES IN EFFECT UNDER THIS PERMIT, SEE
 REVIEW CYCLES ABOVE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-08 Cont ID  
Sent By adarroug Date 2009-04-08 Time 13:26 Rev Time 0.00
Received By adarroug Date 2009-04-08 Time 13:26 Sent To M
Notes
2009-04-08 13:26:48TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-20 Cont ID  
Sent By adarroug Date 2009-02-20 Time 10:42 Rev Time 0.00
Received By adarroug Date 2009-02-20 Time 10:42 Sent To E
Notes
2009-02-20 10:42:39TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-04 Cont ID  
Sent By rmcdouga Date 2009-02-04 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2009-01-27 Time 10:38 Sent To  
Notes
2009-01-27 10:38:55TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-08-05 Cont ID  
Sent By rregueir Date 2009-08-05 Time 15:25 Rev Time 0.00
Received By rregueir Date 2009-08-05 Time 15:24 Sent To PC
Notes
2009-08-05 15:25:18PAGE M-10 REVISION DELTA 1 **PROVISO**
  
 NEED ENGINEERING DETAIL FOR ATTACHMENT OF EXPANSION
 TANK TO SLAB FOR WIND RESISTANCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-04-16 Cont ID  
Sent By rregueir Date 2009-04-16 Time 09:16 Rev Time 0.00
Received By rregueir Date 2009-04-16 Time 08:51 Sent To PC
Notes
2009-04-16 09:16:26REVISED M-6, M-8, M-16, M-18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-03-09 Cont ID  
Sent By rregueir Date 2009-03-09 Time 18:04 Rev Time 0.00
Received By rregueir Date 2009-03-09 Time 18:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-02-03 Cont ID  
Sent By btrobaug Date 2009-03-06 Time 14:31 Rev Time 0.00
Received By rregueir Date 2009-02-03 Time 20:13 Sent To B
Notes
2009-02-03 20:56:35REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PROVIDE DETAIL FOR INSTALLATION AND ATTACHMENT OF ROOF
 CURB AND VENTILATOR. SHOW THESE THINGS DESIGNED AND
 INSTALLED FOR WIND RESISTANCE IN ACCORDANCE WITH FBCM
 301.13.
  
 MECHANICAL PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]